System Backup Protection (51V, 21) • Mengembankan proteksi terhadap gangguan dari luar zona proteksi generator • Voltage supervised time-overcurrent (51V) or distance relaying (21) may be used • Distance relay set to include generator step up transformer and reach beyond, into the system • Time delays must be coordinated with those of the system protection to assure that system protection will operate before back up • CTs on neutral side of generator will also provide backup protection for the generator System Backup Protection (51V, 21) System Backup Protection (51V, 21) System Backup Protection (51V, 21)
• For medium and small sized generators, voltage-restrained or
voltage controlled time overcurrent relays (51V) are often applied
• Control or restraining function used to prevent or desensitize
the overcurrent relay from tripping until the generator voltage is reduced by a fault