Medium Voltage Distribution

up to 52 kV

WI

Gas-Insulated Switchgear with Vacuum Circuit-Breaker 1, 2 or 3-phase

System configuration

Conditions of Delivery The General Conditions of Delivery as amended shall apply. Illustrations The illustrations are not binding

WI

Contents

Overview .............................................................................................................. 4 Features ......................................................................................................... 4 Product description............................................................................................ 5 Technical description ...................................................................................... 5 Components of the switching unit .................................................................. 6 Modular design............................................................................................... 7 Single busbar WIA up to 36 kV..................................................................... 7 Double busbar WIB up to 36 kV ................................................................... 7 Single busbar WIA 52 kV, 250 kV BIL .......................................................... 8 Double busbar WIB 52 kV, 250 kV BILL ....................................................... 8 Operator interfaces ........................................................................................ 9 Switchgear panels ........................................................................................ 10 Current/voltage transformers ....................................................................... 11 Busbar modules ........................................................................................... 13 Modules ........................................................................................................ 15 Interlocks ...................................................................................................... 16 Gas compartment monitoring WIA, WIB ...................................................... 17 Gas-filled compartments of the WIA/ WIB ................................................... 18 Standards, regulations, provisions and standards....................................... 19 Type designation .......................................................................................... 20 Applied norms .............................................................................................. 21 Selection tables ................................................................................................ 22 WIA/WIB 12 kV ............................................................................................ 22 WIA/WIB 17 kV ............................................................................................ 24 WIA/WIB 24 kV ............................................................................................ 26 WIA/WIB 36 kV ............................................................................................ 28 WIA/WIB 38 kV ............................................................................................ 30 WIA/WIB 40.5 up to 52 kV ........................................................................... 32 WIA/WIB 1 and 2-pole, for stationary railway traction power supply 50/60 hz......34 Range of products ............................................................................................ 36 Single busbar panels WIA............................................................................ 36 Double busar panels WIB ............................................................................ 37 Disconnector panel ...................................................................................... 38 Bus section coupler / riser panel.................................................................. 38 Bus section coupler, Bus coupler, metering panel ....................................... 39 Cable connections............................................................................................ 40 Ecological considerations ............................................................................... 43 Design data ....................................................................................................... 44 Space requirements - dimensions and weights ........................................... 44 Busbar connection with fully insulated conductor bars ................................ 48 Shipping instructions....................................................................................... 50 Delievery, packaging .................................................................................... 50

WI EN

WI

Overview

Features
The gas-insulated and metal-enclosed switchgear WI has been designed for operation in power plants, transformer substations and industrial networks. The WI switchgear with vacuum circuit-breaker features maximum availability, optimum operator safety and clear design using SF6 gas as insulating medium. The switchgear units are insensitive to environmental influences, such as humidity, dust and aggressive gases, and offer complete operator safety. Their clear design facilitates operation.

Essential features
Parts under medium voltage in SF6 atmosphere insensitive to air humidity, air pollution and foreign matter High degree of operator safety complete metal enclosure for all system components under medium voltage Compact and clear design No mechanically moved parts in the busbar section No problems with SF6 decomposition products currents are switched in the vacuum interrupter chamber Inert insulating gas SF6 protects the switchgear against fire Three-pole enclosure of the functional compartments negligible sheath currents small number of static and dynamic seals few gas compartments, pressure relief devices and gas monitoring devices easy access moderate pressure increase in case of internal arcs straightforward kinematics between drive and circuit-breaker or three-position switch Steel used as enclosure material high pressure proofness good screening effect against X rays Optimum security of operation complete interlocking system separate actuators for isolation and earthing automatic circuit-breaker ON or OFF operation in case of earthing at the outgoing feeder High capacity current and voltage transformer Delivery of prefabricated switchgear panels to the construction site Fully shrouded terminals pluggable, fully insulated cable end boxes Switchgear extension possible on both sides from single to double busbar system.

