A Single-Phase Voltage Controlled Grid Connected Photovoltaic System with Power Quality Conditioner Functionality
Rosa A. Mastromauro, Student Member, IEEE, Marco Liserre, Senior Member, IEEE, Tamas Kerekes, Student Member, IEEE, Antonio DellAquila, Member, IEEE
Abstract Future ancillary services provided by photovoltaic (PV) systems could facilitate their penetration in power systems. Also low power PV systems can be designed to improve the power quality. This paper presents a single-phase photovoltaic system that provides grid voltage support and compensation of harmonic distortion at the point of common coupling (PCC) thanks to a repetitive controller. The power provided by the PV panels is controlled by a Maximum Power Point Tracking (MPPT) algorithm based on the incremental conductance method specifically modified to control the phase of the PV inverter voltage. Simulation and experimental results validate the presented solution. Index Termssingle-phase PV inverter, shunt controller, MPPT algorithm.

I. INTRODUCTION

mong the renewable energy sources, a noticeable

growth of small PV power plants connected to low-voltage distribution networks is expected in the future [1-2], as a consequence, research has been focusing on integration of extra functionalities such as active power filtering into PV inverters operation [3-4]. Anyway, distribution networks are less robust than transmission network and their reliability, because of the radial configuration, decreases as voltage level decreases. Hence, usually it is recommended to disconnect low-power systems when the voltage is lower than 0.85 pu or higher than 1.1 pu [5]. For this reason PV systems connected to low-voltage grids should be designed to comply with these requirements but can also be designed to enhance the electrical system offering ancillary services [6]. Hence they can contribute to reinforce the distribution grid maintaining proper quality of supply which avoids additional investments. However low-voltage distribution lines have a mainly resistive nature and, when a distributed power generation system (DPGS) is connected to a low-voltage grid, the grid frequency and the grid voltage cannot be controlled adjusting active and reactive power independently [7-9].
Copyright (c) 2007 IEEE. Personal use of this material is permitted. However, permission to use this material for any other purposes must be obtained from the IEEE by sending a request to pubspermissions@ieee.org.

This problem together with the need of limiting cost and size of the DPGS, that should remain economically competitive even when ancillary services are added, makes the design problem particularly challenging. The present paper proposes to solve this issue using a voltage controlled converter that behaves as a shunt controller improving the voltage quality in case of small voltage dips and in presence of nonlinear loads. Shunt controllers can be used as static var generator for stabilizing and improving voltage profile in power systems and to compensate current harmonics and unbalanced load current [10-18]. In this paper the PV inverter supplies the power produced by the PV panels but also improves the voltage profile as already pointed out [19]. The presented topology adopts a repetitive controller [20-27] able to compensate the selected harmonics. Among the most recent MPPT algorithms [28-31] it has been chosen an algorithm based on incremental conductance method [32-34]. It has been modified in order to take into account the power oscillations on the PV side and it controls the phase of the PV inverter voltage. The paper is organized as follows, in II it is discussed the possible voltage and frequency support provided by a DPGS converter connected to the grid; Section III discusses the use of shunt controllers for voltage dips compensation; the PV system improved with shunt controller functionality is proposed in IV; V presents the simulation results and VI shows the experimental results, finally, VII presents the conclusions. II. VOLTAGE AND FREQUENCY SUPPORT The power transfer between two sections of the line connecting a DPGS converter to the grid can be studied using short-line model and complex phasors, as shown in Fig.1. When the DPGS is connected to the grid through a mainly inductive line X>>R, R may be neglected. If also the power angle is small, then sin and cos 1 : XPA (1)
VAVB VA VB XQA VA

(2)

Authorized licensed use limited to: Aalborg Universitetsbibliotek. Downloaded on December 9, 2008 at 07:17 from IEEE Xplore. Restrictions apply.

