PROTECTION RELAYS

Over Current Relays


Types - MC31A, MC61A, MC61C Technical Data

Page

Current Sensing Relays


Types - MC11A, ME11, SCKIS

Page

5/2 5/3 5/4

Technical Data Wiring Diagram Ordering Information

5/5 5/6 5/7

Wiring Diagram Ordering Information

Neutral Displacement, Generator Load Sharing, U/V or Over Voltage


Types - MND11, RRS, MV11 Technical Data Wiring Diagram Ordering Information

Page

Secondary Relays
Types - TCS01, MTM01, PT.03

Page

5/8 5/9 5/10

Technical Data Wiring Diagram Ordering Information

5/11 5/12 5/13

Power .actor Control or Monitoring Relays


Types - P.C8, P.C14, MVP01 Technical Data Wiring Diagram Ordering Information

Page

Motor Protection Relay


Type MM30

Page

5/14 5/15 5/16

Technical Data Wiring Diagram Ordering Information

5/17 5/18 5/19

PROTECTION RELAYS

Generator Protection Relays


Types - IM3GV, IM30G, MD32G Technical Data Wiring Diagram Ordering Information

Page

Synchronising Relay
Types - SPM21, SCM21

Page

5/20 5/21 5/22

Technical Data Wiring Diagram Ordering Information

5/23 5/24 5/25

Voltage / .requency Relay, Direction O/C, E/. Relay


Types - U.D34, UM30A, DM30 Technical Data Wiring Diagram Ordering Information

Page

Transformer Protection Relay Capacitor Bank Protection Relay


Types - MD32T, IM30T, DIN30C

Page

5/26 5/27 5/28

Technical Data Wiring Diagram Ordering Information

5/29 5/30 5/31

Control and Supervision Relays


Types - MW33, MU30 Technical Data Wiring Diagram Ordering Information

Page

Reverse Power Relay


Type MRP11

Page

5/32 5/33 5/34

Technical Data Wiring Diagram Ordering Information

5/35 5/36 5/36

PROTECTION RELAYS

Other Relays
Types - MX7/5, MC-R, REX, CPSC, MSCOM Ordering Information

Page

5/37

PRODUCT DESIGN STANDARDS

Reference standards Dielectric test Impulse test H. disturbance test Electrostatic discharge test Electrical fast transient Radiated electro magnetic field test Surge immunity Ring wave test Voltage dips & interruption test Power frequency magnetic test

: : : : : : : : : : :

IEC 60255, IEC 61000 IS3231, IS8686 IS 3231 / IEC 60255-5 IS 8686 / IEC 60255-5 IS 8686 / IEC 60255-22-1 IEC 61000-4-2 IEC 61000-4-4 IEC 61000-4-3 IEC 61000-4-5 IEC 61000-4-12 IEC 61000-4-11 IEC 61000-4-8

TIME - CURRENT CHARACTERISTICS (AT TMS=1)

.or Trip time at TMS other than 1 Trip time = (Trip time at TMS=1) x TMS OR 50msec whichever is more

A : Normal Inverse 3.0 Sec. B : Normal Inverse 1.3 Sec. C : Very Inverse D : Extreme Inverse

5/1

TECHNICAL DATA
THREE PHASE OVER CURRENT AND EARTH .AULT RELAYS
Display of Currents, settings, Trip data & Trip history for analysis & trouble shooting. Built in Self Supervision & Self testing feature to ensure continuous reliability. Separate Indication for power ON & Programming mode or relay fault. Separate fault indication. In MC61C - Communication with Computer & breaker control through RS 485 Port. .our User Programmable Output relays. MC31A MC61A MC61C

Model

5
Description 3 Phase O/C + E/. 3 Phase O/C + E/. + Highset 3 Phase O/C + E/. + Highset Communication and breaker control Device Code Design .unctions Available 51 RYBN Numerical Relay Lowset O/C Lowset E/. -ls -Os 50/51 RYBN Numerical Relay Lowset O/C Highset O/C Lowset E/. Highset E/. Settings O/C ls = 20-200% Step 5% E/. Os = 5-80% Step 5% HS O/C = (0.2 to 40) x In step of 0.2 In or disable HS E/. = (0.1 to 20) x On step of 0.1 On or disable Time Characteristics available NI, VI, EI, or Definite Time TMS 0.1 - 1.6 Step 0.05 Other .eatures Site selectable Trip time Char. Display of Currents, Trip count Self supervision feature Burden on CT Burden on PT Operating temp Weight Burden on Auxiliary supply Output Contact Construction Dim W x H x D in mm Panel Cutout
5/2

