This document discusses different types of air conditioning systems, focusing on all-air systems. It describes single duct and dual duct systems, and covers constant volume and variable volume systems. Within single duct systems it discusses single zone and multiple zone configurations. It also discusses advantages and disadvantages of all-air systems compared to all-water systems. All-water systems are described as using water rather than air to transport thermal energy, using fan coil units, convectors or radiators in terminal units.
Original Description:
Original Title
LECTURE 8 AIR CONDITIONING - SYSTEMS & EQUIPMENT CONTINUED
This document discusses different types of air conditioning systems, focusing on all-air systems. It describes single duct and dual duct systems, and covers constant volume and variable volume systems. Within single duct systems it discusses single zone and multiple zone configurations. It also discusses advantages and disadvantages of all-air systems compared to all-water systems. All-water systems are described as using water rather than air to transport thermal energy, using fan coil units, convectors or radiators in terminal units.
This document discusses different types of air conditioning systems, focusing on all-air systems. It describes single duct and dual duct systems, and covers constant volume and variable volume systems. Within single duct systems it discusses single zone and multiple zone configurations. It also discusses advantages and disadvantages of all-air systems compared to all-water systems. All-water systems are described as using water rather than air to transport thermal energy, using fan coil units, convectors or radiators in terminal units.
EQUIPMENT Continued QUICK RECAP OF ALL AIR SYSTEMS Based on the fluid media used in the thermal distribution system, air conditioning systems can be classified as:
All Air System
All Water System A combination of the above two.
All air system air is used as the media that transports
energy from the conditioned space .
All air systems can be further classified into:
1. Single duct systems, or 2. Dual duct systems ALL AIR SYSTEMS – SINGLE DUCT SYSTEM The single duct systems can provide either cooling or heating using the same duct, but not both heating and cooling simultaneously.
These systems can be further classified into:
Constant volume, single zone system Constant volume, multiple zone system Variable volume systems
The dual duct systems can provide both cooling and
heating simultaneously. These systems can be further classified into: Dual duct, constant volume systems Dual duct variable volume systems CONSTANT VOLUME SINGLE ZONE SYSTEM There is only one supply duct, through which either hot air or cold air flows, but not both simultaneously. It is called as a constant volume system as the volumetric flow rate of supply air is always maintained constant.
Applications of single duct, single zone, constant volume
systems:
1.Spaces with uniform loads, such as large open areas
with small external loads e.g. theatres, auditoria, departmental stores.
2. Spaces requiring precision control such as
laboratories The Multiple, single zone systems can be used in CONSTANT VOLUME MULTIPLE ZONE SYSTEM Advantages of single duct, multiple zone, constant volume systems with reheat coils: Relatively small space requirement Excellent temperature and humidity control over a wide range of zone loads Proper ventilation and air quality in each zone is maintained as the supply air amount is kept constant under all conditions
Disadvantages of single duct, multiple zone, constant
volume systems with reheat coils:
High energy consumption for cooling
Simultaneous cooling and heating is not possible. CONSTANT VOLUME MULTIPLE ZONE SYSTEM SINGLE DUCT VARIABLE VOLUME MULTIPLE ZONE SYSTEM Compared to constant volume systems, the variable air volume systems offer advantages such as:
a)Lower energy consumption in the cooling system as
air is not cooled to very low temperatures and then reheated as in constant volume systems.
b) Lower energy consumption also results due to
lower fan power input due to lower flow rate, when the load is low. However, since the flow rate is controlled, there could be problems with ventilation, IAQ and room air distribution when the zone loads are very low. In addition it is difficult to control humidity precisely using VAV systems. Balancing of dampers could be difficult if the airflow rate varies widely. However, by combining VAV systems with terminal reheat it is possible to maintain the air flow rate at a minimum required level to ensure proper ventilation and room air distribution. SINGLE DUCT VARIABLE VOLUME MULTIPLE ZONE SYSTEM Dual Duct Constant Volume Multiple Zone System Advantages of dual duct systems: Since total airflow rate to each zone is constant, it is possible to maintain proper IAQ and room air distribution. Cooling in some zones and heating in other zones can be achieved simultaneously. System is very responsive to variations in the zone load, thus it is possible to maintain required conditions precisely. Disadvantages of dual duct systems: Occupies more space as both cold air and hot air ducts have to be sized to handle all the air flow rate, if required. Not very energy efficient due to the need for simultaneous cooling and heating of the air streams. ADVANTAGES OF ALL AIR SYSTEM All air systems offer the greatest potential for energy conservation by utilizing the outdoor air effectively.