2 When a voltage sag occurs, the converter provides reactive power in order to support the load voltage and the grid current I g has a dominant reactive component (3) The amplitude of the grid current depends on the value of the grid impedance since

I g + I C = I load

Fig. 1. (a) Power flow through a line; (b) phasor diagram.

where VA , PA , QA denote respectively the voltage, the active power and the reactive power in A and VB is the voltage in the section B, indicated in Fig.1. For X>>R, a small power angle and a small difference VA VB , equations (1) and (2) show that the power angle depends predominantly on the active power, whereas the voltage difference VA VB depends predominantly on the reactive power. In other words the angle can be controlled regulating the active power whereas the inverter voltage VA is controlled through the reactive power. Thus by adjusting the active power and the reactive power independently, frequency and amplitude of the grid voltage are determined. These conclusions are the basis of the frequency and voltage droop control through respectively active and reactive power [7]. In this paper the relation (1) has been adopted to optimize the power extraction from the PV panels (MPPT). III. SHUNT CONTROLLERS FOR VOLTAGE DIPS MITIGATION Shunt devices are usually adopted to compensate small voltage variations which can be controlled by reactive power injection. The ability to control the fundamental voltage at a certain point depends on the grid impedance and the power factor of the load. The compensation of a voltage dip by current injection is difficult to achieve, because the grid impedance is usually low and the injected current has to be very high to increase the load voltage. The shunt controller can be current or voltage controlled. When the converter is current controlled it can be represented as a grid-feeding component ( Fig. 2(a)) that supports the grid voltage by adjusting its reactive output power according to the grid voltage variations. When the converter is voltage controlled it can be represented as a grid-supporting component (Fig. 2(b)) which controls its output voltage. However also in this second case the control action results in injecting reactive power in order to stabilize the voltage. The vector diagrams of a shunt controller designed to provide only reactive power are reported in Fig. 3. When the grid voltage is 1 pu the converter supplies the reactive power absorbed by the load and the vector diagram of the current or voltage controlled converter is the same, in the first case it is controlled the compensating current IC , in the second one it is controlled the load voltage as underlined in Fig. 3(a) and Fig. 3(b).

Ig =
where

V Lg j Lg

(4)

V Lg is the inductance voltage drop shown in Fig.

3(c). If the shunt controller supplies the load with all the requested active and reactive power, in normal conditions it provides a compensating current I c = I load , hence, the system operates as in island mode and

Ig = 0.

Fig. 2. Use of a shunt controller for voltage dips compensation: (a) simplified power circuit of the current controlled shunt controller; (b) simplified power circuit of the voltage controlled shunt controller.

Fig. 3. Vector diagram of the shunt controller providing only reactive power: (a) current controlled converter in normal conditions; (b) voltage controlled converter in normal condition; (c) vector diagram for compensation of a voltage dip of 0.15 pu.

Authorized licensed use limited to: Aalborg Universitetsbibliotek. Downloaded on December 9, 2008 at 07:17 from IEEE Xplore. Restrictions apply.

3 In case of a voltage dip, the converter has to provide the active power required by the load and it has to inject the reactive power needed to stabilize the load voltage as shown in Fig. 4(b). The grid current in this case is reactive. It can be seen that

V load = E + V Lg (5) hence, during a voltage sag, the amount of reactive current needed to maintain the load voltage at the desired value is inversely proportional to Lg. This means that a large inductance will help in mitigating voltage sags, although it is not desirable during normal operation.

Fig. 5. Grid-connected PV system with shunt controller functionality. Fig. 4. Vector diagram of the shunt controller providing both active and reactive power: (a) normal conditions; (b) vector diagram for compensation of a voltage dip of 0.15 pu.

IV. PV SYSTEM WITH SHUNT-CONNECTED MULTIFUNCTIONAL CONVERTER In case of low power applications it can be advantageous to use the converter which is parallel connected to the grid for the compensation of small voltage sags. This feature can be viewed as an ancillary service that the system can provide to its local loads. The proposed PV converter operates supplying active and reactive power when the sun is available. At low irradiation, the PV converter operates only as harmonic and reactive power compensator. As explained in Section III, it is difficult to improve voltage quality with a shunt controller since it cannot provide simultaneously control of the output voltage and the output current. Besides, a largerated converter is necessary in order to compensate voltage sags. However this topology is acceptable in PV applications since the PV shunt converter must be rated for the peak power produced by the panels. In the proposed system the PV converter operates as a shunt controller; it is connected to the load through an LC filter and to the grid through an extra inductance Lg* of 0.1 pu as shown in Fig. 5. Usually in case of low power applications, the systems are connected to low voltage distribution lines whose impedance is mainly resistive, but, in the proposed topology, the grid can be considered mainly inductive as a consequence of Lg* addition on the grid side. However, since the voltage regulation is directly affected by the voltage drop on the inductance Lg*, it is not convenient choosing an inductance Lg* of high value in order to limit the voltage drop during grid normal conditions. It represents the main drawback of the proposed topology.

