DESIGN

VENTILASI
INDUSTRI
ASBESTOS
Ir. MUH. ARIF LATAR, MSc

6/2/12

1.1 DATA AWAL

I.

2.

Idustriasbestos,denganjenisbahanseratcrysotile
UnitproduksipadaunitCrusing,dengandatasebagaiberikut:
q
Tipehoodenclosure
q
Generatianrate
-------------------------------200fiber/cc/60
menit
q
TLV-TVWA(asbestos ----------------------2fiber/cc
q
FaktorK ---------------------------------------2
q
Volumeruang(8x7x3=168m3)-------.........5.880ft3
q
Airflowslotsvelocity
-------------------400fpm
q
Ductvelocity ------------------------------3.500.fpm

3.

Elbow
q
q

4.

-------------------------0,24

Entry
q
q

6/2/12

R/D=2
losscoefisient:

Entrysudut=300
Entrylosscoefisien

---------------0,28


1.2. BENTUK DAN LAY PROSES OPERASI RUANG
KERJA
Pertimbangan desain sangat tergantung bentuk dan lay
out peores operasi, ruang kerja dan bentuk kontruksi
bangunan

Gambar -1 : BENTUK KONTRUKSI BANGUNAN

6/2/12

6/2/12

Gambar 2 : SKEMA SISTEM SALURAN


PIPA

Gambar- 3 : UKURAN LAY PROSES OPERASI

6/2/12

Gambar 4 : BENTUK DESAIN VENTILASI

6/2/12

2.2..

PENENTUAN DEMENSI

Dari data awal yang diketahui dan bentuk dan ukuran kontruksi bangunan pada
gambar 1 s/d gambar 4, maka ditetapkann sebagai berikut, pada table- 1.1.
Tabel- 1.1. Ukuran nomor detail, flow rate, diameter dan panjang pipa , elbow
dan enteries

6/2/12

II. PENENTUAN UKURAN UKURAN


UTAMA
2.1.

PENENTUAN FLOW RATE SUPLAY (Q)

Untukmenghitung flow rate di gunakan


rumus :

Q
= volume ruang x generation rate x
K
TLV

Q = (5.880 x200)/60 x 2
2
Q = 19.600 cfm
Dimana :

Volume ruang
= 5.880 ft3
TLV
= 2 fiber/cc
Generatian rate = 200 fiber/cc/60 menit
Faktor K
= 2

6/2/12

3.2.

PEMELIHAN ALTERNATIF BRANCH ENTRY

Pemilihan alternative bentuk brach entry tergantung pada bentuk kontruksi, saluran
pipa yang dinginkan , pada desain ini diambil bentuk prefereddengan sudut
maximal = 300 , gambar 5.28 indutrial ventilation ACGIH edition 20. Ukuran
data yang diambil seprti digambarkan pada Gambar 6,

6/2/12

III.

6/2/12

DESAIN PROSEDUR
3.1. DESAIN DUCT

6/2/12

3.3..DESAIN DETAIL HOOD


- SLOT

6/2/12

IV. PERHITUNGAN

Metode perhitungan yang digunakan dalam desain ini adalah


menggunakan metode desain Perhitungan Kecepatan Tekanan
atau Velocity Pressure Method Calculation Sheet

4.1. METODE KECEPATAN TEKANAN

Dari hasil perhitungan yaitu untuk mengetahui distribusi


volume flow rate, duct velocity, slot velocity, slot static
pressure, hood static pressure, duct SP loss, dan qumulatif
static pressure, Fan SP dan Fan TP.
Denagan data hasil perhitungan besar daya , dan putaran
Fan yang akan digunakan.

6/2/12

6/2/12

4.1.1. Hasil
Perhitungan
Velocity Pressure Method Calculation Sheet
PlantName:____________________________
CONTOH TUGAS
Location:_______________________________
Department:____________________________+

Elevation:_________ Date:__15januari2011______________
Temp:____________ Drawing#.:___________
Factor:___________ Designer:_____________

1
2
3

DuctSegmentIdentification
TargetVolumeFlowrate, Q=V*A-Chap10
Min.TransportVelocity,V Chap10

cfm
fpm

A1-B
4500.0
3500

A-B
3600.0
3500

B-C
19600.0

C
19600.0

C-D
19600.0

D
19600.0

D-E
19600.0

4
5

MaximumDuctDiameter (D=((4*144*Q)/(pi*V)) inches


)
SelectedDuctDiameter
inches

19.00
19.00

13.00
9.00

29.00
29.00

A
I

29.00
29.00

33.00

30.00
30.00

6
7

DuctArea (pi*(D/12) /4)


