Professional Documents
Culture Documents
Module 1 - Update Vline WWS TCN - Mod.1, 22.july.2021. (Repaired)
Module 1 - Update Vline WWS TCN - Mod.1, 22.july.2021. (Repaired)
1. PROTECTIVE RELAYS
2. PROTECTIVE RELAYS, TRANSMISSION SYSTEMS
3. CONTROL EQUIPMENT
4. SUBSTATION BATTERIES
5. SUBSTATION BATTERY TESTING
6. SUBSTATION BATTERY CHARGES
7. SUBSTATION BATTERY, CELL & CHARGER REPLACEMENT
Yashar Jokar
Hassan taha
1
Protective Relays
2
Protective Relays Topics
• Introduction to Relays
• Overcurrent Relays
• Directional Overcurrent Relays
• Transformer protection Relays
• Line protection Relays
• Reclosing Relays
• Voltage Relays
• Auxiliary Relays
• Solid-State Replays
3
WHAT IS A PROTECTION RELAY:
4
PROTECTIVE RELAYS: AN EXPANDED
DEFINITION
• An electric device that is designed to respond to input conditions in a prescribed manner
and, after specified conditions are met, to cause contact operation or similar abrupt
change in associated electric control circuits.
• A relay may consist of several relay units, each responsive to a specified input, with the
combination of units providing the desired overall performance characteristic of the
relay. Inputs are usually electric but may be mechanical, thermal or other quantities or a
combination of quantities. Limit switches and similar devices are not [protective] relays.
(IEEE C37.100-1992 and C37.90-2005)
5
SAFETY ASPECT OF THE RELAYS
6
General Safety Rules while working with the relays
• Speed is secondary to safety of workers.
• Inventory & visually check grounding equipment before & after each use. Replace if necessary.
• Install the clamp at the ground-end of grounding jumper first, & remove it last. Install the
conductor-end of the grounding jumper last, & remove it first.
• Use hot sticks, not rubber gloves, to attach & remove conductor clamps. When you make the
final connection, you might be picking up load & you don’t want to be close to a clamp when
that happens. Use a hots tick. The hear (arc flash) is the danger, more than the voltage, so keep
your distance.
• Don’t make contact any part of the worker protection grounds while they are being installed,
removed, or in place.
• Choose worker protection grounds that are able to carry the maximum available fault current
until protective devices have cleared the fault.
• When grounding tree wire, use hot-stick stripping tools to expose the conductor. In an
emergency, if hot-stick stripping tool are not available, use a spiking tool. Wear a rubber glove
after spiking when removing the cover.
7
How Dead Conductors Become Hot
8
Fundamental Of Relay Protection
9
PROTECTION EQUIPMENT.1
a. Protection System: a complete arrangement of
protection equipment and other devices required to
achieve a specified function based on a protection
principal (IEC 60255-20)- NETA
10
2. ZONES OF PROTECTION
2.1. Division of power system
into protection zones
11
2.2. Overlapping zones
of protection systems
12
3. RELIABILITY
Incorrect operation can be attributed to one of the following
classifications:
a. incorrect design/settings
b. incorrect installation/testing
c. deterioration in service
13
4. SELECTIVITY
4.1. Time Grading
4.2. Unit Systems
5. STABILITY
The term ‘stability’ is usually associated with unit protection schemes and refers to the
ability of the protection system to remain unaffected by conditions external to the
protected zone, for example through load current and external fault conditions.
14
6. SPEED
Typical power/time relationship
for various fault types
15
7. SENSITIVITY
Sensitivity is a term frequently used when referring to the minimum operating
level (current, voltage, power etc.) of relays or complete protection
schemes. The relay or scheme is said to be sensitive if the primary operating
parameter(s) is low.
With modern digital and numerical relays the achievable sensitivity is seldom
limited by the device design but by its application and CT/VT parameters.
16
8. PRIMARY AND BACK-UP
PROTECTION
Back-up protection systems should, ideally, be completely separate from the primary systems. For
example a circuit protected by a current differential relay may also have time graded overcurrent and
earth fault relays added to provide circuit breaker tripping in the event of failure of the main primary
unit protection. To maintain complete separation and thus integrity, current transformers, voltage
transformers, relays, circuit breaker trip coils and d.c. supplies would be duplicated. This
ideal is rarely attained in practice. The following compromises are typical:
a. separate current transformers (cores and secondary windings only) are provided.
This involves little extra cost or accommodation compared with the use of common
current transformers that would have to be larger because of the combined burden. This
practice is becoming less common when digital or numerical relays are used, because of
the extremely low input burden of these relay types.
b. voltage transformers are not duplicated because of cost and space considerations.
Each protection relay supply is separately protected (fuse or MCB) and continuously
supervised to ensure security of the VT output. An alarm is given on failure of the
supply and, where appropriate, prevent an unwanted operation of the protection.
17
c. trip supplies to the two protections should be separately protected (fuse or MCB).
Duplication of tripping batteries and of circuit breaker tripping coils may be provided. Trip
circuits should be continuously supervised.
d. it is desirable that the main and back-up protections (or duplicate main protections)
should operate on different principles, so that unusual events that may cause failure of
the one will be less likely to affect the other.
18
9. RELAY OUTPUT DEVICES
9.1. Contact Systems The most common types encountered are as follows:
a. Self-reset
The contacts remain in the operated condition only while the controlling quantity is applied, returning
to their original condition when it is removed.
. Contact types
19
9.2. Operation Indicators
Protection systems are invariably provided with indicating devices, called 'flags', or 'targets', as a guide
for operations personnel.
