Transformer Protection Against Grid Faults
Transformer Protection Against Grid Faults
2
Effect of grid side fault on transformer protection
For grid side fault some of the current is flowing through power transformer HV side , when this
value greater than pick up value relay will give trip, and this will result into nuisance tripping
This fault current impacts the OC and EF settings as well as stand by earth fault settings
By enabling directionality feature in OC and EF protection we can overcome effect of grid fault on
OC and EF settings, and we can avoid nuisance tripping.
REF and differential protection are not affected by grid faults
3
Transformer HV and LV backup protection
Stand by earth fault protection
We can increase the time delay of stand by earth fault to 0.9 seconds so that
by that time external protection system will isolate grid fault.
if it persists more than 0.9 seconds then transformer protection is
important so stand by earth fault protection will operates
5