Citymulti (17 1 2018)
Citymulti (17 1 2018)
Voltage
လွ်ပ္စစ္ဖိအား(သို ႔) တြန္းအားျဖစ္သည္။ယင္း၏သေကၤတ (Symbol) မွာ E ျဖစ္ၿပီး Unit
မွာ V ျဖစ္သည္။ ယင္းကို သိရွိရန္္ Volt Meter ျဖင့္တို င္းတာရသည္။
Current
လွ်ပ္စစ္၏လွ်ပ္စီးပမာဏျဖစ္သည္။ ယင္း၏သေကၤတ(Symbol) မွာ I ျဖစ္ ၿပီး Unit မွာ A
ျဖစ္သည္။ယင္းကို သိရွိရန္ Ampere Meter ျဖင့္တို င္းတာရသည္။
Frequency
လွ်ပ္စီး၏ႀကိမ္ႏွဳန္းပမာဏျဖစ္သည္။ ယင္း၏သေကၤတ(Symbol) မွာ F ျဖစ္ျပီး Unit မွာ
Hz(Hazard) ျဖစ္သည္။ယင္းကို သိရွိရန္ Frequency Meter ျဖင့္တို င္းတာရသည္။
Resistnce
လွ်ပ္စစ္၏ခု ခံ မႈျဖစ္သည္။ ။ ယင္း၏သေကၤတ(Symbol) မွာ R ျဖစ္ျပီး Unit မွာ Ω (Ohm)
ျဖစ္သည္။ယင္းကို သိရွိရန္ Ohm Meter ျဖင့္တို င္းတာရသည္။
• 1M = 3.28 FT
• 1 in = 25.4 mm
• 1 kg = 2.2 lb
• 1 Hp = 746 W
REFRIGERATION CYCLE
• Compressor
• Condenser
• Expansion Device
• Evaporator
Refrigeration cycle is
To transport heat from a low temperature region to a high temperature
region.
Expansion stage
Evaporator Condenser
Evaporation stage Condensation stage
Compressor
Compression stage
• Compressor
Refrigerant Pressure ျမွင့္တင္ျခင္း ၊ ေလ်ာ့ ခ်ျခင္း အလု ပ္ကို တစ္ျပိဳင္န
က္တ ည္းလု ပ္ေဆာင္သည္။
• Condenser
Refrigerant မွသယ္ေဆာင္လာေသာ Heat အပူ ပမာဏကို ပတ္၀န္းက်င္
သို ႔စြန္႕ထု တ္ေပးသည္။
• Expansion device
Condenser မွေပးပို ႔ေသာ Hight Pressure Liquid မ်ားကို Low
Pressure ဘ၀သို ႔ေျပာင္းေပးၿပီး Evaporator မွလို အပ္ေသာ Liquid ပမာဏကို
ထိန္းခ်ဳပ္လႊတ္ေပးသည္။
• Evaporator
Expansion device မွပို ႔လႊတ္လိုက္ေသာ Low Pressure Liquid မ်ားကို
Low Pressure vapour ဘ၀သို ႔ေျပာင္းေပးၿပီးပတ္၀န္းက်င္မွအပူ မ်ားကို
စု ပ္ယူေပးသည္။
There are heat radiation and endothermic at the refrigerating cycle.
1.9MPa 0.5MPa
30℃ 25℃ 放
吸 50℃ 5℃ 熱
熱 High pressure Low pressure
Easy to liquefy by Easy to evaporate by
pressure high. pressure low.
Condenser Evaporator
〔 High Press. High Temp. Gas 〕 Comp. 〔 Low Press. Low Temp. gas 〕
1. Window type
Inverter
AC power
Input Converter Inverter Compressor
AC DC AC
32 - 25 °C
23 - 24 °C
22 °C
50
50 Hz
Hz
compressor
High Starting current wastes energy
Energy Saving
Smooth INVERTER Compressor Control & Operation
32 °C
25 °C
CITY MULTI
Model Selection
R-410A
CMB-P1016V-HB
CMB-P1016V-HA
2 New BC Controllers
CMB-P1016V-HB
CITY MULTI- OUTDOOR UNITS
Standard type base model (YKA series)
8,10,12HP 14,16,18HP
S module L module
20HP
XL module
21
Expand Cooling Operation Temperature Range
22
24
Increase in the Limit of Piping Length
Piping Length
between
1 Branch and
st
Height between
indoor units :
*1 : Need one size bigger Max 30m*1
liquid pipe between max
difference height indoor unit
in case of more than 15m.