Using dual duct systems, it is possible to provide
simultaneous cooling and heating. Changeover from summer to winter and vice versa is relatively simple in all air systems.
It is possible to provide good room air
distribution and ventilation under all conditions of load. ADVANTAGES OF ALL AIR SYSTEM All air systems offer the greatest potential for energy conservation by utilizing the outdoor air effectively.
Using dual duct systems, it is possible to provide
simultaneous cooling and heating. Changeover from summer to winter and vice versa is relatively simple in all air systems.
It is possible to provide good room air
distribution and ventilation under all conditions of load. DISADVANTAGES OF ALL AIR SYSTEM They occupy more space and thus reduce the available floor space in the buildings.
Retrofitting may not always be possible due to the
space requirement.
Balancing of air in large and particularly with
variable air volume systems could be difficult. ALL WATER SYSTEM In this system, water is used as working fluid that transports thermal energy between conditioned space and A/C plant. Chilled water is circulated for cooling while Hot water is circulated through coils for space heating. As only water is supplied by HVAC plant to the space, Fresh air has to be supplied by another unit to maintain Indoor air quality and ventilation. These systems are also known as Chilled water systems for cooling applications. Based on number of pipes used in system, they are classified as 2-pipe system and 4-pipe system ALL WATER SYSTEM A 2-pipe system can provide either cooling or heating only, but not both at a time. As shown in next slide, chiller supplies cold water or heater supplies hot water to different spaces. Out of 2 pipes, one is for supply and the other is for return of water to central plant. Chilled water/ hot water circulates through Fan coil units (FCU), or convectors or Radiators located in the each space. Thermal energy is exchanged between water and air in the conditioned space. Flow control valve controls the water flow rate as per load variation. Flow control valve is driven by zone thermostat which gives signal to adjust flow rate as per load. ALL WATER SYSTEM A 2-pipe system can provide either cooling or heating only, but not both at a time. As shown in the next slide, chiller supplies cold water or heater supplies hot water to different spaces.
Out of 2 pipes, one is for supply and the other is
for return of water to central plant. Chilled water/ hot water circulates through Fan coil units (FCU), or convectors or Radiators located in the each space. ALL WATER SYSTEM ALL WATER SYSTEM A Fan Coil Unit (FCU) is a simple device consisting of a heating and/or cooling heat exchanger or 'coil' and fan.
It is part of an HVAC system found in residential,
commercial, and industrial buildings. A fan coil unit is a diverse device sometimes using ductwork, and is used to control the temperature in the space where it is installed, or serve multiple spaces. ALL WATER SYSTEM ALL WATER SYSTEM Warm air passes over cooling coils, where it is cooled and dehumidified to supply conditions. Condensate is collected in drain pan after dehumidification and then discharged through condensate drain pipe. Sometimes ductable FCU is used for relatively large spaces.
A short duct runs to 3-4 spaces from FCU which
supplies air to supply diffusers.
Return diffusers are also provided. This duct
system ensures proper air distribution. FCUs are available upto 5-10 TR capacity (Ton of Refrigeration). *A ton of refrigeration (TR), also called a refrigeration ton (RT), is a unit of power used in some countries (especially in North America) to describe the heat extraction capacity of refrigeration and air conditioning equipment. It is defined as the rate of heat transfer that results in the melting of 1 short ALL WATER SYSTEM Mostly FCUs are ceiling mounted in the false ceiling. Capacity is controlled by varying chilled water flow rate. Room thermostat senses and signals the variation in space temperature to control valves to regulate chilled water flow. Convectors are mainly used for heating applications. Hot water is circulated through heating coil. Space air heating takes place by natural convection. Radiators are also used for space heating applications. Heat transfer occurs majorly by radiation. Recently radiators are also being used for cooling applications by Radiant cooling or ALL WATER SYSTEM ALL WATER SYSTEM A 4-pipe system consists of two supply pipelines – one for cold water and one for hot water; and two return water pipelines.
The cold and hot water are mixed in a certain
proportion as per the zone load, and the mixed water is supplied to the terminal units in the conditioned space. The return water is split into two streams, one stream flows to the heating coil while the other flows to the cooling coil..
