MD-BFP START PER MISSIVE & TRIP

PROTECTION
MD-BFP STRAT
PERMISSIVE
• MD- BFP inlet MOV open
• MD- BFP inlet MOV close
• MD- BFP recirculation inlet MOV open
• MD- BFP Recirculation control valve position > 80%
• MD- BFP Recirculation CV O/L mov opened
• MDBFP BSP INL PRESS > 10 bar
• MD- BFP HCP lube oil pressure Normal
• MD- BFP Filter DP < 600 mbar
• Dearator LVL Normal (-200 mm < LVL> +200 mm)
• MDBFP main motor TEMP Normal
MD-BFP Temp Normal permissive
• MD- BFP JNL BRG Temp Drive/ Non Drive end ( <75*C) – 4 element
• MD- BFP Thrust BRG Temp ( <75*C) – 4 element
• MD- BFP motor BRG Temp (<80*C) - 2 element
• MD- BFP motor winding temp (<120*C) – 6 element
• MD- BFP motor CLR temp ( 120*C) – 2 element
• MD- BFP HCP BRG temp ( <85*C) – 10 element
• MD- BFP working oil cooler ( inlet temp <110*C, Outlet temp <60*C)
• MD- BFP Lube oil cooler inlet temp ( < 75*C) and Outlet Temp ( <55*C)
• MD- BFP JNL BRG DE/NDE Temp Normal ( <75*C) -2 element
• MDBFP Thrust BRG Temp ( booster pump) inboard/outboard ( <80*C) – 2
element
MD-BFP Trip Condition
• MD- BFP Inlet MOV opened and Dearator level LL (2 out of 3 switch <280 mm)

• MD-BFP inlet MOV closed and BFP Main motor ON F/B (time delay- 30 sec)
• MD-BFP Main motor ON F/B & O/L MOV closed & Recirculation I/L MOV & O/L MOV
closed & BFP Outlet Flow < 370 mbar ( 2 out of 3) with delay of 10 sec
• MD-BFP Main motor ON F/B & MDBFP BSP pressure < 1 bar ( time delay- 30 sec)
• MD-BFP HCP Lube oil pressure switch ( 2 out of 3)
• MD-BFP TEMP PROT (WORK OIL CLR INL>130) time delay – 3 sec
• MD-BFP TEMP PROT (JNL BRG DE / NDE TEMP>100) time delay – 3 sec
• MD-BFP TEMP PROT (THR BRG Inboard/Outboard TEMP >110) time delay – 3 sec
• MD-BFP TEMP PROT ( INL OIL temp HHH (2/3)
MD-BFP Trip Condition
• MDBFP VIB PROT (BFP DE ( X / Y) & NDE ( X/Y) BRG VIB> 7 mm/sec) delay time -10 sec
• MDBFP VIB PROT (MTR BRG BSP SIDE (X OR Y) VIB > 8.9 mm/s) delay time -10 sec
• MDBFP VIB PROT (MTR BRG HCP SIDE (X OR Y) VIB > 8.9 mm/s ) delay time -10 sec
• MDBFP TEMP/VIB PROT (DE BRG ( X OR Y) VIB > 10 mm/s ) delay time -10 sec
• MDBFP TEMP/VIB PROT (NDE BRG ( X OR Y) VIB > 10 mm/s ) delay time -10 sec