Electrical indicators may be simple attracted armature elements, where operation of the armature
releases a shutter to expose an indicator as above, or indicator lights (usually light emitting diodes).
20
10. TRIPPING CIRCUITS
There are three main circuits in use for circuit breaker tripping:
a. series sealing
b. shunt reinforcing
c. shunt reinforcement with sealing
21
11. TRIP CIRCUIT SUPERVISION
The trip circuit includes the protection relay and other components, such as fuses, links, relay contacts,
auxiliary switch contacts, etc., and in some cases through a considerable amount of circuit wiring with
intermediate terminal boards.
22
23
Protection Relay Technology
24
Relays may be classified according to the technology
used:
a. Electromechanical
b. Solid State
c. Digital
d. Microprocessor
25
1. ELECTROMECHANICAL RELAYS
These relays were the earliest forms of relay used for the protection of power systems, and they date
back nearly 100 years.
a. Attracted armature
b. Moving coil
c. Induction
d. Thermal
e. Motor operated
f. Mechanical
26
27
28
2. STATIC RELAYS
The term ‘static’ implies that the relay has no moving parts.
Introduction of static relays began in the early 1960’s. Their design is based on the use of analogue
electronic devices instead of coils and magnets to create the relay characteristic.
Early versions used discrete devices such as transistors and diodes in conjunction with resistors,
capacitors, inductors, etc., but advances in electronics enabled the use of linear and digital integrated
circuits in later versions for signal processing and implementation of logic functions.
Selection of
static relays
Compared to static relays, digital relays introduce A/D conversion of all measured analogue quantities and
use a microprocessor to implement the protection algorithm.
30
4. NUMERICAL RELAYS
The distinction between digital and numerical relay rests on points of fine technical detail, and is rarely
found in areas other than Protection. They can be viewed as natural developments of digital relays as a
result of advances in technology.
Typically, they use a specialized digital signal processor (DSP) as the computational hardware, together
with the associated software tools.
32
SIEMENS
we have :
• Siprotec 3
• Siprotec 4
• Siprotec 5
Software _ DIGSI 4
_ DIGSI 5
33
MICOM
• It can be manufacture by Schneider electric co.
• It can be manufacture by Alstom ( now it is GE ) Agile Type.
Series
1. 10 series (Schneider Co.) 2. 20 series (Schneider Co.)
3. 30 series (Schneider Co.) 4. 40 series ( Both )
5. P14,P94 Series ( Alstom , GE series )
Software
1. If Schneider electric then Easergy studio as the software
34
• Single Supply
• Multiple Supply
38
GE CONSUMER & INDUSTRIAL
MULTILIN
INDUSTRIAL SUBSTATION
ARRANGEMENTS
Utility Substation Arrangements
Bus 1
Bus 2
Breaker-and-a-half –allows reduction of equipment cost by using 3 Ring bus –advantage that one breaker per circuit. Also
breakers for each 2 circuits. For load transfer and operation is each outgoing circuit (Tx) has 2 sources of supply. Any
simple, but relaying is complex as middle breaker is responsible to breaker can be taken from service without disrupting
both circuits others.
Utility Substation Arrangements
Main bus
Aux. bus
Main
Reserve
Transfer
Bus 1
Tie breaker
Bus 2
Double Bus: Upper Main and Transfer, bottom Main-Reserved and Transfer Bus: Allows
Double Main bus maintenance of any bus and any breaker
Switchgear Defined
• Assemblies containing electrical switching, protection, metering and
management devices
• Used in three-phase, high-power industrial, commercial and utility
applications
• Covers a variety of actual uses, including motor control, distribution
panels and outdoor switchyards
• The term "switchgear" is plural, even when referring to a single
switchgear assembly (never say, "switchgears")
• May be a described in terms of use:
• "the generator switchgear"
• "the stamping line switchgear"
SWITCHGEAR EXAMPLES
SWITCHGEAR:
METAL CLAD VS. METAL-ENCLOSED
• Metal-clad switchgear (C37.20.2)
• Breakers or switches must be draw-out design
• Breakers must be electrically operated, with anti-pump feature
• All bus must be insulated
• Completely enclosed on all side and top with grounded metal
• Breaker, bus and cable compartments isolated by metal barriers, with no
intentional openings
• Automatic shutters over primary breaker stabs.
• Metal-enclosed switchgear
• Bus not insulated
• Breakers or switches not required to be draw-out
• No compartment barriering required
SWITCHGEAR BASICS [1]
• All Switchgear has a metal enclosure
• Metal clad construction requires 11 gauge steel
between sections and main compartments
• Prevents contact with live circuits and
propagation of ionized gases in the unlikely
event of an internal fault.
• Enclosures are also rated as weather-tight for
outdoor use
• Metalclad gear will include shutters to ensure
that powered buses are covered at all times,
even when a circuit breaker is removed.
SWITCHGEAR BASICS [2]
• Devices such as circuit breakers or fused switches provide protection against
short circuits and ground faults
• Interrupting devices (other than fuses) are non-automatic. They require control
signals instructing them to open or close.
• Monitoring and control circuitry work together with the switching and
interrupting devices to turn circuits on and off, and guard circuits from
degradation or fluctuations in power supply that could affect or damage
equipment
• Routine metering functions include operating amperes and voltage, watts,
kilowatt hours, frequency, power factor.