A. Control of the converter The proposed converter is voltage controlled with a repetitive algorithm. An MPPT algorithm modifies the phase displacement between the grid voltage and the ac voltage produced by the converter in order to force it to inject the maximum available power in the given atmospheric conditions. Hence the current injection is controlled indirectly. The amplitude of the current depends on the difference between the grid voltage and the voltage on the ac capacitor Vc. The phase displacement between these two voltages determines the injected active power (decided by the MPPT algorithm) and the voltage amplitude difference determines the reactive power exchange with the grid. The requested reactive power is limited by the fact that a voltage dip higher than 15 % will force the PV system to disconnect (as requested by standards). The active power is limited by the PV system rating and leads to a limit on the maximum displacement angle dmppt. Moreover the inverter has its inner PI-based current control loop and overcurrent protections. A phase-locked-loop (PLL) detects the amplitude Vpeak and phase grid of the grid voltage. Then the phase displacement dmppt is provided by the MPPT algorithm described in Section B. The voltage error between Vref and Vc is pre-processed by the repetitive controller which is the periodic signal generator of the fundamental component and of the selected harmonics: in this case the third and the fifth ones are compensated (Fig.6). The proposed repetitive controller is based on a finiteimpulse response (FIR) digital filter [20]; it is a moving or running filter, with a window equal to one fundamental period, defined as 2 N 1 2 (6) FDFT ( z ) = i = 0 hN cos h ( i + N a ) z i h N N
where N is the number of samples within one fundamental

Authorized licensed use limited to: Aalborg Universitetsbibliotek. Downloaded on December 9, 2008 at 07:17 from IEEE Xplore. Restrictions apply.

4 period, Nh is the set of selected harmonic frequencies and Na is the number of leading steps determined to track the reference exactly. The repetitive controller ensures a precise tracking of the selected harmonics and it provides the reference for the inner loop. In it a proportional-integral (PI) controller improves the stability of the system offering low-pass filter function. The PI controller Gc
Gc ( s ) = k p + ki s

(7)

is designed to ensure that the low frequency poles have a damping factor of 0.707. The open-loop Bode diagram of the system is shown in Fig. 6(b): the stability is guaranteed since the phase margin is about 45 degrees. In normal operation mode the shunt-connected converter injects the surplus of active power in the utility grid and, at the same time, it is controlled in order to cancel the harmonics of the load voltage. At low irradiation, the PV inverter acts only as a shunt controller eliminating the harmonics. Controlling the voltage Vc the PV converter is improved with the function of voltage dips compensation. In presence of a voltage dip, the grid current Ig is forced by the controller to have a sinusoidal waveform which is phase shifted by 90 with respect to the corresponding grid voltage.

(a)

B. MPPT algorithm Power supplied from a PV array depends mostly on present atmospheric conditions (irradiation and temperature), therefore in order to collect the maximum available power the operating point needs to be tracked continuously using a Maximum Power Point Tracker algorithm [28]. To find the maximum power point (MPP) for all conditions, it has been used an MPPT control method based on the Incremental Conductance Method [32], [34], which can tell on which side of the PV characteristic the current operating point is. The MPPT algorithm modifies the phase displacement between the grid voltage and the converter voltage providing the voltage reference Vref, furthermore, there is an extra feature added to this algorithm, which monitors the maximum and minimum values of the power oscillations on the PV side. In case of single-phase systems, the instant power oscillates with twice the line frequency. This oscillation in the power on the grid side leads to a 100 Hz ripple in the voltage and in the power on the PV side. If the system operates in the area around the MPP the ripple of the power on the PV side is minimized [33]. This feature can be used to detect in which part of the powervoltage characteristics the system operates. It happens in the proposed control scheme where the information about the power oscillation can be used to find out how close the current operating point is to the MPP, thereby slowing down the increment of the reference, in order not to cross the MPP. A flowchart of the MPPT algorithm is shown in Fig. 7 explaining how the angle of the reference voltage is modified, in order to keep the operating point as close to the MPP as possible. The MMP can be tracked by comparing the instantaneous conductance I pv _ k V pv _ k to the incremental conductance dI pv dVpv as shown in the flowchart. Considering the power-voltage characteristic of a PV array, it can be observed that operating in the area on the left side of the MPP d mppt has to decrease. This decrement is indicated in Fig.7 with side = 1 , moreover, operating in the area on the right side of the MPP d mppt has to increase and it is indicated with side = +1 . The increment size determines how fast the MPP is tracked. The measure of the power oscillations on the PV side is used to quantify the increment which is denoted with incr in Fig. 7.

