“AIR TO WATER CONVERTER”
THDC-IHET, B-PURAM,TEHRI-GARHWAL
UTTARAKHAND
PRESENTED BY:
1. RITESH KUKRETI (160970104042)
2. SANJAY BASERA (160970104045)
3. SHUBHAM SINGH GUSAIN (160970104049)
4. SHUBHAM SURKALI(160970104050)
5. SURAJ CHANDRA CHANDOLA (160970104058)
6. PAVAN PUNDIR (670970104008)
PROJECT GUIDE:
MR. HIMANSHU NAUTIYAL
PRESENTATION FLOW:
1. INTRODUCTION
2. MONTHLY PLAN
3. WORKING PRINCIPLE
4. DESIGN OVERVIEW
5. PROCESS REVIEW
6. EQUIPMENT LIST
8. PROJECT COST
9. APPLICATION
INTRODUCTION
SCENARIO
DEHUMIDIFICATION).
• THIS DEVICE SUCKS AIR FROM ONE END AND COLLECT THE WATER
FROM MOIST AIR WITH THE HELP OF EVAPORATOR COIL AND BLOW
COIL.
Diagram Depicting the process of cooling and dehumidification
In psychrometry chart
Source : Bright Hub Engineering
DESIGN OVERVIEW
MOIST Air
FLOW
DIFFUSER
AIR
COMPRESSOR
EVAPORATOR
COMPRESSOR
COIL
PROCESS REVIEW
2. HUMIDITY
4. SIZE OF COMPRESSOR
EQUIPMENT LIST
VCRS COMPONENT –
• COMPRESSOR
• AIR COOLED CONDENSER
• FINNED EVAPORATOR
• CAPILLARY TUBE
EXTERNAL COMPONENT –
• AIR COMPRESSOR
• DIFFUSER
PROJECT COST
COMPONENTS COST ( IN RUPEES)
COMPRESSOR ( USED IN VCRS) 10000
DIFFUSER 1000
ASSUMPTIONS-
• AVERAGE OF DRY BULB TEMPERATURE OF INLET AIR (TD1 ) = 35
˚C
• RELATIVE HUMIDITY OF INLET AIR (ø1 ) = 50%
• BY PASS FACTOR = 0.50
• APPARATUS DEW POINT TEMPERATURE = 5˚C
• FLOW RATE OF AIR = 1m3/min.
EXPECTED RESULT-
• TIME REQUIRED TO PRODUCE 1 LTR. WATER =2 HR. & 45 MIN .
• 1 LTR. WATER COST= RS. 8.25 .
Saturation pressure at 35˚C = 0.05629 bar
ø1 = Pv / Ps
Pv = 0.5x0.05629x105 N/m2
Pv = 2314.5 N/m2
At 2314.5 N/m2, Dew point temperature = 23˚C
By Pass Factor = (Td2 – Td3) / (Td1 – Td3)
0.5 = (Td2 – 5) / (35 – 5)
Td2 = 20˚C
W1 = (0.622x2814.5) / (101325 – 2814.5)
W1 = 0.01777 kg/kg of dry air
W2 = 0.01155 kg/kg of dry air (using psychrometry
chart)
Mass of Dry Air :-
Ma = PaxV/RaxT
= (101325 – 2314.5) / (287x308)
Ma = 1.11kg/min.
Mass of Water Vapour :-
W1 = mv / ma = 0.01777 kg/kg of d.a.
mv = 0.01972 kg/min.
Amount of Water Condense :-
Ø2 = 80% (using psychrometry chart)
W2 = 0.01153 kg/kg of d.a.
Saturation pressure at 20˚C = 0.02337 bar
Pv = 0.8x0.02337 = 0.018696 bar
Pa = 1.01325 – 0.018696 = 0.994554 bar
ma = 99455.4x1 / 287x293
ma = 1.1827 kg/min.
mv = Wxma
= 0.01155x1.1827
mv = 0.013660 kg/min.
Amount of water condense = 19.72 – 13.66
= 6.06 gm/min.
Time required to collect 1000gm of water
= 1000/6.06
= 165.0165 min.
= 2hr.45min.
Power consumed by compressor = 500 watt
Power consumed by fan = 100watt
Total Power consumed= 600watt
Power consumption in 2hr.45min. = 600x11/4
= 1650 watt-hr.
=1.65 kwatt-hr.
Price of 1kwatt-hr energy consumption = Rs.5
Price of 1.65Kwatt-hr. energy consumption = 1.65x5 = Rs. 8.25
Which is less than Rs.20 bottle of drinking water
•• PAYBACK PERIOD =
• FARMING
• MILITARY