You are on page 1of 28

Eaton 93E 60-500kVA UPS

Operation Training

© 2014 Eaton Corporation. All rights reserved


93E Product Snapshot

Power Rating: 80, 100, 120, 160, 200kVA


300kVA, 400kVA
Topology: Double-Conversion,
Transformer-Free with
High Efficiency Mode
Input/Output Voltage: 230/400 4
Wire
Frequency: 50/60 Hz
Features:
Hot Sync®
ABM®
High Efficiency Mode
Easy Capacity Test

© 2014 Eaton Corporation. All rights reserved 2


Summary of Major Features & Customer
Benefits
• High density: Small Footprint reduces space required for UPS
• Hot Sync paralleling: No common control system means
increased reliability
• Advanced Battery Management: Enhances battery life, safety and
makes batteries more predictable
• IP30 cabinet with washable dust filter: Increases system reliability in
harsh environments
• Front Service Access: Reduced service time and costs, less space
required
• Optional Internal Switchgear: Flexibility, reduced need
for external switchgear
• Optional internal Back-feed Contactor: Enhanced safety and
reliability
• Easy Capacity Test: No need for load banks, reduces total cost of
ownership over UPS life
© 2014 Eaton Corporation. All rights reserved 3
93E Compact Footprint

200kVA Configuration Vs global competitors

Dimensions Footprint
Product (cm, W x D x H) (m3)
93E 60 80 188 0.48
Competitor A 141 85 190 1.20
Competitor B 97.5 85.8 190 0.84 1876

Competitor C 60 84.3 160 0.51


Competitor D 70 80 193 0.56

Up to a 60% smaller footprint! 800

600

All 80-200kVA models


feature same dimensions

© 2014 Eaton Corporation. All rights reserved 4


93E Compact Footprint

400kVA Configuration Vs global competitors

Dimensions Footprint
Product (cm, W x D x H) (m3)
93E 160 82 188 1.31
Competitor A 165 85 190 1.40
Competitor B 167.5 88 190 1.44 1880

Competitor C 150 100 160 1.50


Competitor D 160 99.5 193 1.59

820
1600
Up to a 18% smaller footprint, including
top and bottom cable entry capability!
(Competitors require additional footprint)

© 2014 Eaton Corporation. All rights reserved 5


Display – Graphical LCD
Status Bar
LEDs:
On Mains
Navigation
On Battery buttons
On Bypass
Fault

Status Bar: Meters Events History Controls Setup Event History: 512 Events
• Automatically scrolls between model number, User Controls:
date/time, active alarms, UPS status, load % and • Bypass Command
battery runtime • Battery Test
Meters: • Display Test
• Input: V Ph-N, V Ph-Ph, I/Ph, Hz, kW, kVA, pf Setup:
• Output: V Ph-N, V Ph-Ph, I/Ph, Hz, kW, kVA, pf • Clock, Language, Lamp
• Bypass: V Ph-N, V Ph-Ph, I/Ph, Hz, kW, kVA, pf Test etc
• Battery: V, I, Time remaining bargraph

© 2014 Eaton Corporation. All rights reserved 6


93E Serviceability

The 93E was designed to reduce


mean-time-to-repair to less than 30
minutes!
• Front Service Access Washable
Dust Filters
• Slide Out Modules/Trays
• Modules weigh less than 25kg
• Optional Integral Maintenance switch
for 80-120kVA
• IP30 cabinet with washable Dust Filters

© 2014 Eaton Corporation. All rights reserved 7


Communications Panel
Communication
cable entry points

Mini Slot 1 Building Alarms (3)

REPO (NO & NC)

Pull Chain

Mini Slot 2
Parallel CAN Input (RJ45)
Parallel CAN Output (RJ45)

RS232 & USB Ports (for service access only) are


located on front door control PCB

© 2014 Eaton Corporation. All rights reserved 8


Standard UPS Configurations: 80-120kVA

1 Standard Configuration
2 Optional Maintenance Bypass
3 Optional Maintenance Bypass with
Backfeed Contactor

2 3

Single source bridging links are supplied with the UPS


© 2014 Eaton Corporation. All rights reserved 9
80-120kVA Internal Maintenance Bypass