50/51 RYBN Numerical Relay Lowset O/C Highset O/C Lowset E/. Highset E/. -ls -lhs -Os -Ohs

-ls -lhs -Os -Ohs

O/C ls = 20-200% Step 5% E/. Os = 5-80% Step 5% HS O/C = (0.2 to 40) x In step of 0.2 In or disable HS E/. = (0.1 to 20) x On step of 0.1 On or disable Time Characteristics available NI, VI, EI, or Definite Time TMS 0.1 - 1.6 Step 0.05 Site selectable Trip time Char. Highset can be disabled Display of Currents, Trip count Self supervision feature 0.25 VA on CT/Phase Not applicable 0 to 60 C < 2kg 10 VA 1 N/O contact for self suprvn Drawout 121 x 158 x 224 113 x 142

O/C ls = 20-200% Step 5% E/. Os = 5-80% Step 5% HS O/C = (0.2 to 40) x In step of 0.2 In or disable HS E/. = (0.1 to 20) x On step of 0.1 On or disable Time Characteristics available NI, VI, EI, or Definite Time TMS 0.1 - 1.6 Step 0.05 HS delay:0.1-2 Sec step 0.01 Sec. or Inst. RS 485 Communication Breaker control Auto doubling of highset, Relay co-ordination 0.25 VA on CT/Phase Not applicable 0 to 60 C < 2kg 10 VA 1 N/O contact for self suprvn Drawout 121 x 158 x 224 113 x 142

0.25 VA on CT/Phase Not applicable 0 to 60 C < 2kg 10 VA 1 N/O contact for self suprvn Drawout 121 x 158 x 224 113 x 142

WIRING DIAGRAM
THREE PHASE OVER CURRENT AND EARTH .AULT RELAYS

5
MC31A

MC61A

MC61C
5/3

ORDERING IN.ORMATION
THREE PHASE OVER CURRENT AND EARTH .AULT RELAYS
Model MC31A Description 3 Phase Over current and Earth .ault Relay Catalogue No. MC31A 00

Catalogue No. Selection Guide for MC31A

Model MC61A

Description 3 Phase Over current and Earth .ault Relay

Catalogue No. MC61A 00

Catalogue No. Selection Guide for MC61A

Model MC61C

Description 3 Phase Over current and Earth .ault Relay

Catalogue No. MC61C 00

Catalogue No. Selection Guide for MC61C

5/4

TECHNICAL DATA
CURRENT SENSING RELAYS Single Phase Over current / Earth fault Relay Sensitive E/. Relay and Instantaneous Current Relay
Easy Setting through front panel DIP Switches. Indication for Power ON and trip status. Test feature - helps maintenance. Compact, Light weight helps in reducing panel size & thickness. MC11A ME11A SC14S

Model

5
Description Device Code Design .unctions Available 1 Ph O/C or E/. 50/51 or 50N/51N Microcontroller Based Lowset O/C Highset O/C Lowset E/. Highset E/. Settings -ls -lhs -Os -ls S E/. = 1-16% step 1% HS S E/. = (2-16) xls in steps of 2 ls ls = 10-40% step 5% OR 20-80% step 10% 1 Ph Sensitive E/. 50N/51N Microcontroller Based Lowset S E/. Highset S E/. -ls -lhs Instantaneous current relay 87 N / 64 R Static

O/C ls = 50-200% Step 10% OR E/. ls = 10-40% Step 2% OR E/. ls = 20-80% Step 4% HS O/C = (2-16) xls step 2 ls HS E/. = (2-16) xls step 2 ls Time Characteristics availableNI, VI, EI, or Definite Time 3 ranges of def Time (1, 10, 100) TMS : 0.1 - 1.6 Step 0.1

Time Characteristics availableNI, VI, EI, or Definite Time 3 ranges of def Time (1, 10, 100) TMS : 0.1 - 1.6 Step 0.1 Site selectable Trip time Char. Highset can be disabled Harmonic rejection

Time Characteristics availableInstantaneous (25ms) OR time delayed 100ms / 200 ms Self Powered Relay testing Possible by ext.24V Supply .lag indication / LED indication

Other .eatures

Site selectable Trip time Char. Highset can be disabled

Burden on CT Burden on PT Operating temp Weight Burden on Auxiliary supply Output Contact Construction Dim W x H x D in mm Panel Cutout