ActualDuctVelocity

sq.ft
fpm

1.9689
2285.5

0.9218
3905.6

4.5869
4273.0

4.5869
4273.0

5.9396
3299.9

4.9087
3992.9

"wg
sqft
sqft
fpm

0.3256

0.9510

1.1383

1.1383

0.6789

0.9940

400.00

400.00

C
L
E
A

0.5

8 DuctVelocityPres, VP=(V/4005)
9
H
MaximumSlotArea= (2/11)
10 O
Slotareaselected
11 O S SlotVelocity,Vs Chap10

6/2/12

12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42

L
O
T
S

SlotVelocityPres, VPs=(Vs/4005)
"wg 0.0100
SlotLossCoefficient, Chap10,Chap3
1.78
AccelerationFactor
0or1
0
S
SlotLossperVP (13+14)
1.78
U
SlotStaticPressure (12*15)
"wg 0.0178
C DuctEntryLossFactor F5-12,Chap10
0.250
T AccelerationFactor (1athoods)
1or0
1
I DuctEntryLossperVP (17+18)
1.25
O DuctEntryLoss (8*19)
"wg
0.407
N OtherLosses
"wg
HoodStaticPressureSPh (16+20+21)
"wg
0.425
StraightDuctLength
ft
35.0
FrictionFactor (Hf)
0.0110
FrictionLossperVP (23*24)
0.3853
No.of90degreeElbows
1.00
ElbowLossCoefficient (BottomofPage)
0.24
ElbowLossperVP (26*LossFactor) (bottomofpage )
0.2400
No.ofBranchEntries
(1or0)
1.00
EntryLossCoefficient
0.28
EntryLossperVP (29*LossFactor) (Branch)
0.28
SpecialFittingsLossFactors
DuctLossperVP (25+28+31+32)
0.9053
DuctLoss (8*33)
0.2948
DuctSPLoss (22+34)
0.720
OtherLosses
CumulativeStaticPressure
"wg -0.720
GoverningStaticPressure (atTOlocation)
"wg -1674.000
CorrectedVolumetricFlowrate
cfm
CorrectedVelocity
fpm
CorrectedVelocityPressure
"wg
ResultantVelocityPressure
"wg

0.0100
1.78
0
1.78
0.0178
0.250
1
1.25
1.189

F
A

N
E
R

0.250
1
1.25
1.423
0.400
0.400

0.250
1
1.25
1.423

0.250
1
1.25
1.242
1.242
10.0
0.0060
0.0602

1.206
10.0
0.0168
0.1679
0.18
0.24
0.0432
1.00
0.28
0.28

1.423
15.0
0.0062
0.0937

1.00
0.28
0.28

1.423
15.0
0.0062
0.0937
0.44
0.24
0.1056
1.00
0.28
0.28

0.4911
0.4670
1.674

0.3737
0.4253
1.848

0.400

0.4793
0.5455
1.968

0.3402
0.3382
1.581

-1.674
-1.848

-1.848

-2.248

-4.216

5.797

1.00
0.28
0.28

4.1.2. Hasil Perhitungan


Brach Entry

6/2/12

V. PERHITUNGAN DAYA
FAN
Data yang diperlukan untukmenentukan besarnya daya HP=
House Power dan Putaran (rpm), Fan yang digunakan dalam
desain ini adalah :

N = jumlah blades,

Q=volumemetric flow rate,

FSP = Fan Static Pressure,

FTP = Fan Total Pressure

Rumus yang digunakan sebagai berikut :

FSP = SPout let - SPin let - VPinlet

FTP = FSP + VPout let

BHP = (FTP * Q)/(6356*n)


6/2/12

Dari hasil perhitungan pada hasil perhitungan dengan


data sbb :

SPout let = 5, 797 wg

SPin let
= - 4,216 wg

VPin let
= 1,1383 wg

VPout let = 0,9940 wg

Q
=19.600 cfm

N
=3

FSP = 5,797 (-4,216) 1,1383


FSP = 8,8747 wg

FTP = 8,8747 + 0,9940


FTP = 9,8687 wg

BHP = (9,8687x 19.600)


(6356 x 3)
BHP = 10,14 HP
RPM = 1894
6/2/12

Untuk BHP = 10,14 HP nilai RPM diambil pada (table 6.1. Example of multi
rating table, Buku Industrial Ventilatin ACGIH 20 th ediion 1988)

6/2/12