• Electro-mechanically interlocked bypass

Metal interlock prevents


Metal interlock slides to the right to neutral switch from being
force UPS to static bypass and opened (must always be
enable bypass switch to be closed closed except when
and inverter output switch to be service personnel
opened maintaining UPS are

© 2014 Eaton Corporation. All rights reserved 10


Standard UPS Configurations: 160-500kVA
160-400kVA Dual Input with no switches

1 Standard Configuration
2 Optional Input Switch
3 Optional Input Switch and Backfeed
Contactor
1

160-400kVA Dual Input, optional 3 pole input switch 160-400kVA Dual Input, Input switch & backfeed contactor

2 3

Single source bridging links are supplied with 160-200kVA UPS


© 2014 Eaton Corporation. All rights reserved 11
Battery Configuration

• Default setting = 40 Blocks


Blocks Shut down
• Configurable: 36 or 38 Blocks voltage
36 x 12V 1.80V/cell

• Charging current: 38 x 12V 1.73V/cell

• 80-120kVA: Maximum 40A 40 x 12V 1.67V/cell

• 160-200kVA: Maximum 80A


• 300-400kVA: Maximum 160A
• External Battery CB:
• Standard MCCB, no Shunt Trip or
Under Voltage Release required
• Two Wire connection (+ & -)

© 2014 Eaton Corporation. All rights reserved 12


93E Software and Connectivity

Easy manageability and monitoring….


2 MiniSlots available for additional connectivity
hardware
• WEB/SNMP, Relay/RS232 Card, Modbus card & Industrial
Relay card options

3 Building Alarm Inputs and dedicated EPO


• Building alarms can be programmed to display the alarm
functional name
• Emergency Power Off port accommodates Normally Closed and
Normally Open inputs
RS232 & USB ports
• RS232 & USB ports for service interface
Software Capability
• Eaton Intelligent Power® Manager

© 2014 Eaton Corporation. All rights reserved 13


HMI Panel

The control panel consists of:


• A liquid crystal display (LCD) (1)
• Menu navigation pushbutton switches (2)
• A vertical column of status indicators (3).

© 2014 Eaton Corporation. All rights reserved 14


HMI Panel

© 2014 Eaton Corporation. All rights reserved 15


HMI Panel

© 2014 Eaton Corporation. All rights reserved 16


HMI Panel – Control Screen

© 2014 Eaton Corporation. All rights reserved 17


Start Up in Normal Mode
Start Up in Static Bypass Mode
Transf Normal Mode to Bypass Mode
Transf Bypass Mode to Normal Mode
Transf Normal Mode to Maintenance Bypass
Transf Maintenance Bypass to Normal Mode
UPS Maintenance
DAILY Maintenance
• Check the area surrounding the UPS system. Ensure the area is not cluttered, allowing free access to the unit.
• Ensure the air intakes (vents on the front door of the UPS cabinet and the exhaust openings (on the rear
of the UPS cabinet) are not blocked.
• Ensure the operating environment is within the parameters
• Ensure the UPS is in Normal mode (Normal status indicator is illuminated). If an alarm lamp is
illuminated

MONTHLY / QUATERLY Maintenance


• Monitor system parameters using the Control Panel
• Check the UPS air filters (located behind the front door) and cleaning as necessary
• Unfasten the front door by lifting the latch from the bottom and turning to the right
(counterclockwise) and swing the door open. Clean the filter using vacuum cleaner if
necessary.
• Close the front door and secure the latch.
• Record maintenance results and any corrective actions in a suitable log.

© 2014 Eaton Corporation. All rights reserved 24


Battery Maintenance
Shunt Trip Wiring
Alarm & Troubleshooting

Continued on Service Manual


© 2014 Eaton Corporation. All rights reserved 19