0.25 VA on CT Not applicable 0 to 55 C < 1.5kg 5.5 VA 2 C/O Contacts (S/R) Drawout 71 x 158 x 224 62 x 142

0.25 VA on CT Not applicable 0 to 55 C < 1.5kg 5.5 VA 2 C/O Contacts (S/R) Drawout 71 x 158 x 224 62 x 142

6 VA Not applicable 0 to 55 C < 1.5kg Not applicable 2 C/O Contacts (S/R) Drawout 71 x 158 x 224 62 x 142

5/5

WIRING DIAGRAM
CURRENT SENSING RELAYS

5
MC11A

ME11A

SC14S
5/6

ORDERING IN.ORMATION
CURRENT SENSING RELAYS
Model MC11A Description Single Pole Over current or Earth .ault Relay Catalogue No. MC11A 00

Catalogue No. Selection Guide for MC11A

Model ME11A

Description Single Pole Sensitive Earth .ault Relay

Catalogue No. ME11A 00

Catalogue No. Selection Guide for ME11A

Model SC14S Instantaneous Earth .ault Relay

Description

Catalogue No. SC14S 00

Catalogue No. Selection Guide for SC14S

5/7

TECHNICAL DATA
NEUTRAL DISPLACEMENT RELAY, GENERATOR LOAD SHARING RELAY, UNDER VOLTAGE OR OVER VOLTAGE RELAY
Easy Setting through front panel DIP Switches. LED indication for Power ON and trip status. Test feature - helps maintenance. Compact, Light weight helps in reducing panel size & thickness. MND11 RRS MV11

Model

5
Description Device Code Design .unctions Available Neutral Displacement 59 Vo Microcontroller Based Voltage relay for E/. Protection of generator earthed thro neutral earthing transformer Generator Load Sharing 95 Static Active / Reactive power selection Over Power alarm Load Sharing .requency control Settings .ault voltage Vs2% - 32% of Vn step 2% Alarm voltage Vis2% - 32% of Vn step 2% Time Characteristics availableInverse time or Definite time TMS : 0.1 - 1.6 Step 0.1 Other .eatures LED indication for power ON time characteristics, trip Test feature Third harmonics rejection 26db Burden on PT Burden on CT Operating temp Weight Burden on Auxiliary supply Output Contact Construction Dim W x H x D in mm Panel Cutout
5/8

1 Ph U/V OR O/V 27 OR 59 Microcontroller Based Lowset U/V Highset U/V Lowset O/V Highset O/V -Vs -Vhs OR -Vs -Vhs

U/V Vs = 95-20% step 5% U/V Vhs = 90-20% step 10% O/V Vs = 105-180% step 5% O/V Vhs = 110-180% step 10% Time Characteristics availableInverse time or Definite time TMS : 0.1 - 1.6 Step 0.1 LED indication Site selectable U/V OR O/V Site selectable Trip time char. Highset can be disabled

0.25 VA Not applicable 0 to 55 C < 1.5kg 5.5 VA 1No+2 C/O Contacts (S/R) Drawout 71 x 158 x 224 62 x 142

5 VA 5 VA 0 to 55 C < 1.5kg 8.5 VA 3 N/O Drawout 71 x 158 x 224 62 x 142

0.075 VA on PT Not applicable 0 to 55 C < 1.5kg 5.5 VA 2 C/O Contacts (S/R) Drawout 71 x 158 x 224 62 x 142

WIRING DIAGRAM
NEUTRAL DISPLACEMENT RELAY, GENERATOR LOAD SHARING RELAY, UNDER VOLTAGE OR OVER VOLTAGE RELAY

5
MND11

RRS

MV11
5/9

ORDERING IN.ORMATION
NEUTRAL DISPLACEMENT RELAY, GENERATOR LOAD SHARING RELAY, UNDER VOLTAGE OR OVER VOLTAGE RELAY
Model MND11 MND11 RRS RRS MV11A Description Neutral Displacement Relay 20-110V Neutral Displacement Relay 88-264V Load Sharing Relay 20-110V Load Sharing Relay 88-264V Single Phase Under Voltage or Over Voltage Relay Catalogue No. MND11A00000 MND11B00000 ESRRSAXX000 ESRRSBXX000 MV11A 00 00

Catalogue No. Selection Guide for MV11A

5/10

TECHNICAL DATA
SECONDARY RELAYS Trip Circuit Supervision Relay Timer Relay and PT .use .ailure Relay
Easy Setting through front panel DIP Switches. Indication for Power ON and trip status. Test feature - helps maintenance. Compact, Light weight helps in reducing panel size & thickness. Low Power Burden TCS01 MTM01 PT.03

