You are on page 1of 6

2016 IEEE Students' Conference on Electrical, Electronics and Computer Science

Impact of Grid Disturbances on the Output of Grid


Connected Solar Photovoltaic System

Om Prakash Mahela, Student Member IEEE Sheesh Ram Ola


Department of Electrical Engineering Dean, Research and Development
Indian Institute of Technology Jodhpur, India Apex Institute of Engineering & Technology, Jaipur
Email: opmahela@gmail.com Email: sheeshola@gmail.com

Abstract— The installed power capacity of grid-connected source to load in traditional network [5]. Integration of solar
photovoltaic (PV) systems has increased exponentially around the PV systems to the utility grid offers technical challenges such
world. The size of each unit is also increasing as they are as voltage fluctuations, harmonics, reactive power, low power
becoming more affordable. The grid is a highly non-linear factor, load management, and stability problems [6]. These
system. Hence, the grid disturbances affect the output of the solar problems are further enhanced and output of GCPVs are
PV systems. This paper presents a study of the effects of grid affected in the conditions of disturbances in the grid due
disturbances such as switching of loads, feeder tripping, outage, system operations such as load switching, power system
and synchronization of conventional generators on the output faults, outage and synchronization of conventional generators.
parameters of the grid-connected solar PV system. The voltage,
Significant research work has been reported in the field of
current and power of solar PV at the point of common coupling
have been analyzed. Further, the variations of dc output voltage
performance of grid connected GCPVs. Kumar et al. [7],
of the solar modules have also been investigated. The results are presented a performance study on a grid connected 20 kW
validated using a 100 kW solar PV system integrated with a test solar PV system installed in an industry. Results of the steady-
system in MATLAB/Simulink environment. The presence of state performance of a grid-connected rooftop hybrid wind-
disturbances is validated using the discrete wavelet transform photovoltaic system with battery storage during two years of
(DWT). operation has been presented by the authors in [8].
Performance study of a positive sequence detector plus dq
Index Terms— Feeder tripping, grid disturbance, load PLL synchronization algorithm for a 3-phase GCPV system
switching, photovoltaic system, solar energy, synchronization. under harmonic distortions and unbalances has been reported
in [9]. In [10], authors presented detailed modelling and
control of a grid connected solar PV system. Edalati et al.
I. INTRODUCTION [11], presented a comparative investigation of mono and poly-
Renewable energy sources are a promising alternative that crystalline silicon photovoltaic modules for use in grid-
could help in reducing the green house gases emissions from connected photovoltaic systems in dry climates. The design
electricity generation. These energy sources are expected to and performance of a real 11.04 kW GCPV system established
take a leading role in the future transition from a centralized to in an industrial sector which experiences the same fluctuations
distributed generation scheme [1]. Due to its wide application in solar irradiation and ambient temperature has been
areas, easy construction and low maintenance, the investigated by the authors. A framework for the reliability
photovoltaic (PV) solar energy is the most promising green evaluation of grid-connected photovoltaic system with
energy and grid-connected photovoltaic systems (GCPVs) intermittent faults in the network is proposed using dynamic
have shown the most growth in the world [2]. PV power Bayesian networks (DBN) by the authors in [12]. A three-state
generation directly converts the solar energy into electricity. Markov model is constructed to represent the state transition
PV technology will have good stand in the near future as the relationship of no faults, intermittent faults, and permanent
prices of PV modules are slowly dropping and these are faults. This model is further fused to DBNs. Mahela et al.
becoming economical. The output efficiency of these modules [13], presented a discrete wavelet transform based technique
has also increased in recent years about 20% to 30% [3]. The for the detection and localization of the power quality
GCPVs cumulative installed capacity in the world by the end disturbances associated with outage and grid synchronization
of 2013 was almost 139 GW [4]. of the solar PV system in distribution networks. Power quality
assessment in 3-phase grid connected solar PV system with
The conventional power system networks are designed to single and dual stage power extraction circuits has been
supply electric power from high or medium voltage networks reported in [14].
to consumers through low voltage feeders. With integration of
solar PV systems, the expected network behaviour may This work presents the impact of grid disturbances such as
change such as change in voltage profile with high PV switching of resistive and inductive loads, tripping of feeders
penetration with high voltage near the load against the voltage feeding the consumers, outage of generator and
drop from the source to the load in traditional network, power synchronization of generator with the utility grid on the
flow from load to the source against the power flow from the system parameters such as voltage and current at PCC as well