(b) Fig. 6. Proposed repetitive-based controller: (a) control scheme; (b) Openloop Bode diagram of the system obtained using kFIR=1, Na=0 and Nh={1;3;5}.

Authorized licensed use limited to: Aalborg Universitetsbibliotek. Downloaded on December 9, 2008 at 07:17 from IEEE Xplore. Restrictions apply.

Fig. 7. Flowchart of modified MPPT algorithm.

V. SIMULATION RESULTS The PV system with power quality conditioner functionality has been tested in simulation with the following system parameters: LC filter made by 1.4 mH inductance and 2.2 F capacitance and 1 damping resistance; an inductance Lg* of 0.1 pu; an 1 kW load. The control has been validated in presence of sudden changes of the PV power caused, for example, by irradiation variations. The reported tests show the behavior of the MPPT for a voltage sag. The results refer to the case of inverter controlled in order to collect the maximum available power: 2 kW. The controller parameters are kFIR= 0.3, N=128 (sampling frequency = 6400 Hz) Na = 0, kp = 4.5, ki = 48. The set of test aims to demonstrate the behaviour of the system during a voltage sag and the interaction of the voltage control algorithm with the MPPT algorithm.

The simulation results, shown in Fig. 8-9, are obtained in case of a voltage dip of 0.15 pu. During the sag the inverter sustains the voltage for the local load (Fig. 8) injecting a mainly reactive current into the grid. The amplitude of the grid current Ig grows from 4.5 A to 8.5 A, as shown in Fig. 9, which corresponds to the reactive power injection represented in Fig.10. The inductance Lg* connected in series with the grid impedance limits the current flowing through the grid during the sag.

Fig. 8. Performance of the voltage controlled shunt converter with MPPT algorithm: grid voltage E, load voltage Vload.

Fig. 9. Performance of the voltage controlled shunt converter with MPPT algorithm: grid current Ig, converter current Ic, load current Iload.

Authorized licensed use limited to: Aalborg Universitetsbibliotek. Downloaded on December 9, 2008 at 07:17 from IEEE Xplore. Restrictions apply.

Fig. 10. Active and reactive power provided by the shunt-connected multifunctional converter to compensate the voltage sag of 0.15 pu.

Fig. 12. Laboratory setup.

The experimental tests have been made with grid voltage approximate background distortion THD=1.5%. They have been executed with two different kinds of loads. In the first case it has been tested the voltage sag compensation capability when the system feeds a purely resistive load absorbing 1200 W. In the second one the performances of the proposed system in presence of a highly distorting load have been analyzed. A. Voltage sag compensation The system has been tested in the following conditions: dc voltage Vdc=460 V. The results obtained in simulation in case of a voltage sag of 0.15 pu are confirmed experimentally in Fig. 13. During the dip the load voltage remain constant and equal to the desired voltage. The shunt-connected converter injects reactive current into the grid in order to compensate the load voltage, the current is mainly capacitive as it can be seen in Fig. 14. B. Voltage harmonic compensation in case of highly distorting load The performances of the shunt-connected converter have been analyzed in presence of a distorting load consisting of a single-phase diode bridge connected via a 10 mH inductance to the grid. The bridge feeds a 500 F capacitor with in parallel a 100 resistor. Before connecting the shunt converter the load voltage appears highly distorted, as shown in Fig. 15, and the voltage THD is around 17%. When the shunt-converter is connected to the grid, it compensates the voltage harmonics introduced in the system by the distorting load, as it is evident in Fig. 16 where the voltage THD is 2%. A detailed harmonic spectra comparison between Fig. 15 and Fig. 16 cases are reported in Fig. 17.