Model

5
Description Device Code Design .unctions Available Trip Circuit supervision 95 ABC Static Post Close Supervision Pre Close Supervision Rating Settings Not applicable Trip coil supply 110 - 220V AC OR 24 - 48 - 110 - 220V DC Operation time 500+/-100mS Reset time < 150 mS Other .eatures Same Relay for all Rating Trip supply U/V indication CB ON/O.. status indication Timer Relay 2T Microcontroller Based Programmable as Delay on Pick up or Drop off Not applicable 15 - 999 mS step 1 mS 1 - 9.99 S step 10mS 10 - 99.9 S step 100mS 100 - 999 S step 1S Password protection available Contacts programmable as S/R or H/R LED Indication for each phase Relay trip status Self powered High speed operation Burden on CT Burden on PT Operating temp Weight Burden on Auxiliary supply Output Contacts Construction Dim W x H x D in mm Panel Cutout Not applicable Not applicable 0 to 55 C < 1.5kg 10 VA 2 C/O Contacts (S/R) Drawout 71 x 158 x 224 62 x 142 Not applicable Not applicable 0 to 55 C < 1.5kg 6 VA 2 N/O + 2 N/C Per timer Drawout 71 x 158 x 224 62 x 142 Not applicable <0.5 VA per phase on PT 0 to 55 C < 1.5kg Not applicable 2 C/O Contacts (S/R) Drawout 71 x 158 x 224 62 x 142 Operation time 7mS 110V AC PT Not applicable PT .use .ailure Relay 60 Static 3 Phase PT fuse failure

5/11

WIRING DIAGRAM
SECONDARY RELAYS

5
TCS01

MTMO1

PT.O3
5/12

ORDERING IN.ORMATION
SECONDARY RELAYS
Model TCS01 TCS01 MTM01A MTM01B PT.03 Description Trip Circuit Supervision Relay 20-110V AC/DC Trip Circuit Supervision Relay 80-264V AC/DC Timer Relay 20-110V AC/DC Timer Relay 80-264V AC/DC PT .use .ailure Relay Catalogue No. MCS01A00000 MCS01B00000 MTM01A00000 MTM01B00000 MT.03X00000

5/13

TECHNICAL DATA
POWER .ACTOR CONTROL AND MONITORING RELAYS Power .actor Controller Relay and Voltage & Power .actor Monitoring Relay
On line display of system P.. Easy setting of power factor and C/K ratio from front panel. LED indication for Alarm code, No. of Banks selected, P. status-lead / lag / unity, Auto / Manual mode. DIP switches selection for No. of banks / time relay / bank ratios.

Model

P.C8

P.C14

MVP01

5
Description Device Code Design .unctions Available Microcontroller Based Automatic P. controller Can control upto8 Capacitor Banks Settings P. : 0.8 Lag - 0.95 Lead Switching time 10-20-40-60 S Threshold reactive current setting 0.5 - 1A reactive Capacitor Bank Selection4-5-6-7-8 Banks Other .eatures Display of P. Measurement Auto / Manual Selection Disconnection of Capacitors during over voltage & Power failure Alarm contact for under/over compensation, over voltage, under load Burden on CT Burden on PT Operating temp Weight Output Contacts 0.3 VA 10 VA 0 to 55 C < 2kg 8 NO Microcontroller Based Automatic P. controller Can control upto14 Capacitor Banks P. : 0.8 Lag - 0.95 Lead Switching time 10-20-40-60 S Threshold reactive current setting 0.5 - 1A reactive Capacitor Bank Selection4-5-6-7-8-10-12-14 Banks Display of P. Measurement Auto / Manual Selection Disconnection of Capacitors during over voltage & Power failure Alarm contact for under/over compensation, over voltage, under load 0.3 VA 10 VA 0 to 55 C < 2kg 14 NO 15 VA 0 to 55 C < 2kg 2 N/O for lead P. (self reset) 2 N/O for O/V (1 self/1 manual) 2 C/O for U/V (manual reset) Dim W x H x D in mm Panel Cutout Auxiliary supply
5/14

Power .actor Controller

Power .actor Controller

Voltage / Power .actor monitor

Microcontroller Based U/V, O/V trip and leading P. alarm

U/V 75% to 90% step 1% OV 105% to 120% step 1% leading P. alarm time 20 Sec. U/V - O/V trip time 10 Sec.

