a) Suspended: The thrust bearing is located above the rotor and there
may be one or two guide bearings, one of which is always above the
rotor.
b) Umbrella: The thrust bearing is located below the rotor and one
guide bearing is located in close proximity to the thrust bearing.
Maintenance considerations:
a) Using the specified lubricating oil.
b) Maintaining clean uncontaminated oil.
c) Maintaining proper oil level.
d) Periodically checking the bearing insulation and grounding brush.
e) Maintaining the flow of the cooling medium.
f) Checking the temperature of bearings.
Starting and loading :-
For the first start of a new machine or if any work has been done on any
connections that involve synchronizing, correct phase rotation and
proper operation of the synchronizing instrumentation must be verified.
The phase angle between the generator and the bus voltage should not be
greater than 15° at the moment of closing of the synchronizing breaker.
• Unbalanced loading
• Operation with stator coils cut out
• Operation with winding path cut out.
• Asynchronous Operation
• Loss of field excitation
• Operation in cold ambient temperature.
Hazards of operation during initial installation:- A number of
conditions should be carefully observed during the initial installation and
operation period including the following:
• Insulation strength
• Rotor balance
• Vibration
• Temperatures
• Noises
• Cooling System
Fire protection systems :- Fire protection systems are provided to
ensure that burning of combustible components (usually after an
electrical fault) does not persist and cause secondary damage.
Introduction
• An effective inspection program can significantly minimize
undesirable, unscheduled service interruptions.
i. Stator frame
ii. Stator core assembly
iii. Slot portion of stator winding
iv. Stator end winding area
v. Main and neutral lead assembly
vi. Rotor coils , poles and damper winding
vii. Collector and brush rigging
viii. Spider , spide rim and braker rim assembly
ix. Bearings
x. General assembly details
xi. Verification of protective relaying
• This permits the detection of conditions that might affect test results,
contribute to undesirable test flashovers, or result in the complete failure
of partially damaged insulation structures.
Recommended tests :-
a) This test will not detect clean rupture, break ,or separations in the
insulation structure when the spacing breakdown level is greater
than the test voltage applied.
b) The value of insulation resistance measured is highly dependent on
the area ,thickness and temperature of the insulation under test.
c) Although a high level of insulation resistance is desirable , it is not
in itself an indicator of insulation quality.
Noise measurements
Vibration measurements
Ventilation circuit measurements
Bearing load measurements
Conclusion:
Bearings
Guide bearing clearance checks
Bearing insulation checks
High-pressure lube system checks
Lubrication testing