Single busbar WIA up to 36 kV

WI EN

WI

Product description

Technical description
WI panels are suitable for configuring single or double busbar switchgear in conjunction with indoor installation. WI switchgear units are completely metal-enclosed. The busbar compartment which accommodates fixed parts only is segregated gas-tight from the flange-mounted switching unit. The switching unit comprises the three-position switch with isolating and earthing functions and the vacuum circuitbreaker; in case of double busbar systems, there are two threeposition switches with isolating and earthing functions and the vacuum circuit-breaker. The busbar compartment and the switching unit feature three-pole enclosure. Single-pole enclosure is provided in the area of the toroidalcore current transformers which are located in an easily accessible position outside of the SF6 atmosphere. The compact design results in a very clear switchgear arrangement with low space requirement; it has the advantage that a switching unit can be mounted or removed very quickly without the busbar requiring isolation from the power supply. The panels are equipped with a low-voltage cabinet for the required measuring and protection relays or the terminal strips. The high performance of the instrument transformers installed means that not only electronic but also conventional protection relays can be deployed. Thanks to its design, this panel series permits straightforward extension of an existing switchgear on both sides, and extension from single to double busbar models.

Gas-insulated double busbar switchgear WIB Rated voltage up to 36 kV; rated peak withstand current up to 100 kA; rated current up to 2500 A

WI EN

WI

Product description (contd.)

Components of the switching unit


The circuit-breaker in question is a vacuum circuit-breaker. The switching unit has been equipped, for its isolating and earthing functions, with a three-position switch featuring the positions: Disconnector Disconnector earthing switch Earthing switch ON (CLOSE) OFF (TRIP) ON (CLOSE)

Earthing
The metal-enclosed WI series switchgear is equipped with a separate earthing line running along the length of the switchgear.

Wiring
Wiring is effected with flexible cables (HO7V-K) in the technically required cross-sections.

Corrosion protection
If desired, the indoor panels WIA and WIB can be provided optionally with enhanced corrosion protection. To ensure optimum switchgear protection, the environmental installation conditions, such as wind-borne sand, aggressive dust (to be defined as salt dust, coke dust, cement dust etc.), vermin (termites), increased humidity levels, aggressive atmosphere (type of chemicals and their concentration to be defined) must be specified.

Installation locations
The switchgear has been designed for installation in closed electrical operating facilities.

Connection of cables and bars


The cables are connected by means of metal-enclosed connectors. Switchgear units equipped with multiple connection tanks enable connection of up to five 300 mm2 cables or two 1250 mm2 cables per phase, depending on the insulation rating. Alternatively, fully insulated busbar systems or SF6-insulated conductor bars can be used.

Low voltage cabinet


The secondary devices for protection relay, control, measurement, billing metering and other systems are installed in the low-voltage cabinet. The low-voltage cabinet is separated systematically from the primary part, is shock-proof and arc-resistant. It is an independent, closed low-voltage compartment with mechanical and electrical interfaces to the vertical section (screw-fastened plug-and-socket connector). The clear separation between the rack and the low-voltage cabinet is a particular advantage for the company operating the switchgear. Retrofitting spare panels and conversion or replacement of complete low-voltage cabinets (e.g. due to process changes) at a later date is also straightforward. The panel remains completely enclosed even if the low-voltage cabinet is not attached. Optional inspection ports can be integrated in the torsion-resistant door of the low-voltage cabinet, the door also being able to accommodate measuring instruments, control elements and protection relays.

WI EN

WI

Product description (contd.)

Modular design
A

Single busbar WIA up to 36 kV


B

A Tank with vacuum circuit-breaker and disconnector / earthing switch


C

B Drive with control panel and pressure gauge for gas monitoring C Tank with busbar D Supporting structure with cable connection area E Low voltage cabinet

D E

Double busbar WIB up to 36 kV


A Tank with vacuum circuit-breaker and disconnector / earthing switch B Drive with control panel and pressure gauge for gas monitoring
C2

C1 Tank with busbar 1 C2 Tank with busbar 2 D Supporting structure with cable connection area E Low voltage cabinet

B C1

D E

WI EN

WI

Product description (contd.)