Fig. 11. Power-voltage characteristic of the PV array and current and voltage on the PV side in presence of a grid voltage sag to 0.85 pu.

When the voltage sag of 0.15 pu occurs the converter current grows from 8 A to 10.5 A, for this reason the shunt controller is not a good choice to compensate deeper dips. Fig. 11 demonstrates the robustness of the presented MPPT algorithm to the voltage dip, in fact in it there are shown the voltage and the current on the PV side during the sag. They are not significantly influenced by the dip. VI. EXPERIMENTAL RESULTS In order to verify the previous analysis, some experiments have been carried out on a laboratory set-up (Fig.12) to test the performance of the PV system with shunt controller functionalities. The hardware setup, shown in Fig.12 consists of the following equipment: a Danfoss VLT 5006 7.6 kVA inverter, whose only two legs are used, two series connected dc voltage sources to simulate PV panels string and dSPACE 1104 system. The PV converter is connected to the grid through an LC filter whose inductance is 1.4 mH, the capacitance is 2.2 F with in series a resistance of 1 ; besides an inductance Lg* of 15 mH (0.1 pu) has been added on the grid side of the converter as explained in the previous Sections.

Authorized licensed use limited to: Aalborg Universitetsbibliotek. Downloaded on December 9, 2008 at 07:17 from IEEE Xplore. Restrictions apply.

7 controlled by a software that implements the PV voltagecurrent characteristics as function of the irradiance (see Fig. 18). The test has been done considering a fixed power level of 700 W and a voltage dip of 0.15 pu occurring for 1.5 s. The experimental results are reported in Fig. 19: the dc voltage is not significantly influenced by the sag.

Fig. 13. Experimental results in case of a voltage sag of 0.15 pu: A grid voltage [300V/div], C load voltage [300 V/div], 1 grid current [10V/div].

Fig. 16. Experimental results in case of distorting load and shunt converter connected to the grid: A) grid voltage [300V/div], C) load voltage [300V/div], 1) load current [10V/div].
15 Magnitude [%] 10 5 0

Fig. 14. Experimental results in case of a voltage sag of 0.15 pu: 1 capacitive current injected into the grid to sustain the voltage sag.

6 7 8 9 10 11 12 13 14 harmonic order

Fig. 17. Load voltage harmonic spectrum in case of distorting load: (black bars) without shunt converter; (white bars) with shunt converter connected to the grid.

Fig. 15. Experimental results obtained in case of distorting load and without shunt converter: A grid voltage [300V/div], C load voltage [300V/div], 1 load current [10V/div].

C. Test with solar panels simulator This section proves the capability of the system to compensate a voltage dip when the inverter is fed by two PV arrays connected in parallel. In fact the two dc voltage sources, used in laboratory to feed the inverter, have been

Fig. 18. Graphical User Interface (GUI) of the solar panels simulator software.

Authorized licensed use limited to: Aalborg Universitetsbibliotek. Downloaded on December 9, 2008 at 07:17 from IEEE Xplore. Restrictions apply.

