Professional Documents
Culture Documents
EHTC
R.N.SARANGI
BHEL /TALCHER SITE
GOVERNING SCHEME
The output of EHTC and hydraulic governor are fed to
a hydraulic minm selector gate which generates HP
secondary oil pressure & IP secondary oil pressure. The
secondary oil pressure in turn acts on the hydraulic
servomotor for positioning the control valves. The control
valve position is transmitted by a position transmitter for
remote indication in percentage.
Hydraulic governor is realised by starting device and
speeder gear. The starting device is also called as load
limiting device .
During normal operation, if the tracking device is on,
the hydraulic governor (starting device) tracks EHTC. Thus
during the failure of EHTC hydraulic back-up takes over the
Control.
HYDRAULIC SELECTION
MIN
IP sec. Oil pr.
Hydraulic out put
Raise
Speed NR SPC.
Speed
Ref NR Td. Controller
Lower
SGC Turb.
Speed
Auto Synch.
actual
CRT OR NR raise
Black Pnl P.B.
GCD if pact < stn.load
SGC turb
Auto Synch.
Dn/dt optd
CRT OR NR lower
Black Pnl P.B.
GCD if pact < stn.load
dn/dt Logic
Acceleration is low
nact. > 725 rpm
nact. < 2850 rpm
OR
GCB Open A
N
HP ESV 1&2 D
Not closed
(NR) nref > 700 rpm
dn /dt
Operated
Speed Reference(NR) Logics
2) NR Tracks to nact. + 15 rpm
if :-
i) Load Controller O/p > Speed cont o/p by 5%
and ii) Speed (nact. ) is between 48.5 HZ to 51.5 HZ
and iii) ‘Load controller ON’ Command is there.
ii) NR is automatically raised by 15 rpm after synchronisation
for block loading.
iii)In case of a turbine trip, NR tracks to nact. – 130 rpm to ensure
speed controller output to be less than 0 %
***
nR
Speed raise
Speed lower
Int. NR
(Turb. Trip) Track to Nact – 130 rpm
Block loading
Track to Nact + 15 rpm
nRTD
TSE Tupper,min
Speed between.
N
48.5 HZ to 51.5 HZ D
Int
TSE fault & on
nact - 1
nact - 2 & MV3 n act
nact – 3
NRTD PDT
Controller O/P
nact Gain = 24
5% droop
LOAD CONTROLLER
Load Reference :-
i) From back panel P.B.
ii) From CRT.
iii) SGCT Step –11
Lower Command :-
i) From back panel P.B.
ii) From CRT.
iii) SGCT Step –52
Both Raise and tower commands as above are issued provided
‘CMC is not ON ‘
CMC fault R
CMC OFF Command O
EHC fault
R
Turb follow Boiler
From CMC ( IP mode)
Pressure Cont.
in action 2 sec
O
delay
Speed Cont. R
in action
Load Reference (PR) logic:-
2) PR tracks to CMC Load reference, if “CMC is ON”.
ii) On issue of a “ Load ref tracking” signal,
PR tracks to Load actual for 1sec.
iii) PR tracks to Load actual also on following conditions :-
a) Pressure controller is in action
AND b) IP mode selected.
AND c) Load actual is < 30%, i.e.180 MW
“LOAD REF TRACKING” Signal :-
It is used as a reference matching signal during transition
(High freq. Unloading )
It is activated,if :-
I)Pact. < 180 MW
AND ii) Speed, nact. Is > 3048 rpm.
AND iii) Error to load controller is < -2%.
Load Controller
Push buttom
Raise
CRT >
SGC Turb. &
1
PR PR
S
E PR
‘ CMC not ON’ Lower
L
PR
PRTD
Time
TSE Margins Command
ΣPR M +
I Error
N
PRMAX
Load Act.
_
SUM of PR( ΣPR) Logic
i) EPR = PRTD + PR△f + Pressure correction.
ii) PR△f = 0 MW
if i) freq. Influence is OFF
OR ii) CMC is not “ON” *
OR iii) Turbine follow boiler from CMC.(IP mode)
iii) PR△f is active provided above conditions are not there and Pact.>Stn. Load.
iv) Pressure correction is active, if :-
a) Pact. > Stn. Load.