978-1-4673-7918-2/16/$31.00 ©2016 IEEE

Authorized licensed use limited to: Purdue University. Downloaded on September 18,2021 at 21:27:44 UTC from IEEE Xplore. Restrictions apply.
as output of the solar PV modules. The study has been carried array as reported in [13] have been used in this study. The
out in MATLAB/Simulink environment using a solar PV converter of solar PV plant has dc-dc boost converter which
system integrated with typical electrical power network. increases dc output voltage of PV module from 273.5 V to 500
Further, the presence of disturbances is detected using the V. The dc-ac inverter converts 500 V dc to 260 V three-phase
discrete wavelet transform (DWT). The sum of absolute ac supply. The transformer XPV steps up the 260 V three-
values of detail coefficients is used for the same. phase ac power to the 1.2 kV three-phase ac supply. The test
This paper is organized into six sections. The section II grid is operated at voltage with rms value of 1.2 kV. The loads
describes the test system used for the study. Discrete wavelet L1, L2 and L4 are initially connected in the network while the
transform and proposed algorithm are presented in Sections III load L3 is initially open circuited. The loading status of the
and IV respectively. Section V includes simulation results and test network is shown in Table I. The technical data of
their discussion. Finally, the conclusions are drawn in Section transformers are provided in Table II.
VI.
TABLE I. LOADING STATUS
II. TEST SYSTEM
Load MW Rating MVAR Rating
Single line diagram of the test system used for proposed L1 30 2
study is shown in Fig. 1. The conventional generators G1 and L2 2 0
G2 are connected to the network through the transformer L3 30 2
L4 2 0
(XFM). The generator G1 is initially connected to the system
while generator G2 is open. Three transmission lines TRL1,
TABLE II. TRANSFORMER DATA
TRL2 and TRL3 are connected in network as shown in the test
system. The positive and zero sequence impedances of Transformer MVA kV- kV- HV winding LV winding
High Low
transmission lines are (0.1153+j0.3958) ᅅ/km and R(ᅅ) X(ᅅ) R(ᅅ) X(ᅅ)
(0.4130+j1.2516) ᅅ/km respectively. The length of each
transmission line TRL1 and TRL2 is 14 kms. XFM 50 1.2 0.50 0.3807 2.7688 0.0510 0.0042
XPV 5 1.2 0.260 0.3807 2.7688 0.0510 0.0042

III. DISCRETE WAVELET TRANSFORM


The wavelet transform is a mathematical tool that
decomposes a signal into different scales with different levels
of resolution by dilating signal prototype function. It provides
local representation of a signal in both time and frequency.
Therefore, it is suitable for analyzing a signal where time-
frequency resolution is needed such as disturbance transition
events in power quality [15], [16]. The continuous wavelet
transform (CWT) of a signal x(t) is defined as

where

where is the base function or the mother wavelet.


Asterisk denotes the complex conjugate and a, b are the
dilation and translation parameters respectively. The
discretized mother wavelet is given by the relation

where a0 and b0 are the fixed constants; m, n are positive


Fig. 1. Single line diagram of the test system. integers. The discrete wavelet transform (DWT) is given by
The solar PV system is connected to the test grid through
the transmission line TRL3 having a length of 2.5 kms and
transformer (XPV). The point of integration of solar PV
The selection of ao=2 and bo=1 gives an algorithm, which
system with the network is known as point of common
is known as the multi-resolution signal decomposition
coupling (PCC). The bus B5 is considered as PCC. The solar
technique, to decompose a signal into scales with different
PV system consists of 66 parallel strings and each string has 5
time and frequency resolution.
modules connected in series. The technical data of solar PV