SWITCHGEAR BASICS [3]
• Power to switchgear is connected via Cables or
Bus Duct
• The main internal bus carries power between
elements within the switchgear
• Power within the switchgear moves from
compartment to compartment on horizontal bus,
and within compartments on vertical bus
• Instrument Transformers (CTs & PTs) are used
to step down current and voltage from the
primary circuits or use in lower-energy
monitoring and control circuitry.
QUESTION & ANSWER
Over Current relays OC & EF
Directional OC & Directional EF
49
50
51
52
53
54
55
56
Power Transformer & Line Protection Functions
Transformer Protection Functions
Power
Transformer
Protection
1
59
INTRODUCTION
The type of protection used should minimize the time of disconnection for
faults within the transformer and to reduce the risk of catastrophic failure.
61
WHY USE TRANSFORMER ???
The voltage level of a power is increased, the current of the power is reduced which
causes reduction in ohm or I2R losses in the system.
Low level power must be stepped up for efficient electrical power transmission.
Time required to rectify the Transformer in case of damages is more and it is very
difficult.
• A Power Transformer fault therefore often is a more severe disturbance for the
network than an overhead line fault which usually can be repaired rather quickly.
7 63
INDUCTION LAW
64
POWER TRANSFORMER
65
POWER TRANSFORMER DIAGRAM
66
WHAT CAUSE TRANSFORMER FAILURE?
Insulation Breakdown
Over heating due to over excitation
Oil contamination and leakage
Cooling system failure
Phase to phase and Phase to Ground Fault
Turn to Turn Fault
Transformer Overload
67
WHAT CAUSE TRANSFORMER FAILURE?
Bushings failures 9%
Core failures 2%
Winding Bushing
General aging
Moisture
Contamination
Vibration
Cracking
Overheating Internal moisture
69
Voltage surge
WHAT CAUSE TRANSFORMER FAILURE?
• Metal particle 70
• Moisture
TRANSFORMER FAULTS
1. Overloads
1. Winding Failure
2. Overvoltage
2. Winding inter-turn faults
3. Over heating
3. Core insulation failure, shorted
4. External system short circuits.
laminations
4. Over fluxing.
71
TRANSFORMER FAULTS
Mechanical Electrical
1. Buchholz relay 1. Bias Differential Protection (87)
73
BUCHHOLZ RELAY PROTECTION
74
BUCHHOLZ RELAY PROTECTION
The Buchholz relay is placed between the main tank and the
conservator.
Such type of relay is used in the transformer having the rating higher
than 500KVA.
75
BUCHHOLZ RELAY PROTECTION
When the fault occurs inside the transformer, the temperature of the oil
increases. The oil evaporates in the form of the gas.
The generation of the gas depends on the magnitude of the fault occurs
inside the transformer.
The internal failure occurs in the transformer either because of the insulation
breakdown between the winding or the winding have the weak initial contact.
76
BUCHHOLZ RELAY PROTECTION
77
BUCHHOLZ RELAY PROTECTION
The relay has two elements 1st stage and 2nd stage. The 1st stage for
alarm and the 2nd stage for trip.
The 1st stage work on the accumulation of sufficient gas in the relay chamber
and the 2nd stage work on the high velocity of oil caused due to evolution of
gases as a result of high energy faults.
The setting of 1st stage is done at collected gas volume of 300 to 500ml.
The setting of 2nd stage is done at oil flow velocity of 100cm/s .
78
BUCHHOLZ RELAY PROTECTION
79
SUDDEN PRESSURE RELAY PROTECTION
80
SUDDEN PRESSURE RELAY PROTECTION
• This protection performs better and faster than Buchholz relay 2nd stage protection.
The relay detects a sudden rise in pressure. The alarm is set at 0.32kg/sqcm and
trip at 0.6kg/sq cm per second.
81
26
PRESSURE RELIEF PROTECTION
82
PRESSURE RELIEF PROTECTION
28 83
FIRE PROTECTION
This produces arcing which in turn overheats the insulating oil and
causes the tanks to rupture; further arcing then will start a fire.
84
FIRE PROTECTION
85
LIGHTNING PROTECTION
The charge from the surge produces both short duration high current
impulse and long duration continuing current impulse which affects the
transformer insulation system.
86
LIGHTNING PROTECTION
87
CELICA GEL BREATHER
The purpose of these silica gel breathers is to absorb the moisture in the
air sucked in by the transformer during the breathing process.
88
CELICA GEL BREATHER
89
CELICA GEL BREATHER
During the breathing process, the incoming air may consist of moisture
and dirt which should be removed in order to prevent any damage.
Hence the air is made to pass through the silica gel breather, which will
absorb the moisture in the air and ensures that only dry air enters in to
the transformer.
Silica gel in the breather will be blue when installed and they turn to
pink colour when they absorb moisture which indicates the crystals
should be replaced.
These breathers also have an oil cup fitted with, so that the dust
particles get settled in the cup.
90
CELICA GEL BREATHER
91
3
OIL LEVEL GAUGE
BLADD
@R
OIL LWEL
G+UOE
RELAY
SHUT-
OFF¥ALVE
TRAN4FORNER
TANK
93
OIL LEVEL GAUGE AND ITS IMPORTANCE
If they are not equal it means that a fault occurs between the two ends. 95
DIFFERENTIAL RELAY PROTECTION
96
DIFFERENTIAL RELAY PROTECTION
97
DIFFERENTIAL RELAY PROTECTION
98
RESTRICTED EARTH FAULTS RELAY PROTECTION
The term "REF protection method " means not to sense any earth faults
outside this restricted zone. This type of protection is prevalent in Dyn
group of transformers (Delta Primary and Star Secondary).