Terminal units used in all water system are of
basically three types namely Fan coil units (FCU), Convector and Radiator. APPLICATION - ALL WATER SYSTEM All water systems are suitable for use as low cost central HVAC systems in multi zone High Rise commercial applications. All water system is best solution to replace All air system in High Rise Tall buildings, as it is much easier to carry water through small sized pipes than air through very big sized ducts across farther heights[5]. It is very effective system in certain applications where space is extremely limited, such as narrow ceiling and shafts. In case of Individual room control as required in hotels, multi storey apartments, offices etc. all water systems are more famous. ALL AIR vs ALL WATER SYSTEM The thermal distribution system requires very less space compared to all air systems.. Individual room control is possible, and at the same time the system offers all the benefits of a large central system. Since the temperature of hot water required for space heating is small, it is possible to use solar or waste heat for winter heating. It can be used for new as well existing buildings (retrofitting). Simultaneous cooling and heating is possible with 4-pipe systems. COMBINATION AIR - WATER SYSTEMS Air water system employs best features of all air and all water systems. Combination air-water system distributes both chilled water and /or hot water and conditioned air from a central system to the individual spaces.
Terminal units in each zone provide cooling or
heating to that zone.
One type of air water system uses FCU as terminal
units to provide major part of air conditioning and central AHUs are used to supply only ventilation air directly into the space. COMBINATION AIR - WATER SYSTEMS Another type uses ‘Induction units’ as terminal units. It receives supply air from central AHU, called as primary air and chilled / hot water from central chiller. Primary air is delivered at high pressure in Plenum chamber and discharged into space through high velocity nozzles. This induces room air into induction unit, where it mixes with primary air.
Room air is called as secondary air. Supply air is
mixture of primary and secondary air. Therefore no fan is required in induction unit. Next slide shows schematic of basic induction unit. COMBINATION AIR - WATER SYSTEMS COMBINATION AIR - WATER SYSTEMS Normally terminal unit like FCU keeps on cooling the room air again and again with the help of cooling coil circulating chilled water. Therefore sensible cooling load is handled by water system. Ventilation air is supplied by central AHU of air system.
AHU supplies cooled and dehumidified fresh air
which can take care of room latent loads. Because of this, there is no condensation problem with cooling coils. Similarly, in winter system heated and humidified fresh air is supplied by AHU and hot water circulates through heating coil of terminal unit. ADVANTAGES OF AIR - WATER SYSTEMS Simultaneous heating and cooling is possible in air- water system.
Lot of space is saved, as only ventilation air is
supplied through ducts and chilled/ hot water is passed through pipes.
Economic control of individual zones is possible
using room thermostats which can either regulate secondary air or secondary water in FCUs. ADVANTAGES OF AIR - WATER SYSTEMS
Since there is no latent load on cooling coil,
troubles due to condensation do not occur. It prevents marshy or damp regions in the conditioned space.
Servicing, Repair, Replacement, Maintenance
works etc. are relatively easier than all water systems.
Positive pressures can be maintained in
conditioned spaces under all varying loads. DISADVANTAGES OF AIR - WATER SYSTEMS There are a lot of complications in system operation and controls as both air and water have to be handled carefully.
Mostly air- water systems find limited applications
in perimeter zones.
Constant supply of fresh air has to be supplied to
all zones, no matter whether spaces are occupied are not. Because control is only for cooling/ heating coil through room thermostat. DISADVANTAGES OF AIR - WATER SYSTEMS In case of unusual high latent loads, excessive condensation may cause damp environment and discomfort in the zone.
As systems are complicated with greater extent of
controls, normally air-water systems are costlier than all water systems. APPLICATIONS OF AIR - WATER SYSTEMS It is much suitable for retrofitting of existing buildings, where there is space restriction.
It is very good solution for perimeter zone
buildings with large sensible loads.
It can be used where close control of humidity in
the space is not necessary.
It serves well for large office buildings, hotels,
lodges etc. UNITARY SYSTEMS This particular classification is not according to how the system functions, but how the equipment is arranged.
A Unitary system is one where the refrigeration
and air-conditioning components are factory selected and assembled in a package. This includes refrigeration equipment, fan, coils, filters, dampers and controls.
Unitary equipment is usually located in or close to
the space to be conditioned. Central equipment is usually remote from the space. UNITARY SYSTEMS In theory, both the systems – Unitary and Central – could be air, water or air-water combination systems. But, in practice, unitary systems are generally all-air systems.