Single busbar WIA 52 kV, 250 kV BIL


A Tank with vacuum circuit-breaker and disconnector / earthing switch
C

B Drive with control panel and pressure gauge for gas monitoring C Tank with busbar D Supporting structure with cable connection area E Low voltage cabinet

D E

Double busbar WIB 52 kV, 250 kV BILL


A Tank with vacuum circuit-breaker and disconnector / earthing switch
C2

B Drive with control panel and pressure gauge for gas monitoring C1 Tank with busbar 1 C2 Tank with busbar 2 D Supporting structure with cable connection area E Low voltage cabinet

C1

D E

WI EN

WI

Product description (contd.)

Operator interfaces for WIA (single busbar) and WIB (double busbar)
1 2 3 18 4 5 16 10 11 12 SS1 13 14 9

17

Operator interface, single busbar WIA

Operator interface, single busbar WIA

1 Button circuit-breaker ON 2 Button circuit-breaker OFF 3 Opening for charging the energy- storing device by means of a slide 4 Position indicator Energy-storing device (charged/released) 5 Circuit-breaker position indicator 6 Switch position indicator, disconnector (SS2) 7 Opening for operation of the disconnector (SS2) 8 Interrogating lever, disconnector 9 Earthing switch position indicator 10 Opening for operation of the earthing switch 11 Interrogating lever earthing switch 12 Switch position indicator, disconnector (SS1) 13 Opening for operation of the disconnector (SS1) 14 Interrogating lever, disconnector 15 Mechanical lock-out with cylinder lock 16 Rating plate 17 Insulating gas monitoring device 18 Operations counter SS1: busbar 1 (corresponds to the lower busbar tank) SS2: busbar 2 (corresponds to the upper busbar tank)

6 SS2 7 8 9 10 11 12 SS1 13 14

1 2 3 18 4 5 16

17

15 Operator interface, double busbar WIB

Operator interface, double busbar WIB

WI EN

WI

Product description (contd.)

Switchgear panels
Single busbar
Switchgear panel WIA up to 36 kV

Double busbar
Switchgear panel WIB up to 36 kV
9 10

8 7 1 6
6 7

10

5 3

5 4 3

1 2 3 4 5 6 7 8

Drive mechanism Vacuum circuit-breaker Low voltage cabinet Cable end boxes Current transformers Busbar Disconnector /earthing switch Pressure relief device

1 2 3 4 5 6 7 8 9 10
9

Drive mechanism Vacuum circuit-breaker Low voltage cabinet Cable end boxes Current transformers Busbar I Disconnector /earthing switch SSI Busbar II Disconnector /earthing switch SSII Pressure relief device
10

Switchgear panel WIA up to 52 kV


8 7

Switchgear panel WIB up to 52 kV

8 10

6 2
6

2 1

5
5

4 3
4 3

1 2 3 4 5 6 7 8

Drive mechanism Vacuum circuit-breaker Low voltage cabinet Cable end boxes Current transformers Busbar Disconnector /earthing switch Pressure relief device

1 2 3 4 5 6 7 8 9 10

Drive mechanism Vacuum circuit-breaker Low voltage cabinet Cable end boxes Current transformers Busbar I Disconnector /earthing switch SSI Busbar II Disconnector /earthing switch SSII Pressure relief device WI EN

10

WI

Product description (contd.)

Current/voltage transformers
Current transformers
The current transformers are designed as toroidal-core transformers and are put onto the cable outgoing feeder areas with single-pole enclosure. The current transformers in line with the busbar consist of identical units. There, they are slipped onto the busbar areas which also feature singlepole enclosure. The capacity of the current transformers is designed in such a way that supply of conventional protective devices is also possible. Up to 3 transformers (3 cores) can be accommodated per phase and outgoing feeder. The transformers can also be exchanged subsequently. Three current transformers (3 cores) per phase can also be installed in line with the busbar, in order to measure its currents. A special current transformer arrangement is the bus coupler panel within one panel width. In the double busbar top attachment tank, one core of max. 80 mm height with an ID of 135 mm and an OD of 195 mm can be installed for each phase. The low voltage is led out via a max. 7-pole line which is SF6 proof.