SCEECS 2016

Authorized licensed use limited to: Purdue University. Downloaded on September 18,2021 at 21:27:44 UTC from IEEE Xplore. Restrictions apply.
IV. PROPOSED ALGORITHM
The test system is simulated in MATLAB/Simulink
environment. Three-phase voltage, current and power injected
by the solar PV system into the grid are captured at the PCC.
The output dc voltage of the solar PV is also captured to see
behaviour of the solar PV during disturbances. The voltage
and current of phase-A at PCC and power injected by the solar
PV system into the grid are plotted for each of the cases under
study. The voltage signal is passed through the DWT and
decomposed using db4 as mother wavelet up to level 4 with
sampling frequency of 3.2 kHz. The sum of absolute values of
the detail coefficient is obtained using moving window of
width of 32 samples. The result so obtained clearly detects the
presence of disturbances in the signal.
V. SIMULATION RESULTS AND DISCUSSION
The impact of disturbances in the grid due to the system
operations such as switching of loads, generators and feeders
have been investigated using the test system. Frequency of 60 Fig. 2. (a) Voltage at PCC (b) current injected into the grid at PCC (c) power
Hz has been used for the ac supply. The bus B5 has been supplied to the grid and (d) output dc voltage of solar PV panel during
selected as the test point where voltage and current signals switching off the resistive load.
have been captured to carry out the proposed study. The data
has been captured after 60 cycles from the start of simulation
to avoid any disturbance due to start of simulation. Hence, the
time scale is represented from 1 to 2 seconds in the graphs.
A. Switching off the Resistive Load
The resistive load L2 has been switched off at 20 cycles.
The voltage of phase-A at PCC, current injected into the grid
at PCC, power supplied by the solar PV into the grid and Fig. 3. Detail coefficient for switching off the resistive load.
output dc voltage of solar PV module during switching off the
resistive load are shown in Fig. 2. The voltage at PCC the network change through small values for a period of 10
increases and current supplied by the GCPV into the network cycles. The power supplied by the solar PV into the network
decreases. The power supplied by the solar PV to the network increases slightly with small oscillations. The dc output
also increases. The dc output voltage of solar PV module voltage of solar PV module changes slightly for a period of 10
decreases from 280 V to 275 V. Small oscillations have been cycles.
observed in the dc output voltage of the solar PV module in
the Fig. 2 (d) as well as power oscillations in the power
injected by the solar PV into the grid for a period of 30 cycles.
Peak in the power curve of Fig. 2 (c) has also been observed at
the instant of switching off the load, this may be used to detect
the initiation of the event of switching off the load.
The sum of absolute values of detail coefficient at level 4
of voltage of phase-A during the event of switching off the
resistive load is plotted in Fig. 3. The initiation of the event is
detected by the sharp peak available in the plot and the
disturbances are detected by the continuous variations in the
values.
B. Switching off Inductive-Resistive Load
The inductive-resistive load L1 connected on the bus B2 has
been switched off at 20 cycles. The voltage of phase-A at
PCC, current injected into the grid at PCC, power supplied by Fig. 4. (a) Voltage at PCC (b) current injected into the grid at PCC (c) power
the solar PV into the grid and output dc voltage of solar PV supplied to the grid and (d) output dc voltage of solar PV panel during
switching off the inductive-resistive load.
module during switching off the inductive and resistive load
are shown in Figs. 4 (a), (b), (c) and (d) respectively. The The sum of absolute values of detail coefficient at level 4 of
system voltage at PCC and current supplied by the GCPV into voltage of phase-A during the event of switching off the

SCEECS 2016

Authorized licensed use limited to: Purdue University. Downloaded on September 18,2021 at 21:27:44 UTC from IEEE Xplore. Restrictions apply.
inductive-resistive load is plotted in Fig. 5. The event is
detected by the slight depression in the values as shown in the
plot. Significant disturbances have not been detected during
this event.