Display of Power .actor LED indication for O/V trip, U/V trip, P. status- lead / lag, lead P. alarm 1A / 5A field selectable

144 x 144 x 110 138 x 138 415V AC

144 x 144 x 110 138 x 138 415V AC

144 x 144 x 110 138 x 138 110V AC

WIRING DIAGRAM
POWER .ACTOR CONTROL & MONITORING RELAYS

5
P.C14

P.C8

MVP01
5/15

ORDERING IN.ORMATION
POWER .ACTOR CONTROL & MONITORING RELAYS
Model P.C8 P.C14 MPV01 Eight Stage AP.C Relay .ourteen Stage AP.C Relay Voltage & P. Monitoring Relay Description Catalogue No. MP.08XOOOOO MP.14XOOOOO MVP01X00000

5/16

TECHNICAL DATA
MOTOR PROTECTION RELAY
Display of various parameters, trip count and trip data on 8 digit alphanumeric display. Separate LEDs for various fault indication. .our user programmable output relays. Built in self supervision & self testing feature helps maintenance. Easy operation by 5 push buttons. RS 485 port for serial communication with MSCON user friendly software. MM30

Model

5
Description Device Code Design .unctions Available Motor Protection 49, 51lr, 46, 37, 50/51, 64, sTnO, LTR Numeric Thermail O/L and Pre-alarm Locked Rotor Current unbalance, phase reversal, phase loss Over Current Earth .ault Repeat and prolonged starts Restart Inhibition No load running Blocking .unction Other .eatures Auto setting 1 A or 5 A site selectable (Default 5 Amp) Selectable motor time constant (1 - 60 min) Display of parameters Built in self supervision RS485 PORT Burden on CT Burden on PT Operating temp Weight Burden on Auxiliary supply Output Contacts Construction Dim W x H x D in mm Panel Cutout 0.2 VA for 5A, 0.01 VA for 1A Not applicable 10 to 60 C < 2kg 8.5 VA 4 C/O + 1 C/O for self supervision Drawout 121 x 158 x 224 113 x 142
5/17

WIRING DIAGRAM
MOTOR PROTECTION RELAY

MM30

5/18

ORDERING IN.ORMATION
MOTOR PROTECTION RELAY
Model MM30 MM30 Motor Protection Relay 20-110V Motor Protection Relay 88-264V Description Catalogue No. EMM30AXX000 EMM30BXX000

5/19

TECHNICAL DATA
GENERATOR PROTECTION RELAYS Multifunction Generator Protection Relays and Percentage Biased Generator Differential Relay
Display of various parameters, trip count & trip data on 8 digit alphanumeric display. Separate LEDs for various fault indication. .our user programmable output relays. Built in self supervision & self testing feature help maintenance Easy operation by 5 push buttons. RS 485 port for serial communication with MSCOM User friendly software. IM3GV IM30G MD32G

Model

5
Description Device Code Design .unctions Available Generator Protection 50/51V, 49,46,27,59,81,40,32,37 Numeric Voltage rest. O/C Highset Trip time char. NI, Def time Thermal Image Lowset Negative sequence Highset Negative sequence Under voltage, Over frequency Loss of field, Reverse Power Low forward power, CB .ailure protection Other .eatures 1 A or 5 A site selectable Display of Parameters Built in Self supervision RS485 Port, Blocking .unction Burden on CT Burden on PT Burden on Auxiliary supply Operating temp Weight Output Contacts 0.2 VA for 5A, 0.01 VA for 1A 0.04 VA 8.5 VA 10 to 60 C < 2kg 4 C/O, S/R or H/R or Time del 1 C/O for self supervision Construction Dim W x H x D in mm Panel Cutout
5/20

Generator Protection 50/51, 46, 64S, 40, 32 Numeric Lowset O/C Highset O/C Stator E/. Negative Sequence Reverse Power

Generator Differential 87, 50/51, 50LBB, 64S / 87N Numeric Generator Differential Bias % with dual adjustable slope Over Current Stator E/. CB .ailure protection

1 A or 5 A site selectable Display of Parameters Built in Self supervision RS485 Port, Blocking .unction 0.2 VA for 5A, 0.01 VA for 1A 0.04 VA 8.5 VA 10 to 60 C < 2kg 4 C/O, S/R or H/R or Time del 1 C/O for self supervision Drawout 121 x 158 x 224 113 x 142

1 A or 5 A site selectable Display of Parameters Wave form capture feature Built in Self supervision, RS485 Port 0.2 VA for 5A, 0.01 VA for 1A Not applicable 8.5 VA 10 to 60 C < 2kg 4 C/O, S/R or H/R or Time del 1 C/O for self supervision Drawout 121 x 158 x 224 113 x 142