8
Power Systems, 2007. Josep M. Guerrero, Jos Matas, Luis Garca de Vicua, Miguel Castilla, Jaume Miret, Wireless-Control Strategy for Parallel Operation of Distributed-Generation Inverters, IEEE Transactions on Industrial Electronics , vol.53, no.5, Oct. 2006, pp. 1461-1470. Josep M. Guerrero, Jos Matas, Luis Garca de Vicua, Miguel Castilla, Jaume Miret, Decentralized Control for Parallel Operation of Distributed Generation Inverters Using Resistive Output Impedance, IEEE Transactions on Industrial Electronics, vol.54, no.2, April 2007, pp. 994-1004. K. De Brabandere, B. Bolsens, J. Van den Keybus, a. Woyte, J. Driesen, R. Belmans, A Voltage and Frequency Droop Control Method for Parallel Inverters, IEEE Transactions on Power Electronics,vol.22, no.4,July 2007, pp.1107-1115. M. Bollen, Understanding Power Quality Problems: Voltage Sags and Interruptions; Piscataway, NJ: IEEE Press, 1999. M. H. J. Bollen and I. Gu, Signal Processing of Power Quality Disturbances. New York: Wiley, 2006. Hasan Kmrggil, sman Kkrer,. A New Control Strategy for Single-Phase Shunt Active Power Filters Using a Lyapunov Function, IEEE Transactions on Industrial Electronics, vol.53, no.1, Feb. 2006, pp. 305-312. Micah E. Ortzar, Rodrigo E. Carmi, Juan W. Dixon , Luis Morn, Voltage-Source Active Power Filter Based on Multilevel Converter and Ultracapacitor DC Link, IEEE Transactions on Industrial Electronics, vol.53, no.2, April 2006, pp. 477-485. Bor-Ren Lin, Chun-Hao Huang, Implementation of a ThreePhase Capacitor-Clamped Active Power Filter Under Unbalanced Condition, IEEE Transactions on Industrial Electronics, vol.53, no.5, Oct. 2006, pp. 1621-1630. Ion Exteberria-Otadui, Amaia Lpez de Heredia, Haizea Gaztaaga, Seddik Bacha, M. Ral Reyero, A Single Synchronous Frame Hybrid (SSFH) Multifrequency Controller for Power Active Filters, IEEE Transactions on Industrial Electronics, vol.53, no.5, Oct. 2006, pp. 1640-1648. G Escobar,P. Mattavelli, A. M. Stakovis, A.A. Valdez, J. Leyva-Ramos, An Adaptive Control for UPS to Compensate Unbalance and Harmonic Distortion Using a Combine d Capacitor/Load Current Sensing, IEEE Transactions on Industrial Electronics, vol.54, no.2, April. 2007, pp. 839-847. Djaffar Ould Abdeslam, Patrice Wira, Jean Merckl, Damien Flieller, Yves-Andr ChapuisA Unified Artificial Neural Network Architecture for Active Power Filters, IEEE Transactions on Industrial Electronics , vol.54, no.1, Feb. 2007, pp. 61-76. M. Routimo; M. Salo; H. Tuusa; Current sensorless control of a voltage-source active power filter, Applied Power Electronics Conference and Exposition, 2005. APEC 2005. Twentieth Annual IEEE, Vol.3, Iss., 6-10, March 2005 pp. 1696- 1702. P. Wang, N. Jenkins, M.H.J. Bollen,; Experimental investigation of voltage sag mitigation by an advanced static VAR compensator , IEEE Transactions on Power Delivery, Vol.13, No. 4, October 1998. P. Mattavelli, F. Pinhabel Marafao, Repetitive-Based Control for Selective Harmonic Compensation in Active Power Filter, IEEE Transactions on Industrial Electronics, vol. 51, no. 5, October 2004, pp. 1018-1024. Fernando Bottern, Humberto Pinehiro, A Three-Phase UPS That Complies With The Standard IEC 62040-3, IEEE Transactions on Industrial Electronics , vol.54, no.4, Aug. 2007, pp. 2120-2136. G Escobar, A.A. Valdez, J. Leyva-Ramos, P. Mattavelli, Repetitive-Based Controller for a UPS Inverter to Compensate Unbalance and Harmonic Distortion, IEEE Transactions on Industrial Electronics , vol.54, no.1, Feb. 2007, pp. 504-510. G Escobar, P.R. Martnez, J. Leyva-Ramos, Analog Circuits to Implement Repetitive Controllers UIT Feedforward for Harmonic Compensation, IEEE Transactions on Industrial Electronics , vol.54, no.1, Feb. 2007, pp. 567-573.

