You are on page 1of 5

1. Disain Duct dan Taper (bila diperlukan).

2. SP FAN dan TP FAN

Branch θ = 30o
R/D = 2. 3 pieces ACD
R/D = 2 stamped
F
A SP A B SPB L =10’ 5”
A
900 L =10’ 600 L =10’
C N
Elbow R/D = 2. 3 peces
L =10’ 60o
Q1 Q2 Q3
Titik A Titik B
SPhood
SPhood
SP1-A SP3-B
Hood 1 Hood 2 Hood 3 SP2-A SPA-B
SPB
SPA
Q1 = 9600 cfm Q2 = 960 cfm Q3 = 1000 cfm Vduct = 3500-4500 fpm

SP hood = 1,5 VPduct Duct Material : steel

Taper θ 10o lihat hal : 5-35 SPA = SP1 + R ( VP1 – VP2)


Qcorr = Qdesign SPgov.
SP duct

VPr = Q1 + Q2 2

4005(A1+ A2 )
Branch Entry to Duct

• VPr = Q1 + Q2 2

4005(A1+ A2 )

VPr = 1935 + 340 2


= 0.81 “
4005 (0.545 + 0.087)

SP3 = SP1 –(VP3-VPr) = -2.11 – (1.08 – 0.81 ) = -2.38 “ wg


Branch
B
A

Duct D1 D3

D2

Duct
hbranch Fig : 5-17 Hal : 5-32
Taper
B

D1 SP2 D2
SP1

htaper Fig : 5-19 Hal : 5-35

SP2 = SP1 + R(VP1-VP2)