Drawout 121 x 158 x 224 113 x 142

WIRING DIAGRAM
GENERATOR PROTECTION RELAYS

5
IM3GV

IM30G

MD32G
5/21

ORDERING IN.ORMATION
GENERATOR PROTECTION RELAYS
Model IM3GV IM3GV IM30G IM30G MD32G Description Generator Protection Relay 20-110V Generator Protection Relay 88-264V Generator Protection Relay 20-110V Generator Protection Relay 88-264V Differential Relay for Generator 20-110V Differential Relay for Generator 88-264V Catalogue No. EI3GVAXX000 EI3GVBXX000 EI30GAXX000 EI30GBXX000 ED32GAXX000 ED32GBXX000

MD32G

5/22

TECHNICAL DATA
SYNCHRONISING RELAYS Generator Synchronising / Synchrocheck relays
Display of various parameters, event count & event data on 8 digit alphanumeric display. Separate LEDs for various fault indication. .our user programmable output relays. Built in self supervision & self testing feature help maintenance. Easy operation by 5 push buttons. RS 485 port for serial communication with MSCOM User friendly software. SPM21 SCM21

Model

5
Description Device Code Design .unctions Available Auto Synchronising Relay 25 Numeric Auto Synchronising with Adjustable voltage, Adjustable .requency, Adjustable Phase angle, Adjustable Reclose time, Bus Live / Dead operation Speed Regular Control, Voltage Regulator Control, Digital inputs to monitor CB position Rating Other .eatures 110V - 125 V PT input Display of Parameters, Built in self supervision, RS485 Port Burden on PT Operating temp Weight Burden on Auxiliary supply Output Contacts Construction Dim W x H x D in mm Panel Cutout 0.04 VA 10 to 60 C < 2kg 8.5 VA 5 C/O Drawout 121 x 158 x 224 113 x 142 Synchronising Check Relay 25 Numeric Synchro Check with Adjustable voltage Adjustable .requency Adjustable Phase angle Adjustable Reclose time, Check Synch / Dead line / Dead bus modes of operation, Over voltage protection, Under voltage protection, Over .requency Protection Under frequency protection, Digital inputs to monitor CB position 110V - 125 V PT input Display of Parameters, Built in self supervision, RS485 Port 0.04 VA 10 to 60 C < 2kg 8.5 VA 5 C/O Drawout 121 x 158 x 224 113 x 142
5/23

WIRING DIAGRAM
SYNCHRONISING RELAYS

5
SPM21
Connection diagram of 1 bus with 2 lines

Connection diagram of 1 bus with 1 line

SCM21
5/24

ORDERING IN.ORMATION
SYNCHRONISING RELAYS
Model SPM21 SPM21 SCM21 SCM21 Description Auto Synchronising Relay 20-110V Auto Synchronising Relay 88-264V Synchrocheck Relay 20-110V Synchrocheck Relay 88-264V Catalogue No. EPM21A00000 EPM21B00000 ESC21A00000 ESC21B00000

5/25

TECHNICAL DATA
VOLTAGE / .REQUENCY RELAYS, DIRECTIONAL O/C, E/. RELAY 3 Phase voltage / frequency and Load shedding Relay 3 Phase voltage / frequency and zero sequence voltage Relay
Display of various parameters, trip count & trip data on 8 digit alphanumeric display. Separate LEDs for various fault indication. .our user programmable output relays. Built in self supervision & self testing feature help maintenance. Easy operation by 5 push buttons. RS 485 port for serial communication with MSCOM User friendly software. U.D34 UM30A DM30

Model

5
Description Device Code Design .unctions Available 3 Ph Voltage & .req. Relay 81, 27, 59, df/dt, de/dt Numeric .requency-4 stages selectable as under or over or under/over Voltages - 2 stages selectable Rate of change of frequency protection df / dt - 2 Stages Blocking function 3 Ph Voltage & .req. Relay 81, 27, 59, V/Hz, 59d, 59s, 59Uo Numeric Over exitation-2 stages .requency-2 stages selectable as under or over or under/over Voltages - 2 stages selectable as under or over Zero Sequence - 2 Stages Blocking function Rating Other .eatures 100 - 125V PT input Display of Parameters Built in Self supervision RS485 Port communication Burden on CT Burden on PT Operating temp Weight Burden on Auxiliary supply Output Contacts Not applicable 0.04 VA 10 to 60 C < 2kg 8.5 VA 4 C/O, S/R or H/R or Time del 1 C/O for self supervision Construction Dim W x H x D in mm Panel Cutout
5/26

