Gordiano villiage

Operation & Maintenance


Training for
FM 200 suppression system in Gordiano village

3
WHAT IS FIRE …………

4
 FM-200® is a colorless, liquefied
compressed gas. –
Heptafluoropropane
 It is stored as a liquid and dispensed
into the hazard as a colorless,
eclectically non-conductive vapor
 It is clear and does not obscure vision.
 FM-200® does not displace oxygen
 It is safer for use in occupied spaces
without fear of oxygen deprivation

5
6
PROTECTED AREAS

7
What Is A Total Flooding Fire
Suppression System?

Detect

Control

Suppression

8
 SMOKE
DETECTORS

 REMOTE ALARM
INDICATORS

 MANUAL RELEASE
STATION
 ABORT SWITCH

9
 Working in a cross
Zone Scenario.
 Covering range –84
Sq.m
 Activation information
by local Led indication
on the detector

10
 Unseen area smoke
detector Indication
!!! (Below floor ,
Upper floor and
Trenches )

11
 Manual
Operation….
incase of Fire !!!
 Direct discharge
of FM200 gas in
protected area –
With out any
time delay
 Do not try to
reset ….( Only
trained person )

12
ELECTRIC CONTROL HEAD

13
 Remove The
Safety Tag and
Pull the Lever ..To
activate the
System Manually

14
SYSTEM OPERATION: 1ST STAGE

Activation of any of the detector in either


circuit will cause…..
 Alarm Indication on the FMCP with custom
LED for proper zone indication.
 Alarm bell will ring inside the protected
area (First Stage)

 Fire indication signal to building fire alarm system

15
 INDICATION OF
FIRST STAGE OF
SMOKE
DETECTION

16
 Find the Area-
Where You got
the
Alarm…………….
 Inform Health &
Safety Dept.
 call 999 (Fire
Dept.)
 Close the Door &
move to Master
point

17
SYSTEM OPERATION: 2ND STAGE

Activation of a Second Detector (Cross


Zoned) in the other circuit will cause.
 Predischarge indication on FMCP with
custom LED for proper zone indication.
 Horn/Strobe Alarm will activate (Second
Stage)
 Starts countdown of Set Time Delay
 Fire indication signal to building fire alarm system
 Signal to close Fire Damper/AC Unit.
4

18
 Actual Fire
Indication.
Ready to Vacate
the Area !!!!!
After 30 Sec. FM
Gas will
Discharge……….

19
 Inform Health &
Safety Dept.
 Call. 66633188 - 44897362
 Dial 999 To Fire
Department.
 Close the Door & Go
to Master Point
 If found it is false
alarm & its required
to stop the novec
1230 Discharge
!!!!!!!! Press & Hold
Abort Switch

20
 Press & Hold !!!!

ACTION…
 Stop the FM 200
GAS discharging
 Hold Until reset
the panel
 With out resetting
the panel it will
cause to start
again 30 Sec. time
count.

21
How to reset the panel

 Find the Fault


 Rectify the Fault
 Press the Acknowledge
Button
 Press the reset Button

22
SYSTEM OPERATION: 3RD STAGE

At the end of Set Time Delay.


Activation of circuit to release HFC 227ea
into the protected area.
Release indication on the FACP and
display custom LED for discharge
indication.
Activation of Strobe light visual indicator
outside the hazard area.

23
 Indication Of
FM200 Gas
Discharge…
 Do not enter
with out
Authorization.

24
25
26
27
Maintenance Requirements for Fire
Suppression System

Daily Maintenance (End-user)

• Check cylinder pressure

28
Monthly Maintenance

• Performed by end-user (typically)


– Ensure access to hazard areas,
manual pull stations, abort switches
and cylinders are unobstructed
– Check cylinder
– Check for missing or damaged
equipment
• Check nozzles for dirt, damage or obstructions
• Check flex hoses for loose fitting or damage
• Check control heads for connection to cylinders

29
Semi-Annual Inspection
(To Be Performed by Trained Person)
• Inspect system for missing or damaged equipment
• Test system for proper operation
– Control Panel functions
– Detectors, aborts, pull stations, control heads and
notification appliances
– Pressure switches and auxiliary connections
– Check for proper sequence of operation and time
delays
- Test all detection and control devices as per NFPA 72

30