99
RESTRICTED EARTH FAULTS RELAY PROTECTION
100
RESTRICTED EARTH FAULTS RELAY PROTECTION
Differential protection has excellent operation in most fault cases, but in the
situations that a single phase to ground fault that current increases slightly and
causes differential protection not to detect the fault.
Differential relay will operate for earth faults inside the zone only if the earth fault
current is more than the bias setting in the relay. The normal bias setting in a
101
102
OVER FLUXING PROTECTION
The flux in the core increases with either increasing voltage or decreasing
frequency.
103
OVER FLUXING PROTECTION
Over fluxing relays are so adjusted, that for every transient over flux
condition the transformer does not trip for maintaining the power
system stability.
the Transformer.
105
OVERCURRENT BACK UP PROTECTION
It operates whenever the current pass CTs exceed the setting values.
These over current are mostly Inverse Definite Minimum Time (IDMT) or
Definite Minimum Time (DMT).
The setting is done at 300% of the rated current and no case shall be less
than 175%.
106
SUMMARY
107
SUMMARY
108
Condition Monitoring For Transformers:
QUESTION & ANSWER
Line Protection Functions for Over Head Line
Type of protection that we use at Line protection:
G G
N.O.
N.C.
Fault
Load
Graded distance zones
Z3
t = grading time
time Z2 t3
Z1 t2
t1
A B C D
D1 D2 D3
distance
Grading rules:
Safety margin is 15 %:
Z1 = 0,85 ZAB - line error
- CT, VT error
Z2 = 0,85 (ZAB + 0,85 ZBC) - measuring error
Z3 = 0,85 (ZAB + 0,85 (ZBC + 0,85 ZCD))
Determination of grading times (At numerical relays 250 ms are possible )
2nd Zone: It must initially allow the 1st zone on the neighbouring feeder(s) to clear the fault.
The grading time therefore results from the addition of the following times:
+errors of the distance relay internal timers mechanical: 5% of the set time, minimum 60-100 ms
static: 3% of the set time, minimum 10 ms
digital: 1% of the set time, minimum 10 ms
+distance protection starting time * mechanical: O/C starter: 10 ms, impedance starter: 25 ms
static: O/C starter: 5 ms, impedance starter: 25 ms
digital: generally 15 ms
)
Power system
RAB is the angle by which the fault current lags the relay voltage for
a fault on the line
AB and RAC is the equivalent leading angle for a fault on
line AC
AM for all faults behind the bus bars up to an impedance
AL represents the reach of instantaneous Zone 1 protection, set to
cover 80% to 85% of the protected line
Disadvantages :
It is non-directional
It has non-uniform fault resistance coverage
• Zone 1:
131
STEP DISTANCE SCHEMES
132
STEP DISTANCE SCHEMES
133
STEP DISTANCE SCHEMES
134
STEP DISTANCE SCHEMES
135
STEP DISTANCE PROTECTION
136
STEP DISTANCE COORDINATION
137
NEED FOR PILOT AIDED SCHEMES
138
PILOT COMMUNICATIONS CHANNELS
140
PILOT-AIDED DISTANCE-BASED SCHEMES
• Requires only underreaching (RU) functions which overlap in reach (Zone 1).
• Applied with FSK channel
o GUARD frequency transmitted during normal conditions
o TRIP frequency when one RU function operates
• Scheme does not provide tripping for faults beyond RU reach if remote breaker is
open or channel is inoperative.
143
PERMISSIVE UNDERREACHING TRANSFER TRIP (PUTT)
144
PUTT SCHEME
145
PERMISSIVE OVERREACHING TRANSFER TRIP (POTT)
147
POTT SCHEME
148
POTT SCHEME
149
POTT SCHEME
150
POTT SCHEME
151
POTT SCHEME
152
HYBRID POTT
153
HYBRID POTT
154
DISTANCE RELAY APPLICATION EXAMPLE
48.42<80 °Ω
Z3 Phase reach
QUESTION & ANSWER
Other PROTECTION Or CONTROL Functions
Auto-Recloser Or 79 :
Why we use 79 :
It can be 1 pole Or 3 pole operation.
A lot of fault can be transient , so 79 function can be really useful.
1- At distribution system we use reclosing to give the consumer the better service.
2- At Transmission system we use 79 as the purpose of stability.
Two stage
Fast reset (12ms)
External initiation
One timer per phase
Retrip
Trip
BF
INIT
Fault location:
Distance to fault
V and I measurements
Generator protection Functions
Generator protection functions:
It is unit type protection, covering the stator winding for phase to phase faults due to
breakdown of insulation between stator phase windings. This relay is not sensitive for
single line to earth faults as the earth fault current is limited due to the high neutral
earthling resistance.
If CTs of identical ratios are used on neutral and line side of generator, an operating
current setting of 20% it can be adopted. It is instantaneous in operation and it trips the
generator breaker (Class – A) to eliminate the system in – feed to the fault along with
field breaker and turbines.
For all machines of ratings 10 MVA and above, this protection shall be provided.
Diagram:
Settings:
Pickup Value of Differential Current: 0.10 I/InO
T I-DIFF> Time Delay: 0.00 sec
Pickup Value of High Set Trip: 2.0 I/InO
T I-DIFF>> Time Delay: 0.00 sec
With the size and voltage output of generators increasing, this form of protection is
becoming essential for all generating units.