Fig. 7. Detail coefficient for feeder tripping.

D. Switching on the Inductive-Resistive Load


The inductive-resistive load L3 has been switched on at 20
Fig. 5. Detail coefficient for switching off the inductive resistive load.
cycles and connected on the bus B3. The voltage of phase-A at
PCC, current injected into the grid at PCC, power supplied by
C. Feeder Tripping the solar PV into the grid and output dc voltage of solar PV
The transmission line feeder TRL2 supplying the resistive modules during the switching of the inductive-resistive load
load L4 has been tripped at 20 cycles. The voltage of phase-A are shown in Figs. 8 (a), (b), (c), and (d) respectively. The
at PCC, current injected into the grid at PCC, power supplied system voltage at PCC and current supplied by the GCPV into
by the solar PV into the grid and output dc voltage of solar PV the network drop to very low values and harmonic
modules during tripping of feeder supplying resistive load are disturbances has been observed in both the voltage and current
shown in Figs. 6 (a), (b), (c) and (d) respectively. The signals. The power supplied by the solar PV into the network
behaviour of system parameters during tripping of feeder drops drastically to a value of 15 kW only. The continuous
supplying resistive load is similar to that during the switching spikes have been observed in the dc output voltage of solar PV
off the resistive load. The system voltage increases and current modules. This shows that the solar PV system becomes
supplied by the GCPV into the network decreases. The power unstable during such events in the grid.
supplied by the solar PV into the network increases. The dc
output voltage of solar PV module decreases from 280 V to
270 V. Small oscillations have been observed in dc output
voltage of the solar PV modules as well as power oscillations
in the power injected by the solar PV into the grid for a period
of 25 cycles.

Fig. 8. (a) Voltage at PCC (b) current injected into the grid at PCC (c) power
supplied to the grid and (d) output dc voltage of solar PV panel during
switching on the inductive-resistive load.

The sum of absolute values of detail coefficient at level 4


of voltage of phase-A during the event of switching on the
inductive-resistive load is plotted in Fig. 9. The continuous
disturbances are detected by the continuous variations in the
values after the event.
Fig. 6. (a) Voltage at PCC (b) current injected into the grid at PCC (c) power
supplied to the grid and (d) output dc voltage of solar PV panel during feeder
tripping.

The sum of absolute values of detail coefficient at level 4


of voltage of phase-A during the event of feeder tripping is
plotted in Fig. 7. The disturbances are detected by the
continuous variations in the values after the event. Fig. 9. Detail coefficient for switching on the inductive resistive load.

SCEECS 2016

Authorized licensed use limited to: Purdue University. Downloaded on September 18,2021 at 21:27:44 UTC from IEEE Xplore. Restrictions apply.
E. Outage of Conventional Generator A at PCC, current injected into the grid at PCC, power
The outage of conventional generator G1 is simulated at 20 supplied by the solar PV into the grid and output dc voltage of
cycles. The voltage of phase-A at PCC, current injected into solar PV modules during synchronization of conventional
the grid at PCC, power supplied by the solar PV into the grid generator G2 are shown in Fig. 12 (a), (b), (c) and (d)
and output dc voltage of solar PV modules during outage of respectively. The significant changes are not observed in the
conventional generator G1 are shown in Figs. 10 (a), (b), (c) voltage and current signals. The power supplied by the solar
and (d) respectively. The system voltage and current drop at PV into the network slightly increases. The dc output voltage
the time of outage of generator and large oscillations have of solar PV module has constant value and is not affected by
been observed in the current. Maximum disturbances have the synchronization of generator. The grid connected solar PV
been observed in both the voltage and current. The power system remains stable during the event of synchronization of
supplied by the solar PV to the network drops drastically to conventional generator with the grid.
nearly zero values. The continuous spikes with variable
magnitude and dips have been observed in the dc output
voltage of solar PV modules. This shows that the solar PV
system become unstable as capacity of the solar PV system is
very small as compared to the load connected in the network.
High peaks observed in the current signal may also damage
the costly equipment installed in the network.