Current transformer in line with the busbar

Dimensions
Outgoing feeder: Transformer ID Transformer OD Max. stacking height In line with busbar: Minimum ID Maximum OD Maximum stacking height for all cores incl. intermediate layer 185 mm 250 mm 225 mm 185 mm 275 mm 160 mm

Measurement
/dyn Ith (3sec) Class Core rating (VA) Primary rated current Secondary rated current (VA) (A) (A) (kA) (kA) 0.5 M 5 up to 15 100 40 10 P 40 up to 5 150 up to 2500 1 or 5

Protection

10 P 10 up to 30

WI EN

11

WI

Product description (contd.)

Voltage transformer
The conventional solution for the inductive voltage transformer is a separate single-phase metalenclosed module which can be connected via cable connectors almost anywhere in the busbar area and on the outgoing feeder cable, and thus arranged in practically any location as required. in the outgoing feeder area Another design comprises metal-enclosed inductive voltage transformers directly flangemounted to the outgoing feeder block, with the isolating / earthing device mounted upstream. An externally operated isolating feature prevents the voltage transformer from being endangered/ put at risk during DC tests on the cable.

Voltage transformer on busbar

on the busbar A separate metering panel with a set of inductive voltage transformers is provided to this effect. Taking account of the high priority of the busbar, a disconnector enables isolation of the transformer section. Both disconnector and transformer are located in separate compartments. Thus, any damage which might occur in the vicinity of the transformer does not affect the isolating area or the busbar. Performance characteristic Ratings: Class: up to 50 VA 0.5

Voltage transformer in outgoing feeder cable (connection via multi-tank)

1 2

1 2

Multi-tank Test cable connector

12

WI EN

WI

Product description (contd.)

Busbar modules
Gas tank incl. installation parts Busbar Cover attachment on mounting flange with or without pressure relief. All five busbar compartments require one pressure relief device. If it is not possible to mount the device to the ends of the busbar tanks, e.g. if a tank for voltage transformer connection or a busbar earthing switch is located on the busbar end, or if the switchgear consists of over 10 panels, every fifth panel is equipped with a pressure relief device on the mounting flange Cover attachment on the stop flange of the left-hand and right-hand end panel, with or without pressure relief, to connect metalenclosed voltage transformers with cable connection to the front. Gas lines incl. pressure gauges; preferably attached to the end panel. (Only once for each gas compartment.) Desiccant for 4 busbar tanks each, or for each gas compartment. (Cannot be mounted on switchgear panels equipped with pressure relief device.) Compensation element for busbar tanks. Required after 20 single busbar panels, and after 10 double busbar panels. Disconnector for bus sectionalizer Earthing switch for bus sectionalizer to the left and right of the disconnector

WI EN

13

WI

Product description (contd.)

Accessories (for overall system)


SF6 gas for on-site assembly of the busbar sections Special paint Corrosion protection in case of extreme environmental conditions Panel labeling according to specification Operating elements, operating crank for vacuum circuit-breaker, disconnector, earthing switch; for the busbar sections movable segregating cover. Star handle spanner Hex. spanner Castors Transport cover for the busbar tanks (can be returned) Jack rings Integrated Voltage Detection System IVIS Earthing and short-circuit device, 3-phase incl. operating rod Cable dummy plug Cable test socket on cable connector for cable measurement Blanking caps for live cable connectors which have been withdrawn always required optional

Auxiliary equipment for transport only


Possible arrangement of the castors 1 Castors to be used 2 for movements in longitudinal direction 3 for transverse movements

14

WI EN

WI

Product description (contd.)

Modules

The modules and attachments shown on this page apply to outgoing feeder panels incoming feeder panels panels with circuit-breaker in case of coupler panels and bus sectionalizers.

Switching device module

Gas tank incl. pressure relief device, gas lines and pressure gauge Switching devices with three-position switch and vacuum circuit-breaker, desiccant

Drive section module


Drive casing with drive mechanisms incl. interlocks Attachment of drive casing on switching device module incl. connecting parts

