AC for Admin Building

Issues & Possible Solutions


AC Details
Admin Building Management Canteen Workers Canteen

1 x 40 RT for Ground Floor


1 x 40 RT for First Floor

• Make: Trane
• Model: RAUA -400
• Capacity: 40 RT
• Installed Qty: 2
• Type: Direct/Split
• Installation Year: 1882
Current Issues

• Running life of 40 years against ASHARE recommend life of 15 years


• Obsolete Feron refrigerant – R22
• Availability of gas will be a challenge in coming years
• Non-availability of spares
• OEM support is not available
• Low efficiency (high power consumption)
• Running with retrofit low capacity compressor (34 RT against 40 RT)
• Compressors from Carrier Chiller at BX plant are being used
• De-graded Condenser & Evaporator coil
• Deteriorated structure
• Repeated Gas leakages, weak & brittle pipping
Current Issues – Compressor

Original Existing – In Use

TRANE CARRIER
CRHR 400 06EF-299-940E
Reciprocating Reciprocating
40 RT 34 RT
Current Issues – Refrigerant Gas
Possible solutions

Option # 1 Option # 2 Option # 3


• Replacement of Compressor only with • Complete replacement of
refurbished compressor (same type) • Installation of individual split AC unit • Condenser Unit
• Replacement of damaged copper tubing • Evaporator Coil
• Blower

1,200,000 PKR 4,500,000 PKR 12,000,000 PKR


Cost

• • Low Cost • Long Life (15-20 years) & Reliability


Low Cost
Pros • Immediate
• Energy Saving •

Eco friendly refrigerant R410A
• Immediate Energy Saving

• No Guarantees • Short Life span (5-10 years) • High Cost


• Low performance • Maintenance intensive
• Non-sustainable due to R-22 Issue
Cons • Higher cost of Refrigerant
• High Energy Consumption
• High noise & vibrations
Thank You