3 Ph Dir O/C & E/. + Highset 50/67 RYBN, 50 LBB Numeric Low Set Dir O/C Highset Dir O/C Low Set Dir E/. Trip time Char : NI, VI, EI, Def time CB .ailure .unction MTA Setting = 0-359 1A or 5A site selectable 100 - 125V PT input Display of Parameters Built in Self supervision RS485 Port communication 0.2 VA for 5A, 0.01 VA for 1A 8.5 VA 10 to 60 C < 2kg 0.04 VA 4 C/O, S/R or H/R or Time del 1 C/O for self supervision Drawout 121 x 158 x 224 113 x 142

100 - 125V PT input Display of Parameters Built in Self supervision RS485 Port communication Not applicable 0.04 VA 10 to 60 C < 2kg 8.5 VA 4 C/O, S/R or H/R or Time del 1 C/O for self supervision Drawout 121 x 158 x 224 113 x 142

Drawout 121 x 158 x 224 113 x 142

WIRING DIAGRAM
VOLTAGE / .REQUENCY RELAYS, DIRECTIONAL O/C, E/. RELAY

5
U.D34

UM30A

DM30
5/27

ORDERING IN.ORMATION
VOLTAGE / .REQUENCY RELAYS, DIRECTIONAL O/C, E/. RELAY
Model U.D34 U.D34 UM30 UM30 DM30 .requency Relay 20-110V .requency Relay 88-264V U/V Relay with Neutral Monitoring 20-110V U/V Relay with Neutral Monitoring 88-264V 3 Phase O/C and E/. Relay 20-110V (Directional) 3 Phase O/C and E/. Relay 88-264V (Directional) Description Catalogue No. E.D34A00000 E.D34B00000 EUM30A00000 EUM30B00000 EDM30AXX000 EDM30BXX000

DM30

5/28

TECHNICAL DATA
TRANS.ORMER PROTECTION RELAY, CAPACITOR BANK PROTECTION RELAY Percentage Biased Transformer Differential Relay 3 Phase Thermal + Over Current + Earth .ault Relay for transformer protection
Display of various parameters, trip count & trip data on 8 digit alphanumeric display. Separate LEDs for various fault indication. .our user programmable output relays. Built in self supervision & self testing feature help maintenance. Easy operation by 5 push buttons. RS 485 port for serial communication with MSCOM User friendly software. MD32T IM30T DIN30C

Model

5
Description Transformer Differential + Restricted E/. Device Code Design .unctions Available 87 RYB, 87N Numeric Lowset Differential Lowset Op time : <=30mS Highset Differential Highset Op time : 6-20mS Restricted Earth .ault Dual slope Bias 2nd harmonic restraint setting 5th harmonic restraint setting Auto correction of CT Ratio Zero sequence compensation Blocking function Other .eatures Display of Parameters Built in Self supervision RS485 PORT 1 A OR 5 A site selectable Waveform capture feature Burden on CT Operating temp Weight Burden on Auxiliary supply Output Contacts Construction Dim W x H x D in mm Panel Cutout 0.2 VA for 5A, 0.01 VA for 1A 10 to 60 C < 2kg 8.5 VA 5 C/O, S/R or H/R or Time del Drawout 121 x 158 x 224 113 x 142 0.2 VA for 5A, 0.01 VA for 1A 10 to 60 C < 2kg 8.5 VA 5 C/O, S/R or H/R or Time del Drawout 121 x 158 x 224 113 x 142 2 C/O contacts, S/R or H/R DIN rail mounting 105 x 85 x 70 Not applicable 10 to 60 C < 2kg Display of Parameters Built in Self supervision RS485 Port 1 A OR 5 A site selectable Display of Parameters RS 485 port LED indication for Trip / Power ON Test feature 50/51 RYBN, 49, 46, 12t Numeric Lowset O/C Highset O/C Lowset E/. Highset E/. Thermal Overload Lowset current unbalance with Highset current unbalance Inrush Energy protection CB .ailure function Blocking function 3 Ph O/C, E/. + Thermal 3 Ph O/C, E/. .or capacitor banks 51/51 RYBN, 46, 37 1o Numeric O/C - 0.1 - 10 ln E/. - 0.1 - 5 ln negative Seq - 10% - 75% ln undercurrent - 10% unbalance - 2% - 50%