[7]

[8]

[9]

[10] [11] Fig. 19. Experimental results obtained in case of dc voltage sources controlled by solar panels simulator and in presence of a voltage dip of 0.15 pu: 1 dc current [10V/div], 2 load voltage [400V/div], 3 grid voltage [400V/div], 4 dc voltage [200V/div]. [12]

VII. CONCLUSION In this paper a single-phase photovoltaic system with shunt controller functionality has been presented. The PV converter is voltage controlled with a repetitive algorithm. An MPPT algorithm has been specifically designed for the proposed voltage controlled converter. It is based on the incremental conductance method and it has been modified to change the phase displacement between the grid voltage and the converter voltage maximizing the power extraction from the PV panels. The designed PV system provides grid voltage support at fundamental frequency and compensation of harmonic distortion at the point of common coupling (PCC). An inductance is added on the grid side in order to make the grid mainly inductive, it may represent the main drawback of the proposed system. Experimental results confirm the validity of the proposed solution in case of voltage dips and nonlinear loads. REFERENCES
[1] F. Blaabjerg, R. Teodorescu, M. Liserre, A. Timbus; Overview of control and grid synchronization for distributed power generation systems ", IEEE Transactions on Industrial Electronics, vol.53, no.5, October 2006. F. Blaabjerg, R. Teodorescu, Z. Chen, M. Liserre: "Power Converters and Control of Renewable Energy Systems", Plenary session paper for 'ICPE 2004, Pusan (Korea), Oct. 2004. Tsai-Fu Wu, hung Shou Nien, Hui-Ming Hsieh, Chih-Lung Shen PV power Injection and Active Power Filtering with Amplitude-Clamping and Amplitude-Scaling Algorithms, IEEE Transactions on Industry Applications, vol. 43, no. 3, May/June 2007. M. Ciobotaru, R. Teodorescu, F. Blaabjerg, On-line grid impedance estimation based on harmonic injection for gridconnected PV inverter, 2007 IEEE International Symposium on Industrial Electronics, 4-7 June 2007, pp.2437-2442. IEEE 1547 Standard for interconnecting distributed resources with electric power systems, 2003. IEEE 1547.3 Guide for Monitoring, Information Exchange, and Control of Distributed Resources Interconnected with Electric

[13]

[14]

[15]

[16]

[17]

[18]

[19]

[2]

[20]

[3]

[21]

[4]

[22]

[5] [6]

[23]

Authorized licensed use limited to: Aalborg Universitetsbibliotek. Downloaded on December 9, 2008 at 07:17 from IEEE Xplore. Restrictions apply.

9
[24] G Escobar, P.R. Martnez, J. Leyva-Ramos, P. Mattavelli, A Negative feedback Repetitive Control Scheme for Harmonic Compensation, IEEE Transactions on Industrial Electronics, vol.53, no.4, Aug. 2006, pp. 1383-1386. Robert Gri, Rafael Cardoner, Ramon Costa-Castell, Enric Fossas,Digital Repetitive Control of a Three-Phase Four-Wire Shunt Active Filter, IEEE Transactions on Industrial Electronics , vol.54, no.3, June 2007, pp. 1495-1503. R. A. Mastromauro, M. Liserre, A. DellAquila.; Study of the Effects of Inductor Nonlinear Behaviour on the Performance of Current Controllers for Single-Phase PV Grid Converters IEEE Transactions on Industrial Electronics, vol. 55, no. 5, May 2008, pp. 2043-2052. R. A. Mastromauro, M. Liserre, A. DellAquila, R. Teodorescu; Performance comparison of current controllers with harmonic compensation for single-phase grid converter; Proceedings of OPTIM06, 10th International Conference on Optimization of Electrical and Electronic Equipment, Brasov, Romania, May 18-19, 2006. W. Xiao, J. Lind, W. Dunford, and A Capel, Real-Time Identification of Optimal Operating Points in Photovoltaic Power Systems, IEEE Transactions on Industrial Electronics, vol. 53, no. 4, August 2006. [29] Hiren Patel, Vivek Agarwal, Maximum Power Point Tracking Scheme for PV Systems Operating Under Partially Shaded Conditions, IEEE transactions on Industrial Electronics, vol.55, no. 4, April 2008. I. Kim, M. Kim, and M. Youn, New Maximum Power Point Tracker Using Sliding-Mode Observer for Estimation of Solar Array Current in the Grid-Connected Photovoltaic System, IEEE Transactions on Industrial Electronics, vol. 53, no. 4, August 2006. Weidong Xiao, Nathan Ozog, William G. Dunford, Topology Study of Photovoltaic Interface for Maximum Power Point Tracking, IEEE Transactions on Industrial Electronics, vol. 54, no.3, June 2007 J. Park, J. Ahn, B. Cho, and G. Yu, Dual-Module-Based Maximum Power Point Tracking Control of Photovoltaic Systems, IEEE Transactions on Industrial Electronics, vol. 53, no. 4, August 2006. H. Hinz, P. Mutschler, Voltage Source Inverters for Grid Connected Photovoltaic Systems, PEMC 1996. T. Esram, P.L. Chapman, Comparison of Photovoltaic Array Maximum Power Point Tracking Techniques, IEEE Transactions on Energy Conversion, vol.22, Issue 2, June 2007, pp. 439-449.