AND b) Load controller is in action.
AND c) LP Mode is selected.
Load controller ‘ON’ & ‘OFF’
Load controller can be switched ‘ON’ or ‘OFF’ from CRT/P.B. only and only when
speed controller is active ,and speed Controller out put is more than load controller
output.
***
ΣPR LOGIC
Pressure Correction
PRTD + ΣP R
+
PRΔ f
Pressure Correction Signal 1
0% 2 Pressure
Correction
SEL-2
Freq. Inf. OFF
CMC OFF OR
IP mode Selected
FREQ INFLUENCE SCHEME AT TSTPS
LIMITER
47-53 HZ TRACKING FREQ DEVIATION
RAMP GEN SWITCHING
F(X)
-
49-50.34 HZ
0.2 HZ/MIN
+
LIMITER
49-50.34HZ
FREQ ON/OFF
DROOP @ 10% 1 LOAD
FREQ FILTER _/-.3HZ SUM OF PR CONTROLLER
LOQD LIMIT +/-25
+ M
FOR 49<F>50.34 2
-50 TO +25 FOR 0 I
F < 49,50.34 >
SEL -2 + PR MAX N
LOAD < 350 MW LOAD SET
POINT LOAD ACT.
Stop Reference Limiter Logics:-
Stop speed/power set point:-
The signal is generated on any of the following conditions :-
i) Pressure Controller in Action & LP mode selected
& PR › PRTD
OR ii) Speed /PWR set point block from ATRS.
The above signals directly stop PRTD .
Load Gradient ON/OFF. (Page-23)
Load gradient ‘ON’ by manual command provided Set point
controller is balanced.
It is made ‘OFF’ manually if set point controller is also balanced.
It is made ’OFF’ by CMC ON Signal also.
***
Load Controller Input
i) It is = error to load controller+ High
frequency unloading component.
R Isolated grid
detected
Error to Load
controller<8.4% A
N
Reset Command D
LOAD CONTROLLER
It as a PID Controller .
Logics :-
i) During pressure controller in action, the output
follows the pressure controller output + 2%.
ii) If load controller is switched off, then the
output is equal to – 10%.
iii) During load controller not stable, the output
will track speed controller output – 1.5 %.
Load controller not stable signal :-
It is same as ‘FAST FOLLOW’ signal .
***
PRESSURE CONTROLLER
Logics :-
LP Mode :- ( Limit Pressure Mode ).
***
PRESSURE CONTROLLER
Pressure deviation signal is received from CMC.
Also pressure actual valve is received from CMC,
from which set pressure is calculated and fed to
The controller . Actual Press
+
Set Pressure + P
-
I
-10 Kg -1
+ R
0 Kg 2
IP Mode Sel 2 Limit between 50 to 120%
LP Mode
A
N LP reached.
ΔP is +ve Alarm
D
CONTOLLER SELECTION LOGIC
All the three controller’s O/P are fed to the
selection logic, the controller selected acts
on the turbine.
The Logic :-
Speed controller, load controller O/P are
fed to a MAX selector . The O/P of MAX
and the inverted speed controller O/P are
fed to a MIN selector , whose O/P along
with the pressure controller O/P are fed to
another MIN selector . The final output of
this MIN gate is fed as reference (hr) to
the position controller.
***
Cont. Selection
M M
A I
Load cont. O/P X N M
hr
I
Position
reference
Press Cont. O/P N
Position Controller :-
The position controller is a hardware controller which
is a PID type controller. It receives the reference from the
controller selection logic.
The EHC position signal is fed to the controller from a
selector card, which receives the position signal from two
Collins transmitters .Secondary oil pressure is generated as
per the EHC position which is decided by the position
controller.
The control valves take there position as per the secondary
oil pressures.
POSITION CONTROLLER
hr P
I To plunger Coil
Collins-I
S D
E
Collins-II
L
HYDRAULIC SELECTION
MIN
IP sec. Oil pr.
Hydraulic out put
THANKS