Fig. 12. (a) Voltage at PCC (b) current injected into the grid at PCC (c) power
supplied to the grid and (d) output dc voltage of solar PV panel during
synchronization of conventional generator.

The sum of absolute values of detail coefficient at level 4


of voltage of phase-A during the event of synchronization of
conventional generator is plotted in Fig. 13. No significant
disturbances are detected during this event.
Fig. 10. (a) Voltage at PCC (b) current injected into the grid at PCC (c) power
supplied to the grid and (d) output dc voltage of solar PV panel during outage
of conventional generator.

The sum of absolute values of detail coefficient at level 4


of voltage of phase-A during the event of outage of
conventional generator is plotted in Fig. 11. The continuous
disturbances are detected by the continuous variations in the
values after the event. The magnitude of variation is less than Fig. 13. Detail coefficient for synchronization of conventional generator.
that during the event of switching on the inductive-resistive
load.
VI. CONCLUSIONS
A study of impacts of disturbances in the grid due the
power system operations such as switching of loads, tripping
of feeders, outage and synchronization of generators on the
output of grid connected solar PV system is presented in this
paper. The study is carried out in MATLAB/Simulink
environment using a test system with conventional generators,
Fig. 11. Detail coefficient for outage of conventional generator. loads, transmission lines, transformers and solar PV system
integrated through converters. The study showed that
oscillations have been observed in the voltage, current and dc
F. Synchronization of Conventional Generator
output voltage of the solar modules during the conditions of
The synchronization of conventional generator G2 on the switching on the inductive loads and outage of conventional
bus B1 has been simulated at 20 cycles. The voltage of phase- generators. The spikes have also been observed in the dc

