Professional Documents
Culture Documents
2.0
2.0 HVAC
2.1 General 2.1.3 Air-Conditioning
Standards
2.1 General 2.1.1 Definition of Air-
Conditioning 1.Cooling and De-humidifying
2.2 Refrigeration for summer cooling, temperatures of 68
Cycle deg to 74 deg F and 50% relative
the simultaneous control of the humidity are a frequent design average.
2.3 Types of Air- temperature, humidity, motion and
Conditioning Systems purity of the air in a confined space. 2. Heating and Humidifying
for winter cooling, temperatures of 70 deg
2.4 Air-Conditioning
Equipment
2.1.2 Functions or to 75 deg F and relative humidity of 30%
to 35% are found most satisfactory.
Elements of Air-
2.5 Heating Systems Conditioning 3. Air Motion
air velocity should average 4.57 to 7.6
2.6 Provisions in the meters per min measured 36” above the
NBC Concerning 1. Cooling and de-humidifying of air
2. Heating or humidifying of air floor.
HVAC
3. Cleaning of air or filtration
4. Air Supply
4. Circulation of air a. 5 cuft to 7-1/2 cuft of air per minute per
person (5-71/2 cuft/min/pers). In rooms
where smoking is not allowed
2.4 Air-Conditioning
Equipment
e. The necessary
manual or automatic
controls
2.0 HVAC
2. Split Type Air Conditioning
System
2.1 General
2.2 Refrigeration
Cycle
2.4 Air-Conditioning
Equipment
AHU
2.5 Heating Systems
2.2 Refrigeration
Cycle
2.4 Air-Conditioning
Equipment
2.2 Refrigeration
Cycle
2.4 Air-Conditioning
Equipment
2.2 Refrigeration
Cycle
1. Air-Vent System (One-Pipe
2.3 Types of Air- Gravity System)
Conditioning Systems
2.4 Air-Conditioning
Equipment
2.2 Refrigeration
Cycle
2.2 Refrigeration
Cycle
2.4 Air-Conditioning
Equipment
4. Boilers of more than 46 sqm 9. Each boiler shall have at least one
heating surface shall each be safety valve. For boilers having more
provided with two means of feeding than 46 sqm pressure of water heating
water, one steam driven and one surface or a generating capacity
electrically driven, one pump and exceeding 907 kg per hour, two (2) or
one injector. more safety valves shall be required.
2.0 HVAC
10. Each boiler shall have a steam 13. Upon the completion of the
gauge, with a dial range of not less installation, the Building Official shall
than 1-1/2 times and not more than conduct an inspection and test, after
2.1 General which a certificate of operation for a
twice the maximum allowable period not exceeding one year shall be
2.2 Refrigeration working pressure. It may be issued upon payment of the required
Cycle connected to the steam space or to inspection fees.
the steam connection to the water
2.3 Types of Air- column. 14. The Building Official shall notify the
Conditioning Systems owner in writing of the intended date of
11. Whenever repairs/replacements the annual inspection at least 15 days in
2.4 Air-Conditioning advance. However, the owner may
are made on fittings or appliances, request a postponement in writing of said
Equipment
the work shall comply with the inspection and the Building Official shall
2.5 Heating Systems section on New Installation of the fix a date for inspection agreeable to
Philippine Mechanical Engineering both, but not to exceed 30 days from the
2.6 Provisions in the Code. intended date.
NBC Concerning
HVAC 12. After a permit has been granted 15. The owner or user of a boiler shall
prepare the same for inspection by
to install a boiler/pressure cooling it down blanking off all
vessel/pressurized water heater connections to adjacent boilers, removing
upon payment of the installation fees all soot and ashes from tubes, heads,
thereof, it shall be the duty of the shell, furnace and combustion chamber.
Building Official to make periodic The owner shall assist the Building
inspection of the installation to Official by providing all labor and
determine compliance with the equipment required during said
inspection.
approved plans and specifications.
2.0 HVAC
2.6.3 Refrigeration and 5. Where ducts pass thru walls, floors
Air-Conditioning or partitions, the space around the
duct shall be sealed with fire resistant
2.1 General 1. The temperature and humidity of material equivalent to that of the wall,
the air to be used for comfortable floor or partition, to prevent the
2.2 Refrigeration cooling shall be maintained at 68-74ºF passage of flame or smoke.
Cycle
effective temperature at an air
movement from 4.57 to 7.60 MPM 6. When ducts or the outlets or inlets
2.3 Types of Air-
Conditioning Systems
within the living zone. to them pass through fire walls, they
shall be provided with automatic fire
2.4 Air-Conditioning 2. Water from evaporators, dampers on both sides of the fire wall
Equipment condensers and other machinery shall through which they pass.
be properly collected into a suitable
2.5 Heating Systems water or drainage system. 7. Fire doors and fire dampers shall
be arranged to close automatically and
2.6 Provisions in the 3. Ducts shall be constructed entirely remain tightly closed, upon the
NBC Concerning of non-combustible materials such as operation of a fusible link or other
HVAC steel, iron, aluminum or other approved heat actuated device,
approved materials. Only fire located where readily affected by an
retardant lining shall be used on the abnormal rise of temperature in the
inside of ducts. duct.
refrigeration
HEATING,
VENTILATION AND
AIR-CONDITIONING
END