[25]

[30]

[26]

[31]

[32]

[27]

[33] [34]

[28]

Rosa A. Mastromauro (S'05) received the M.Sc. Degree in Electrical Engineering in 2005 from the Politecnico di Bari, where she is currently working toward the Ph.D. degree. Since 2005 she has been with the Converters, Electrical Machines and Drives Research Team at the Politecnico di Bari. Her research activity concerns power converters control for distributed power generation systems based on renewable energies. She is member of the IEEE Industrial Electronics Society, Power Electronics Society, Industrial Applications Society, Women in Engineering Society and of the Italian Electrical and Electronic Association (A.E.I.T.), she has been collaborating for IEEE journals and conference as a reviewer. Marco Liserre, (S'00-M'03-SM'07) received the MSc and PhD degree in Electrical Engineering from the Polytechnic of Bari, respectively in 1998 and 2002. From January 2004 he is an assistant professor in the same university teaching courses of power electronics, industrial electronics and electrical machines. Recently his research interests are focused on industrial electronics applications to distributed power generation systems based on renewable energies. He has co-authored 100 technical papers, 20 of them in international peer-reviewed journals and 3 chapters of a book. He has been a visiting Professor at Aalborg University (Denmark) and he has been giving lectures in different universities including four tutorials in international conferences. Marco Liserre is member of the Industrial Electronics Society, Power Electronics Society and Industry Applications Society. He has served them as reviewer both for conferences and journals. Within the IES he has been active as responsible of student activities, AdCom member, editor of the newsletter, responsible of region 8 membership activities, and chairman of the Technical Committee on Renewable Energy Systems. He has been involved in IEEE conferences organization in different capacities. He is an Associate Editor of the IEEE Transactions on Industrial Electronics. He is Editor-in-Chief of the IEEE Industrial Electronics Magazine.

Tamas Kerekes (S06) was born in 1978 in ClujNapoca, Romania. He obtained his Electrical Engineer diploma in 2002 from Technical University of Cluj, Romania, with specialization in Electric Drives and Robots. In 2005, he graduated the Master of Science program at Aalborg University, Institute of Energy Technology in the field of Power Electronics and Drives. In September 2005 he began the PhD program at the Institute of Energy Technology, Aalborg University. The topic of the PhD program is: "High frequency analysis and modeling of transformerless PV inverter systems".

Antonio Dell`Aquila (M'87) received the M.Sc. degree in Electrical Engineering from the Universit di Bari in 1970. Since 1970, he has been working with the Converters, Electrical Machines and Drives Research Team at the Universit di Bari. He is currently a Full Professor of Electrical Machines at the Politecnico di Bari, Italy, where he is also in charge of courses on power electronics and electrical drives. He has published over 100 technical papers in the fields of electrical machines models, transient analysis of rotating machines, inverter-fed induction machine performance, digital signal processing for non-sinusoidal waveforms, Kalman filtering for real-time estimation of induction motor parameters, control, monitoring and diagnostic of ac drives. His research current interests include harmonic pollution produced by electronic power systems, PWM techniques for power converters, power converters in renewable energy conversion systems, active power filters, multilevel inverters and intelligent control of power electronics equipment with fuzzy logic controllers. Prof. A. Dell'Aquila is a member of the IEEE Power Engineering Society and of the Italian Electrotechnical and Electronic Association (A.E.I.T.)

Authorized licensed use limited to: Aalborg Universitetsbibliotek. Downloaded on December 9, 2008 at 07:17 from IEEE Xplore. Restrictions apply.

You might also like