*2 : Outdoor unit is above
indoor units (IU above: 40m).
*3 : Need one size bigger Farther pipe length : 165 m [190m]
liquid pipe from first branch Total piping length : 1,000 m
in case of more than 40m.
25
26
PUHY-P500-900YSHM, PUHY-EP400-650YSHM
First
Joint
Twinning Kit
CMY-
Y100,200VBK
CITY MULTI (M-NET) System Controller
Price
AE-200E EB-50GU
Spec Middle scale
TG-2000A
buildings
AT-50B PAC-YT40ANRA
Small scale
buildings
Market Size
ME/MA Wireless RC Compact RC
28
28
CITY MULTI (M-NET) System Controller
Local Remote Controller
NEW
NEW
PAR-SA9FA
PAR-SL94B
29
CITY MULTI (M-NET) System Controller
Centralized Remote Controller
NEW
NEW NEW
EB-50GU AT-50B
AE-200E
PAC-YT40ANRA
AG-150A
30
New Controllers
(DDC)
(MCP)
LCD DISPLAY
0 5 1
0
35
Cooling Mode
Values are rough guide, varies depending on operation condition
63HS: 2 – 3.5 MPa
(influenced by ambient temp)
TH5: 3-15 deg’C higher than Te
SHb:
around 4 deg’C
Cooling mode
63LS: Influenced by
ambient temp
LEV2: control refrigerant flow
rate b/w outdoor units
38
Pressure
Heating mode
39
40
ALLOWABLE CURRENT OF WIRE
1.5 mm2 7/.021 18
4 mm2 7/.033 33
5 mm2 7/.044 43
10 mm2 7/.053 59
Earth Leakage Breaker Selection
Model Earth Leakage Breaker
PUCY-P200YKA 20A 100mA 0.1sec or less
PUCY-P250YKA PUHY-P200YKA
PUCY-P300YKA PUHY-P250YKA 30A 100mA 0.1sec or less
PUCY-P350YKA PUHY-P300YKA
PUCY-P400YKA PUHY-P350YKA
PUCY-P450YKA 40A 100mA 0.1sec or less
PUCY-P500YKA
PUHY-P400YKA
PUHY-P450YKA 60A 100mA 0.1sec or less
PUHY-P500YKA
If the unit is inverter type, select an earth leakage breaker for handling high harmonic waves
and surges.
Based on DATABOOK new version[8-60HP] both PUCY-P YKA and PUHY-P YKA
42
<Stop after it operated> Error
code is displayed
Error Code Cause
1*** Refrigerant/System error
2*** Water system error
3*** Outside air temperature (Only PUHY-(E)P Y(S)KA)
4*** Power & Electronic related error
5*** Sensor error
6*** Transmission/Communication error
7*** Communication Setting error
Location
(---)
Error Code
(----)
44
44
Check Code and Error Code
Check Code and Error Code
Check Code and Error Code
Check Code and Error Code
Check Code and Error Code
Check Code and Error Code
Check Code and Error Code
1. Introduction of
Maintenance Tools
52
52
1.2) On-Line Monitor (via MN Converter)
Local connection (via USB) [CMS-MNG-E]
53
53
1.3) On-Line Monitor (via AE-
200E / EW-50E / AE-50E)
AE-200E
EW-50E
54
54
Screen of PUCY-YKA
55
Lossnay
“ Thank You Very Much ”
58
Ventilation - The Facts
Lossnay
...
ZZZ
General fan
SA EA
(Supply Air) (Exhaust Air)
[Supply air goes out] [Exhaust air goes out]
Transfer
heat
RA OA
(Return Air) (Outdoor Air)
[Exhaust air intake] [Outdoor air intake]
Lossnay Core Construction
EA
SA Indoor Outdoor (Exhaust Air)
(Supply Air)
Partition Plate
Spacer Plate
OA
(Outside Air)
RA
(Return Air)
What is Lossnay?
Exhaust fan
EA Lossnay Core
OA
RA
SA
Line up
R-22 Vs R-410A
Refrigerant trend
HFCs R-410A
: R134a, R404A, R407C, R410A, R507.
• CFCHCs= chlorofluorocarbon
: R290, R600a. (ie: R-12).
• MS-09 , 12 LV
• Cut Jumper wire JR-84
• MS- 18 , 24 NV , RV , XV ,PK-1.6~4,PC-2~6
• SL-1, 1.6 , 2 AR
Cut Jumper wire JP-8