SCEECS 2016

Authorized licensed use limited to: Purdue University. Downloaded on September 18,2021 at 21:27:44 UTC from IEEE Xplore. Restrictions apply.
voltage of solar PV modules and GCPV system becomes disturbances in distributed generation systems,” Sustainable Energy, IEEE
unstable in these events. Synchronization of conventional Transactions on, vol. 5, no. 1, pp. 200–208, Jan 2014.
generator with the utility grid do not affect the voltage, current [7] K. A. Kumar, K. Sundareswaran, and P. K. Venkateswaran, “Performance
study on a grid connected 20 kwp solar photovoltaic installation in an
and output dc voltage of the PV modules significantly and industry in tiruchirappalli (india),” Energy for Sustainable Development,
GCPV system remains stable. Switching off of resistive- vol. 23, pp. 294 – 304, 2014. [Online]. Available:
inductive load slightly affects the voltage current and power http://www.sciencedirect.com/science /article/pii/S097308261400101X
output of the solar PV system. Low magnitude variations are [8] F. Giraud and Z. M. Salameh, “Steady-state performance of a grid-
observed at the time of switching off the load. Voltage and connected rooftop hybrid wind-photovoltaic power system with battery
power output of solar PV increase while current decreases storage,” Energy Conversion, IEEE Transactions on, vol. 16, no. 1, pp.
with switching off of the resistive loads and tripping of feeder [9] N. F. Guerrero-Rodrguez, L. C. H. de Lucas, S. de Pablo-Gmez, and A. B.
Rey-Bou, “Performance study of a synchronization algorithm for a 3-
supplying the resistive loads. Transient have also been phase photovoltaic grid-connected system under harmonic distortions and
observed with the output dc voltage and output power of solar unbalances,” Electric Power Systems Research, vol. 116, pp. 252 – 265,
PV system. The presence of disturbances in the events under 2014. [Online].Available:http://www.sciencedirect.com/science/article/
study are validated with the help of discrete wavelet pii/S0378779614002223
transform. [10] F. Bouchafaa, D. Beriber, and M. S. Boucherit, “Modeling and control of
a grid connected pv generation system,” in Control Automation (MED),
2010 18th Mediterranean Conference on, June 2010, pp. 315–320.
REFERENCES [11] S. Edalati, M. Ameri, and M. Iranmanesh, “Comparative performance
[1] A. Gonzlez, J.-R. Riba, A. Rius, and R. Puig, “Optimal sizing of a hybrid investigation of mono- and poly-crystalline silicon photovoltaic modules
grid-connected photovoltaic and wind power system,” Applied Energy, for use in grid-connected photovoltaic systems in dry climates,” Applied
vol. 154, pp. 752 – 762, 2015. [Online]. Available: http://www. Energy, vol. 160, pp. 255 – 265, 2015. [Online]. Available:
sciencedirect.com /science/article/pii/S0306261915005681 http://www.sciencedirect. com/science/article/pii/S030626191501171X
[2] Y. Bouzelata, E. Kurt, R. Chenni, and N. Altn, “Design and simulation of [12] B. Cai, Y. Liu, Y. Ma, L. Huang, and Z. Liu, “A framework for the
a unified power quality conditioner fed by solar energy,” International reliability evaluation of grid-connected photovoltaic systems in the
Journal of Hydrogen Energy, vol. 40, no. 44, pp. 15 267 – 15 277, 2015, presence of intermittent faults,” Energy, vol. 93, Part 2, pp. 1308 – 1320,
the 4th International Conference on Nuclear and Renewable Energy 2015. [Online].Available:http://www.sciencedirect.com/science/article/
Resources (NURER2014), 26-29 October 2014, Antalya, Turkey. pii/S036054421501436X
[Online]. Available: http://www.sciencedirect.com/science/article/ [13] O. P. Mahela and A. G. Shaik, “Detection of power quality events
pii/S0360319915004577 associated with grid integration of 100kw solar pv plant,” in Energy
[3] K. K. Prajapat, A. Katariya, A. Kumar, and S. Shukla, “Simulation and Economics and Environment (ICEEE), 2015 International Conference on,
testing of photovoltaic with grid connected system,” in Computational March 2015, pp. 1–6.
Intelligence and Communication Networks (CICN), 2011 International [14] S. Patra, N. Kishor, S. R. Mohanty, and P. K. Ray, “Power quality
Conference on, Oct 2011, pp. 692–697. assessment in 3-phase grid connected pv system with single and dual
[4] G. A. Rampinelli, F. P. Gasparin, A. J. Buhler, A. Kren-zinger, and F. C. stage circuits,” International Journal of Electrical Power Energy Systems,
Romero, “Assessment and mathematical modeling of energy quality vol. 75, pp. 275 – 288, 2016. [Online]. Available:
parameters of grid connected photovoltaic inverters,” Renewable and http://www.sciencedirect.com /science/article/pii/S0142061515003968
Sustainable Energy Reviews, vol. 52, pp. 133 – 141, 2015. [Online]. [15] S. Santoso, E. J. Powers, W. M. Grady, and P. Hofmann, “Power quality
Available:http://www.sciencedirect.com/science/article/pii/S1364032115 assessment via wavelet transform analysis,” Power Delivery, IEEE
007340 Transactions on, vol. 11, no. 2, pp. 924–930, Apr 1996.
[5] M. J. E. Alam, K. M. Muttaqi, and D. Sutanto, “A sax-based advanced [16] O. P. Mahela and A. G. Shaik, “Power quality detection in distribution
computational tool for assessment of clustered rooftop solar pv impacts system with wind energy penetration using discrete wavelet transform,” in
on lv and mv networks in smart grid,” Smart Grid, IEEE Transactions on, Advances in Computing and Communication Engineering (ICACCE),
vol. 4, no. 1, pp. 577–585, March 2013. 2015 Second International Conference on, May 2015, pp. 328–333.
[6] P. K. Ray, S. R. Mohanty, N. Kishor, and J. P. S. Catalao, “Optimal
feature and decision tree-based classification of power quality

SCEECS 2016

Authorized licensed use limited to: Purdue University. Downloaded on September 18,2021 at 21:27:44 UTC from IEEE Xplore. Restrictions apply.

You might also like