Professional Documents
Culture Documents
Valves are usually non-linear. That is, the flow through the valve is not the same as the valve position. Several types of valves exist: Linear
Same gain regardless of valve position
Equal Percentage
Low gain when valve is nearly closed High gain when valve is nearly open
Quick Opening
High gain when valve is nearly closed Low gain when valve is nearly open
As we will see later, the gain of the process, including the valve, is very important to the tuning of the loop. If the controller is tuned for one process gain, it may not work for other process gains.
At low flow, the head loss through the pipes is less, leaving a larger differential pressure across the valve. At high flow, the head loss through the pipe is more, leaving a smaller differential pressure across the valve.
Valves are usually either: Fail Closed, air to open or Fail Open, air to close
Measurement of dynamics
Disturbances
Manual Mode
Automatic Mode:
Key concepts
The PID control algorithm does not "know" the correct output to bring the process to the setpoint.
It merely continues to move the output in the direction which should move the process toward the setpoint. The algorithm must have feedback (process measurement) to perform.
The PID algorithm must be "tuned" for the particular process loop. Without such tuning, it will not be able to function.
To be able to tune a PID loop, each of the terms of the PID equation must be understood. The tuning is based on the dynamics of the process response.
P PI PID
0.3/D 0.5/D
0.5D
Reset
Derivative