Diagram:
It is a common practice to use the differential relay as primary fault protection for the
generator. Backup fault protection is also highly recommended to protect the generator from
the effects of faults that are not cleared because of failures within the normal protection
scheme. The backup relaying is automatically applied to provide protection in the event of a
failure at the eneration station, on the transmission system, or both.
protection for generators in case of a failure at the generation station Specific generating station
failures would include the failure of the generator or Generator Step Up (GSU) transformer
differential scheme. On the transmission system, failures would include the line protection
relay scheme or the failure of a line breaker to interrupt.
Table of contents:
185
Documents & Schematic Diagram
186
187
188
189
Power Supply For SUB1&2
190
Current From CT (Core 1 & 2 )
191
Voltage From VT
192
Binary Outputs of protection relay
193
Binary Inputs of protection relay
194
Trip Circuit Supervision
195
Protection Relay test Equipment
196
Test Block for isolating protection relay at test sequence
197
Aux Supply of Protection Relay
198
Va
3 Phase Voltage Test
Vb
Output Up to 125 V Block
VaVbVc Vn EX:
Vc
Vn
MMLG01
199
How to enable Or Disable Voltage
output of Omicron
200
Ia
3 Phase Current Test
Ib
Output Up to 12.5 A Block
Ia Ib Ic In EX:
Ic
In
MMLG01
202
Binary Input From Omicron To
Binary Output of Protection Relay
Test
Block
EX:
MMLG01
203
How to enable Or Disable Binary
Input of Omicron
204
Negative (- ) of
DC From Any
where at
Schematic
diagram
Test
Block
EX:
MMLG01
Positive (+) of
DC From Any
where at
Binary Output From Omicron To
Schematic
Binary Input of Protection Relay
diagram
205
How to enable Or Disable Binary Out put of
Omicron
206
1- Current Test
A. Measurement
A.1. Magnitude
A.2. Phase
A.3. Frequency
Pick up
1.01 A
point
I Set (A)
Drop off
0.98A
Point
207
C. Time Test
C.1. DMT (DT)
C.2. IDMT(Curve)
208
209
How TMS Works At
IDMT Curves?
210
2- Differential test
A. Measurement
A.1. Magnitude
A.2. Phase
A.3. Frequency
Tool for Creating Control Logic, Simulation Testing, and Communications Server
Commissioning OPC/DDE Server
Design Logic with Drag-and-Drop ease Send device data to HMI, DCS, and SCADA systems
Real-time feedback of FlexLogic™ states Contains memory maps for GE Devices and firmware
Documentation of Logic Automatic Fault Data Collection
Commissioning Procedures and Tools
Troubleshooting and Reporting Tools Energy Coast Allocation and Billing Software
Single click retrieval of Fault Data Monitor Energy Consumption of parts of a facility
Security Audit Report shows details of setting changes Allocate energy costs to various departments
Health Report showing status of Protective Devices Save energy costs via analysis of energy consumption
Track Firmware Configuration changes to GE devices Perform statistical analysis to avoid peak demand surcharges
Enervista Launchpad
Easy to use Device Setup & Document Management Toolset
Simplifying Engineering effort required for the configuration of relays and meters
Enervista Launchpad
Easy to use Device Setup & Document Management Toolset
Metering
• Status of all inputs and outputs
• Real-Time monitoring of Phasor diagrams
• Analyzing of Current and Voltage Harmonics
• Viewing of Alarms and Relay Front Panel
Troubleshooting
• Analyzing of Event Records
• Powerful Oscillography COMTRADE Viewer
• Real Time Data Logging
• Compare relay settings with setting file
Enervista Launchpad
Easy to use Device Setup & Document Management Toolset
Multiple-Language Support
Languages Supported in UR setup
program:
• English
• French
• Chinese
• Russian
Easy to use Monitoring and Data Recording for Tool for Control Logic Creation, Simulation Troubleshooting and Reporting Tools
Small Systems Testing, & Commissioning
(IEC 61850 Option available)
Viewpoint Monitoring
Easy to use Monitoring and Data Recording for Small Systems
Identify Power System Problems and Automatically Gather Fault Data for Troubleshooting
Viewpoint Monitoring
Easy to use Monitoring and Data Recording for Small Systems
PLUG-AND-PLAY MONITORING GLOBAL COMTRADE VIEWER
AUTOMATIC EVENT AND WAVEFORM RETRIEVAL AUTOMATIC EVENT AND WAVEFORM RETRIEVAL
Status of your GE Multilin Relay Latched Alarms that require clearing Learned motor load
METERING TRIP MAINTENANCE
All metering quantities (Amps, Volts, Power, Demand) Cause of the last motor trip Trip counters and motor Starts
Motor temperature monitored by the RTD’s Pre-trip data Total motor running hours
Viewpoint Monitoring
Plug and Play Monitoring Applications
Motor Monitoring
Power Quality Monitoring
Generator Monitoring
Viewpoint Monitoring
Single-Line Monitoring and Control
Waveform Archiving
• Waveform files from GE Multilin Devices automatically downloaded from a device
and stored on your hard drive
• Devices continually polled to check for new Waveforms
• Diagnose waveform fault data recorded in your power system device in a Time-
based, Phasor Quantity and Tabular view
Viewpoint Monitoring
Trending Reports
Annunciator Alarming
Supported Devices
Viewpoint Monitoring
Third Party Device Support
*Automatic Waveform and Event retrieval for third party devices shipping in 2006
Viewpoint Monitoring
Ordering Information
Graphical Control Logic Tool that offers Real-time Feedback of Logic Status
Viewpoint Engineer
Graphical Flexlogic Designer
Design Control Logic in this intuitive, easy to use IEC 1131 Graphical Logic Designer
• Simplify the process of creating complex control logic for Substation Automation such as advanced
Tripping, Reclosing and Transfer Schemes.
