You are on page 1of 10

Siemens Switzerland Ltd 2007

Synco
TM
700 instaIIation
:ilding Technologies / HVP SYS SYN Ren Kmpfer
Siemens Switzerland Ltd 2007
Page 2 August 02
Synco
TM
700 ControIIers - Mounting Methods
ControI paneI mounting with RMZ790 ControI paneI mounting with RMZ791
:ilding Technologies / HVP SYS SYN Ren Kmpfer
Siemens Switzerland Ltd 2007
Page 3 August 02
Mounting the Extension ModuIes
snap
nsert mod:le vertically along the g:ide rails :ntil it snaps a:dibly on the
DN rail.
1 2
:ilding Technologies / HVP SYS SYN Ren Kmpfer
Siemens Switzerland Ltd 2007
Page 4 August 02
RemovaI of Extension ModuIes
&se a screwdriver (no. 1) to p:sh snap-on element in the release
position and remove mod:le.
1 2
:ilding Technologies / HVP SYS SYN Ren Kmpfer
Siemens Switzerland Ltd 2007
Page 5 August 02
Mounting the RMZ780 ModuIe Connector
snap
snap
nsert mod:le vertically along
the g:ide rails :ntil it snaps
a:dibly on the DN rail
Extension mod:les (with
4-core cable) can be fitted
in a distance of :p to 10
meters
:ilding Technologies / HVP SYS SYN Ren Kmpfer
Siemens Switzerland Ltd 2007
Page 6 August 02
Mounting the RMZ791 Operator Unit
S:rface mo:nting
- Control panel
- Wall
Fl:sh panel mo:nting
- Panel c:to:t 138 x 92 mm
:ilding Technologies / HVP SYS SYN Ren Kmpfer
Siemens Switzerland Ltd 2007
Page 7 August 02
TerminaI Connection Concept
CE-
Y13
X8 X7
G0
Y24
Y23
G0 M M
Y1 G1 G G1 X6
M
G1 X5
M G1 Y2 Y4
Y3 G0
M G1 M
X3 G1 X2
M
X4
M
Q33
Q34
Q43
Q44
Q53
Q54
Q63
Q64 Y14
CE+
G0
G0 X1 G1
Q74
Q73
Konnex TP1
Act:ator DC 0.10 V
Power s:pply AC 24 V
G, G0
Low-voltage side
Mains voltage side
Loops
Power s:pply
A:xiliary terminals
in the control panel
N
3-pos. act:ator
N PE
P:mp
Active
sensor
Passive
sensor
:ilding Technologies / HVP SYS SYN Ren Kmpfer
Siemens Switzerland Ltd 2007
Page 8 August 02
Connecting the Spring Cage TerminaIs
1. Strip 7 mm
2. Place wire
1. P:sh with screwdriver
and insert wire
:ilding Technologies / HVP SYS SYN Ren Kmpfer
Siemens Switzerland Ltd 2007
Page 9 August 02
SuitabIe Conductors
Solid wires
A 2.5 mm
M:lticore stranded wires
A 2.5 mm
Ferr:les
A 1.5 mm
Tinned stranded wires
A 2.5 mm
Stranded wires
A 2.5 mm
:ilding Technologies / HVP SYS SYN Ren Kmpfer
Siemens Switzerland Ltd 2007
Page 10 August 02
RepIacement of ControIIer Insert in Case of Service
1. &se a screwdriver to :nlock
the controller insert on both
sides.
1. Prior to removal, disconnect the system from power s:pply !
1. Remove controller insert caref:lly.