5/29

WIRING DIAGRAM
TRANS.ORMER PROTECTION RELAYS, CAPACITOR BANK PROTECTION RELAY

5
MD32T

IM30T

DIN30C
5/30

ORDERING IN.ORMATION
TRANS.ORMER PROTECTION RELAYS, CAPACITOR BANK PROTECTION RELAY
Model MD32T MD32T IM30T IM30T DIN30C DIN30C Description Differential Relay for Transformer 20-110V Differential Relay for Transformer 88-264V 3 Phase O/C and E/. Relay for Transformer 20-110V 3 Phase O/C and E/. Relay for Transformer 88-264V Capacitor Bank Protection Relay 20-110V DIN mounting Capacitor Bank Protection Relay 88-264V DIN mounting Catalogue No. ED32TAXX000 ED32TBXX000 ED30TAXX000 ED30TBXX000 ED30CAXX000 ED30CBXX000

5/31

TECHNICAL DATA
CONTROL & SUPERVISION RELAYS Power Management Relay Multifunction 3 Phase Measuring Instrument
Display of various parameters, event count & event data on 8 digit alphanumeric display. Separate LEDs for various fault indication. .our user programmable output relays. Built in self supervision & self testing feature help maintenance. Easy operation by 5 push buttons. RS 485 port for serial communication with MSCOM User friendly software. MW33 MU30

Model

5
Description Device Code Design .unctions Available Power management 81, 27, 59, P., P QL, QC , Numeric .requence 2 stages, Voltage 2 stage, Power factor 2 stage, Active power 2 stage, Capacitor reactive power 2 stage. Actual measurement of .req, V, I, P., active power, reactive power. Other .eatures Display of Parameters, MD recording & data logging RS485 Port, Event recording Display of Parameters, Record of last event RS485 Port, Event recording, Event counter, MD recording, Oscillographic wave form capture Burden on CT Burden on PT Operating temp Weight Burden on Auxiliary supply Output Contacts Construction Dim W x H x D in mm Panel Cutout 0.2 VA for 5A, 0.01 VA for 1A 0.04 VA 10 to 60 C < 2kg 8.5 VA max 5 C/O Drawout 121 x 158 x 224 113 x 142 0.2 VA for 5A, 0.01 VA for 1A 0.04 VA 10 to 60 C < 2kg 8.5 VA max 5 C/O Drawout 121 x 158 x 224 113 x 142 Measurement Measure Numeric Actual measurements of .req, I, V, P., Power - Active / Reactive / Apparent Energy - Active / Reactive Maximum Demand

5/32

WIRING DIAGRAM
CONTROL AND SUPERVISION RELAYS

MW33

MU30
5/33

ORDERING IN.ORMATION
CONTROL AND SUPERVISION RELAYS
Model MW33 MW33 MU30 MU30 Description Power Management Relay 20-110V Power Management Relay 88-264V Measuring Relay 20-110V Measuring Relay 88-264V Catalogue No. EMW33AXX000 EMW33BXX000 EMU30AXX000 EMU30BXX000

5/34

TECHNICAL DATA
REVERSE POWER RELAY
Model MRP11

Description Design .unctions Available

Reverse Power Relay Micro-control based Instantaneous and Adjustable time relay Powerful D.T Algorithm .ield selectable voltage rating LED Indicators

Other .eatures

Compact size .lush mounting on panel

Burden on CT Burden on PT Operating temp Weight Burden on Auxiliary supply Output Contacts Construction Dim W x H x D in mm Panel Cutout

Not applicable PT - less than 0.25VA 0 to 60 C approx. 1kg less than 8 VA 1 C/O + 1 NO Contacts (self reset type) Drawout 71 x 158 x 204 142 x 62

5/35

WIRING DIAGRAM
REVERSE POWER RELAY

ORDERING IN.ORMATION
REVERSE POWER RELAY
Model MRP11 Reverse Power Relay Description Catalogue No. MRP11 00

Catalogue No. Selection Guide for MRP11

5/36

ORDERING IN.ORMATION
OTHER RELAYS
Model MX7/5 MX7/5 MC-R MC-R REX REX REX REX CPSC MSCOM Matrix Interface Module 20-110V Matrix Interface Module 88-264V Data Rec. & Comm. Module 20-110V Data Rec. & Comm. Module 88-264V Expansion Module 20-110V Expansion Module 88-264V Expansion Module 20-110V Expansion Module 88-264V RS232-485 Converter Communication Software Description Catalogue No. 99M75A000 99M75B000 99MCRA000 99MCRB000 99REXA000 99REXB000 99REXA001 99REXB001 99CPSC00 99MSCOM00

5/37