Unitary systems are limited largely to single zone
systems with or without reheat or multi-zone units.
These have three categories:
1. Room units 2. Unitary Conditioners 3. Rooftop Units. UNITARY SYSTEMS In theory, both the systems – Unitary and Central – could be air, water or air-water combination systems. But, in practice, unitary systems are generally all-air systems.
Unitary systems are limited largely to single zone
systems with or without reheat or multi-zone units.
These have three categories:
1. Room units 2. Unitary Conditioners 3. Rooftop Units.
*Unitary conditioners are also called self-contained units or packaged units
UNITARY SYSTEMS - ROOM UNITS Generally of two types: Window units or Through- the-wall units.
Compressor, evaporator cooling coil, condenser,
filter, motors, fans and controls are assembled in the unit casing.
Dampers can be adjusted so that only room air is
used, or so that some outside ventilation air can be brought through the conditioner.
Room units are available for upto 3 Tons of
refrigeration capacity. UNITARY SYSTEMS - ROOM UNITS UNITARY SYSTEMS - ROOM UNITS UNITARY SYSTEMS - ROOM UNITS Room units have no flexibility in handling high latent heat gains or changed sensible heat ratios, and therefore do not give good humidity control.
Air cleaning quality is minimal because the filters
remove only large particles, in order that the resistance to air flow be low.
When used in multi-room buildings, maintenance
of the large number of units can be very burdensome and expensive. These units are inherently energy wasteful in multiple use because they cannot modulate capacity. UNITARY AIR CONDITIONERS Designed to be installed in or near a conditioned space. Components are contained in the unit. Heating components are sometimes included. Can be a vertical or a horizontal arrangement according to space available. Can discharge directly into the space or can have a limited amount of ductwork. Popular in small commercial applications. Units are available all components are packaged except the condenser. Another common arrangement is called a split system where the condenser and compressor are in one package located outdoors and the fan and cooling coil are another package located outdoors. WORKING OF SPLIT UNITS UNITARY AIR CONDITIONERS – SPLIT UNITS Has distinct advantages: Compressor – condenser package is located out side – noise less objectionable and Easier access for maintenance. No problem for finding a suitable and adequate space in the building.
In larger units, multiple compressors are used.
Units are available in sizes up to about 50 Tons. UNITARY AIR CONDITIONERS – ROOFTOP UNITS Designed to be located outdoors and generally installed on roofs.
Usually, all of the refrigeration, cooling and air-
handling equipment comes in sections that are assembled together although the condenser and compressor are remote. Heating equipment may may also be incorporated in the unit.
Weather proofing features, moisture-proof
electrical parts, casing and exposed parts are corrosion protected. UNITARY AIR CONDITIONERS – ROOFTOP UNITS DIFFERENT TYPES OF AIR-CONDITIONING SYSTEMS FFERENCE BETWEEN CENTRALIZED & DECENTRALIZED SYSTE CENTRALIZED DECENTRALIZED
Source components - comprising of Source, distribution, delivery and
the compressor (reciprocating, control functions in a single screw, centrifugal or scroll type), package. condenser (water cooled shell & The most common Decentralized tube or air cooled finned type), air-conditioning system includes expansion valve, and the evaporator window, split, package and heat (chilled water shell & tube type or pump air-conditioning units. direct expansion finned coil type). All these components are assembled in a skid, known as the chiller package. Refrigerant piping required to connect these parts is also enclosed in this skid. The chiller package is located in a dedicated plant room. DIFFERENT TYPES OF AIR-CONDITIONING SYSTEMS FFERENCE BETWEEN CENTRALIZED & DECENTRALIZED SYSTE CENTRALIZED DECENTRALIZED
Distribution system comprising of For large buildings decentralized
chilled water & cooling water systems may be viewed as collection pumps, air handling units, and of multiple independent units placed ductwork. The pumps are generally at different locations in a located in the chiller plant room and distributed network with each unit the air handling units are installed working in isolation. Each system is in separate air handling rooms local self-contained unit consisting distributed at various locations of of its own compressor/s, evaporator the building. coil, fan, condensing unit and filtration unit. Terminal elements comprising of Decentralized systems maintenance grilles, diffusers, ventilation tends to be simple but such systems, and a number or elements maintenance may have to occur adjusting comfort. Heat rejection directly in occupied spaces. system (cooling tower/s or air cooled condensers) are located outdoors.