Professional Documents
Culture Documents
Power System Analysis
Power System Analysis
To monitor the voltage at various buses, real and reactive power flow between
buses.
To study the ability of the system for small and large disturbances (Stability studies)
Components of power system
1. Alternator
2. Power transformer
3. Transmission lines
4. Substation transformer
5. Distribution transformer
6. Loads
SINGLE LINE DIAGRAM
The ratings and the impedance of the components are also marked on the single line
diagram.
Single line diagram
Purpose of using single line diagram
The purpose of the single line diagram is to supply in concise form of the significant information
about the system.
The per unit value of any quantity is defined as the ratio of the actual value of the any
quantity to the base value of the same quantity as a decimal.
The components or various sections of power system may operate at different voltage and power
levels. It will be convenient for analysis of power system if the voltage, power, current and
impedance rating of components of power system are expressed with reference to a common value
Symmetrical components
Introduction
In balanced system,analysis can be done on a single phase basis. The knowledge of voltage and current in one
phase is sufficient to determine the voltage and current in other two phases.
Real and reactive powers are three times the corresponding per phase values.
When the system is unbalanced,the voltages, the current and the phase impendences are in general unequal.
Unbalanced system operation can result due to unsymmetrical fault, such ass:
1. single line to ground
2. line to line fault
3. double line faoult
4. double line to ground fault
5.three line fault and
6. three line to grond fault
Cont…
Unbalanced operation may also result when loads are unbalanced. unbalanced
operation can be analyzed through symmetrical component.
Unbalanced three phase voltages and currents are transformed into 3 set of
balanced voltages and currents called symmetrical components.
Symetrical components
Since the direct solution of such a circuit is very difficult, the solution can be more
easily obtained by using symmetrical components since this yields three (fictitious)
single phase networks, only one of which contains a driving emf
General principles
Any set of unbalanced 3-phase voltages (or current) can be transformed into 3 balanced sets. These are:
1.positive sequence
A positive sequence set of three symmetrical voltages (i.e. all numerically equal and all displaced from each
other by 1200) having the same phase sequence abc as the original set and denoted by Va1,Vb1,Vc1 as
shown in the fig(1a)
2. Negative sequence
A negative sequence set of three symmetrical voltages having the phase sequence opposite to that of the original
set and denoted by Va2, Vb2, Vc2 as shown in fig(1b)
3.Zero sequence
3. A zero sequence set of three voltages, all equal in magnitude and in phase with each other and denoted by
Va0, Vb0, Vc0 as shown in fig (1c) below:
Unsymmetrical fault
Introduction
The term unsymmertrical fault is used to mean an unbalanced condition.
It is a connection or situation which causes an unbalance among the three
phases. If an unbalanced connection is attached at a point F on a balanced
system then F is called the fault point of the system.
Thus, if there is a single line to ground fault at bus M then bus M becomes the
fault point.
The different types of unbalanced fault that occurs in power systems are:
1. shunt type fault and 2. series type fault
Shunt type fault