• Design Logic with drag and drop ease using a library of inputs, outputs, logic gates, symbols and
configuration tools
Optimizes control logic equations to obtain maximum efficiency and to use the fewest possible lines of
logic
Viewpoint Engineer
Real-Time Flexlogic Analyzer
Analyze the Status of each component of your UR Flexlogic in Real-Time
• Identify which inputs are triggering and enabling each logic gate
• Create Logic in an Graphical IEC 1131 Editor • Link Control Logic from multiple UR Devices • Link Control Logic from multiple UR Devices
• Analyze status of logic in Real-Time • Create Setting Files for multiple UR’s • Create Setting Files for multiple UR’s in IEC 61850
• Analyze the status of Peer-to-Peer messages in format
Real-Time • Analyze the status of Peer-to-Peer messages in Real-
• Shipping Q1, 2006 Time
• Shipping Q4, 2006
Viewpoint Engineer
Ordering Information
Viewpoint Maintenance
Troubleshooting and Reporting Tools
Helping Electrical Staff gather Fault Diagnostics, Security Audits and Device Status
Viewpoint Maintenance
Software Tool that creates reports to simplify all Maintenance Tasks
Viewpoint Maintenance will provide the following reports to simplify all maintenance tasks
• Fault Diagnostics Repot
• Device and Equipment Status Report
• Settings Security Report
...and stores the zipped file on your hard drive for easy
emailing to your engineers or instantly emails to GE Tech
support
Viewpoint Maintenance
Equipment Status Reports
Viewpoint Maintenance
Setting Security Report
Viewpoint Maintenance
Ordering Information
EnerVista Integrator
HMI
Communications Server
EnerVista Integrator
EnerVista Integrator
Powerful OPC / DDE Communications Server
Makes it easy to integrate Multilin Devices into existing Systems
EnerVista Integrator
Automatic Event and Waveform Retrieval
Event Logging
• Automatic download of events which are stored in a system wide Sequence of
Event Record
• Devices continually polled to check for new Events
• Sort and Query system event record to view events categorized by date, device
type, timestamp, or customized criteria
• No configuration required
Waveform Archiving
• Waveform files from GE Multilin Devices automatically downloaded from a device
and stored on your hard drive
• Devices continually polled to check for new Waveforms
• Diagnose waveform fault data recorded in your power system device in a Time-
based, Phasor Quantity and Tabular view
EnerVista Integrator
Ordering Information
EnerVista Energy Aggregator
Monitor Energy Consumption from different parts of a facility and allocate costs to various
departments based on the energy they used
EnerVista Software
Viewpoint Monitoring
PLUG-AND-PLAY MOTOR MONITORING
Instantly view critical data including:
• Motor Temperature
Back to Presentation
Viewpoint Monitoring
PLUG-AND-PLAY FEEDER MONITORING
• Breaker Status
• Synchronism data
Back to Presentation
Viewpoint Monitoring
PLUG-AND-PLAY TRANSFORMER MONITORING
Instantly view critical data including:
Back to Presentation
Viewpoint Monitoring
PLUG-AND-PLAY GENERATOR MONITORING
Instantly view critical data including:
• Generator Loading
• Generator Temperature
Back to Presentation
Viewpoint Monitoring
PLUG-AND-PLAY POWER QUALITY MONITORING
Instantly view critical data including:
Back to Presentation
Viewpoint Monitoring
PLUG-AND-PLAY BACKUP MONITORING
Instantly view critical data including:
Back to Presentation
Viewpoint Monitoring
PLUG-AND-PLAY BREAKER MONITORING
Instantly view critical data including:
• Breaker Status
Back to Presentation
Viewpoint Monitoring
Appendix A – Supported Devices
The following Devices and Firmware Versions are supported by Viewpoint
Motor Prote ctionMonitoring Version 5.00
Firm w a re Ve rsion Supporte d Tra nsform e r Prote ction Firm w a re Ve rsion Supporte d
239 2.3x, 2.4x, 2.5x, 2.6x SR745 2.4x, 2.5x, 2.6x, 2.8x
269 6.0x 2.4x, 2.6x 2.8x, 2.9x, 3.0x, 3.1x, 3.2x,
T35
369 1.6x, 1.7x, 1.8x, 1.9x, 2.0x 3.3x, 3.4x, 4.0x, 4.2x
SR469 2.5x, 2.6x, 2.8x, 2.9x, 4.0x 1.8x, 2.0x, 2.2x, 2.4x, 2.6x 2.8x, 2.9x,
T60
2.6x 2.8x, 2.9x, 3.0x, 3.1x , 3.2x, 3.3x, 3.0x, 3.1x, 3.2x, 3.3x, 3.4x, 4.0x, 4.2x
M60
3.4x, 4.0x, 4.2x Tra nsm ission Line Prote ction Firm w a re Ve rsion Supporte d
MM2 4.0x, 4.1x, 5.0x, 5.1x D30 3.0x, 3.1x, 3.2x, 3.3x, 3.4x, 4.0x, 4.2x
