case 1 is like this: if we want to transfer House load 1 from PLN to PP then we select 25 G1 trigger HBT. After that Generator 1 will adjust until Voltage, frequency & phase angle in 1PP-SG-TG-02 same as 1PP-SG-TG-04 then transfer HBT C. The Red line is Gen1 power & the blue is PLN power.
The existing 25 G1 trigger HBT C
case 2 is like this: if we want to transfer House load 1 from PP to PLN then we select 25 G1 trigger HBT. After that Generator 1 will adjust until Voltage, frequency & phase angle in 1PP-SG-TG-04 same as 1PP-SG-TG-12 then transfer. Existing 25 G1 Trigger HBT C Logic :
For confirmation. In Case 1 : VT1 is 1PP-SG-TG-02 VT2 is 1PP-SG-TG-04
In Case 2 : VT1 is 1PP-SG-TG-04
VT2 is 1PP-SG-TG-12
Is it correct? The Red line is Gen2 power & the blue is PLN power.
The new 25 G2 trigger HBT C
case 1 is like this: if we want to transfer House load 1 from PP to PLN then we select 25 G2 trigger HBT. After that Generator 2 will adjust until Voltage, frequency & phase angle in 1PP-SG-TG-02 same as 1PP-SG-TG-04 then transfer HBT C. The Red line is Gen2 power & the blue is PLN power.
The new 25 G2 trigger HBT C
case 2 is like this: if we want to transfer House load 1 from PP to PLN then we select 25 G2 trigger HBT. After that Generator 2 will adjust until Voltage, frequency & phase angle in 1PP-SG-TG-04 same as 1PP-SG-TG-12 then transfer HBT C. New 25 G2 Trigger HBT C Logic :
In Case 1 : VT1 is 1PP-SG-TG-02
VT2 is 1PP-SG-TG-04 G2 In Case 2 : VT1 is 1PP-SG-TG-04 GCP2 VT2 is 1PP-SG-TG-12 G2