MM3 1.0x. 1.1x, 1.2x 1.8x, 2.0x, 2.2x, 2.4x, 2.6x 2.8x, 2.9x,
RRTD 1.4x, 1.5x D60
3.0x, 3.1x, 3.2x, 3.3x, 3.4x, 4.0x, 4.2x
SPM 2.0x, 2.1x
1.8x, 2.0x, 2.2x, 2.4x, 2.6x 2.8x, 2.9x,
Fe e de r Prote ction Firm w a re Ve rsion Supporte d L90
3.0x, 3.1x, 3.2x, 3.3x, 3.4x, 4.0x, 4.2x
SR735/737 1.5x
1.8x, 2.0x, 2.2x, 2.4x, 2.6x 2.8x, 2.9x,
SR750/760 3.6x, 3.7x, 4.0x, 5.0x, 6.0x L60
3.0x, 3.1x, 3.2x, 3.3x, 3.4x, 4.0x, 4.2x
F650 1.3x, 1.4x
Controlle rs Firm w a re Ve rsion Supporte d
1.8x, 2.0x, 2.2x, 2.4x, 2.6x 2.8x, 2.9x,
F35 Micro Versa Trip Units 5.16
3.0x, 3.1x, 3.2x, 3.3x, 3.4x, 4.0x, 4.2x
Enhanced Micro Versa Trip Units 4.13
1.8x, 2.0x, 2.2x, 2.4x, 2.6x 2.8x, 2.9x, 1.8x, 2.0x, 2.2x, 2.4x, 2.6x 2.8x, 2.9x,
F60 C30
3.0x, 3.1x, 3.2x, 3.3x, 3.4x, 4.0x, 4.2x 3.0x, 3.1x, 3.2x, 3.3x, 3.4x, 4.0x, 4.2x
Bus Firm w a re Ve rsion Supporte d 1.8x, 2.0x, 2.2x, 2.4x, 2.6x 2.8x, 2.9x,
C60
2.2x, 2.4x, 2.6x 2.8x, 2.9x , 3.0x, 3.1x, 3.0x, 3.1x, 3.2x, 3.3x, 3.4x, 4.0x, 4.2x
B30
3.2x, 3.3x, 3.4x, 4.0x, 4.2x Me te rs Firm w a re Ve rsion Supporte d
Ge ne ra tor Firm w a re Ve rsion Supporte d EP M 5000P 3.9
SR489 1.3x, 1.4x, 1.5x EPM 5200/ E PM 5300/ EPM 5350 2.4
2.2x, 2.4x, 2.6x 2.8x, 2.9x , 3.0x, 3.1x, EP M 9450/ E PM 9650 217
G60
3.2x, 3.3x, 3.4x, 4.0x, 4.2x PQM 3.3x, 3.4x, 3.5x, 3.6x
Tra nsfe r Sw itche s Firm w a re Ve rsion Supporte d PQMII 1.0x, 2.0x, 2.2x
MX150 5.4x, 6.0x
MX250 5.4x, 6.0x Back to Presentation
Viewpoint Maintenance
Software Tool that creates reports to simplify all Maintenance Tasks
Back to Presentation
Question & Answer
INSTRUMENT TRANSFORMERS
Instrument Transformers
What is an Instrument Transformer ?:
• It is a transformer that is used in conjunction with any measuring instrument (i.e., Ammeter,
Voltmeter, Wattmeter, Watt-hour-meter, …etc.)or protective equipment (i.e., Relays).
• It utilizes the current-transformation and voltage transformation properties to measure high ac current
and voltage.
INSTRUMENT TRANSFORMERS
1. Current transformers
2. Potential Or Voltage transformers
INSTRUMENT TRANSFORMERS
Applications of Instrument Transformers:
• For measurement of high ac current, it is usual to use low range ac ammeter with
suitable shunt.
• For measurement of high ac voltage, low range ac voltmeters are used with high
resistances connected in series.
• For measurement of very high ac current and voltage, we cannot use these
methods. Instead, we use specially constructed HV instrument transformers to
insulate the high voltage circuit from the measuring circuit in order to protect the
measuring instruments from burning.
INSTRUMENT TRANSFORMERS
• Application of Instrumentation Transformers In dc circuits for current
and voltage measurement, we use low range dc ammeters and
voltmeters with rectifiers connected in their secondary circuits.
• The vast primary application of Instrument Transformers is for the
protection and control of power system and power equipment of high
and very high ratings.
• The working of these instrument transformers are similar to those of
the ordinary transformers.
INSTRUMENT TRANSFORMERS
• C.T. has a primary coil of one or more turns made of thick wire connected in
series with the line whose current is to be measured.
• The secondary consists of a large number of turns made of fine wire and is
connected across an ammeter or a relay’s terminals.
CONSTRUCTION TYPES OF CURRENT
TRANSFORMERS
Window-type Bar-type
CURRENT TRANSFORMERS
Function of CT:
• The principal function of a CT is to produce a proportional current at a level of
magnitude, which is suitable for the operation of low-range measuring or
protective devices such as indicating or recording instruments and relays.
• The primary and secondary currents are expressed as a ratio such as 100/5 or
1000/5 .
• With a 100/5 ratio CT, 100A flowing in the primary winding will result in 5A
flowing in the secondary winding, provided that the correct rated burden is
connected to the secondary winding.
CURRENT TRANSFORMERS
“Class” of a CT:
• The extent to which the actual secondary current magnitude differs from the calculated
value, expected by the virtue of the CT ratio, is defined as the accuracy “Class” of the
CT.
• The greater the number used to define the class, the greater the permissible “current
error” [the deviation in the actual secondary current from the calculated value].
CURRENT TRANSFORMERS
Specifications of CT:
CTs should be specified as follow:
RATIO : Input / output current ratio
VA: Total burden (rating) including pilot wires.
Common burden ratings are 2.5, 5, 10, 15 and 30 VA. For example:
• Moving iron ammeter is 1-2 VA
• Moving coil rectifier ammeter is 1-2.5 VA
• Electro-dynamic instrument is 2.5-5 VA
• Maximum demand ammeter is 3-6 VA
CURRENT TRANSFORMERS
Single-Ratio Multi-Ratio CT
CT
Multi-ratio CT:
• As indicated in the previous Figure, current transformers having a center tapped secondary are
referred to as a dual ratio CT.
• Dual ratio CT are used in applications where it is necessary to have available two ratios of
primary to secondary current from the same secondary winding of the CT.
• This may be accomplished by adding a tap in the secondary winding to get a second ratio.
• The ratio obtained by the tap is usually one-half the ratio obtained by the full secondary
winding.
• A schematic example is previously shown with 200 amperes flowing in the primary, a
connection X2 – X3 will produce 5 amperes out of the secondary. As the load grows to 400
amperes, the secondary circuit will be reconnected to X1 – X3 to still produce 5 amperes in the
secondary circuit.
CURRENT TRANSFORMERS
Working (Measurement):
• If a current transformer has primary to secondary current ratio of 100:5 then it steps up the voltage 20
times and step down the current 1/20 times of its actual value.
• If we know the current ratio and the reading of an a.c. ammeter, the primary current can be calculated as:
Iron Core
• The `doughnut' fits over the primary conductor, which constitutes one primary turn. If
the toroid is wound with 240 secondary turns, then the ratio of the C.T. is 240 : 1 or
1200 : 5A
• This type of `doughnut' C.T. is most commonly used in circuit breakers and power
transformers. The C.T. fits into the bushing, and the porcelain bushing fits through the
centre of the `doughnut'.
• Up to four C.T.'s of this type can be installed around each bushing of an oil circuit
breaker. This arrangement is shown in a following diagram.
Substation Class Circuit Breakers' CTs
100
___ = 100:5 or 20:1
5
Polarity Direction of
Secondary Current
Direction of
Primary Current
X1 IEEE Secondary
IEEE H1
S1
IEC Polarity
Primary Marks
Polarity
Marks IEC P1
X1 IEEE Secondary
IEEE H1
S1
IEC Polarity
Primary Marks
Polarity
Marks IEC P1
Direction of
Primary Current
Then:
ZT = RCT + RL + ZB
ZT = Total burden in ohms (vector summation of
resistance and inductance components)
RCT = CT secondary resistance in ohms @75 deg C
RL = Resistance of leads in ohms (Total loop distance)
ZB = Device impedance in ohms
CT Saturation
Factors Affecting Degree and Time to Saturation
1. High DC offset
2. High fault current Magnitude (symmetrical current)
Example:
•100 to 5 CT@20 times= 2000 amps.
•Also @20,000 amps we have 200 times CT
3. Low CT Turns Ratios
4. High secondary burden
5. Low CT Accuracy (Class)
6. High reminance flux
• Can occur if current interrupted when core is saturated
• If DC flows in windings during testing
• Need a voltage above 60% of knee point to reduce the Reminance to less than 10% of saturation flux
density.
Tips for Avoiding CT Saturation
1. Use higher ratio CTs
2. Use separate set of high ratio CTs for high fault current
tripping
3. Reduce secondary burden by:
-Selecting low burden relays & meters
-Distributing single phase burdens among phases
-Increasing the size of secondary leads
-Reducing the length of secondary leads
-Using “step down” auxiliary CTs
Avoiding CT Saturation
with Linear Operation
(Knee limit of the Curve)
CT Actual Connections
Typical window CT
Power Transformers’ CT Connections
Slip over current transformer for installation over exterior
of outdoor bushing
• A PT or sometimes called VT is a step-down transformer having many primary turns but few
secondary turns.
• In a step-down transformer the voltage decreases and the current increases, thus voltage can be
easily measured by using a low-range voltmeter instrument.
• The voltage is stepped-down in a known ratio called the voltage ratio.
POTENTIAL TRANSFORMERS
Construction and working of P.T.:
Construction
• A potential transformer has many primary winding turns but few number of secondary winding turns that makes it a step-
down transformer.
• A Voltmeter is connected to the secondary winding is usually a voltmeter of 150 V.
Working (Measurement):
• Primary terminals are connected in parallel across the line to which the voltage is to be measured.
• The voltmeter reading gives the transformed value of the voltage across the secondary terminals.
• The deflection of the voltmeter when divided by the transformed ratio gives the actual voltage across the primary winding as:
• Since the secondary of a p.t. is connected to relays, their ratings are usually
40 to 100 Watts.
• For safety purpose the secondary should be completely insulated from the
high voltage primary and should be in addition grounded.
POTENTIAL TRANSFORMERS
Types of P.T. :
Some types of p.t. are:
• Shell type
• Dry type
• Oil type
Rating Type
1. Below 5000 v Shell type
2. 5000-13800 v Dry type and oil type
3. Above 13800 v only oil type
Potential Transformer
Common Ratios
VP
14,400/120 = 120/1
4200/120 = 35/1
2400/120 = 20/1
Vs
Relay
CONNECTIONS OF 1-PHASE POTENTIAL TRANSFORMERS
Other PT and 3-Phase Typical Connections
Y – Broken Corner VT
Connection
damping resistor R
Other PT and 3-Phase Typical Connections