Attachments for the vacuum circuit-breaker

Motor drive mechanism to charge the energy-storing device Auxiliary switch, 8, 12 or 16 contacts; 8 contact elements are required for the basic circuitry (material: silver [normal], gold, silver-palladium) Passing contact for pulse contact time stretching (contacts normal or gold-plated) Push switch actuated by energystoring device. (Push switches for basic circuitry included in basic design) Push switch, actuated by ON-OFF pushbutton. (The basic design includes 1 push switch for each) Shunt closing release, 1 ea. Shunt opening release, 1 or 2 ea. with or without auxiliary spring energy store Secondary release, 1 or 2 ea., or in case of design without undervoltage release: 3 ea. Undervoltage release, with or without time delay Blocking coil on ON pushbutton. Always required on coupler switch in case of bus section coupler and bus coupler, consisting of 2 panels (switchgear panel + bus riser panel) Blocking coil on OFF pushbutton. Always required on coupler switch in case of bus section coupler and bus coupler, consisting of 1 or 2 panel(s) (switchgear panel + bus riser panel) Mechanical lock-out with lock (for vacuum circuit-breaker and threeposition switch) Counter

Attachments for three-position switch

Motor-drive mechanism. In case of single busbar: 1 motor-drive mechanism each for isolating and earthing movements. In case of double busbar: 1 motor-drive mechanism for the isolating movement of busbar 1, busbar 2 and earthing movement of busbars 1+2. The vacuum circuitbreaker s ON button features a mechanical lock-out. An auxiliary switch, 2-20 contact elements each, for disconnecting and earthing movement. (Material: silver (normal), gold, silverpalladium) Interlocking solenoid. Single busbar: only in circuit-breaker panel of coupler and in bus riser panel of bus sectionalizer. Generally required in case of double busbar. If the interlocking solenoids are not installed in case of remote control (motor-drive mechanism) of the three-position switch, the local actuation is not locked. In this case, mechanical lockouts (locks) are required on the ON button of the vacuum ircuit-breaker and on the threeposition switch. always required optional

WI EN

15

WI

Product description (contd.)

Interlocks
Actuation of the three-position switch and the continuous mechanical interlock between circuitbreaker and three-position switch are designed in such a way that the operator can proceed as usual. This means separate, completely interlocked actuation for the switching procedures Establishing isolating distance and Earthing. For the earthing procedure, which is only possible with the three-position switch in isolated position, the circuit-breaker switched off and the circuit-breaker energy-storing device pre-charged, the circuitbreaker is connected positively after the contact blades have beeninserted into the earthing contacts, and protected against immediate mechanical or electrical switching OFF. Vice versa, on de-earthing, the circuit-breaker is first switched off positively before the isolating distance to the earthing contacts established. The interlocks ensure that each switching operation is always performed completely. Thus, once the switching operation has commenced, the motion cannot be reversed, if applicable, and the operating lever cannot be removed before it reaches its end position. The description only refers to the single busbar. In the case of double busbars, some of the internal interlocking functions of the panel, as well as all inter-panel interlocking functions are performed by electro-mechanical interlocks (blocking coil). The following interlocking functions are provided: Disconnector does not switch ON while the circuit-breaker or the earthing switch are ON None of the disconnectors switches OFF while the circuit-breaker or the earthing switch are ON Circuit-breaker only switches ON with the disconnector in its end position No earthing with disconnector engaged No earthing with circuit-breaker ON No earthing without circuit-breaker being in ready-to-operate condition Automatic connection of circuitbreaker during earthing Automatic disconnection of circuit- breaker during de-earthing The following has been ensured: The operating crank cannot be removed from the disconnector or earthing switch before it has reached its end positions completely The circuit-breaker cannot be actuated while a switching operation is being performed on the disconnector or earthing switch The circuit-breaker cannot be switched off with the three-position switch in earthing position All interlocks act partly mechanically and partly electrically An operating crank can only be inserted on the disconnector or earthing switch once the insertion opening has been released via a manual interrogation system. All interlocks also effective when the three-position switch is motor-actuated.

16

WI EN

WI

Product description (contd.)

Gas compartment monitoring


Single busbar WIA with bus section coupler

1 Gas-filled busbar compartments 2 Gas-filled circuit-br eaker compartments

Gas-tight electrical bushing Check valve Gas connector socket (disposal valve) Pressure gauge

Gas compartment monitoring


Double busbar WIB with bus coupler
1

1 Gas-filled busbar2 compartments 2 Gas-filled busbar1 compartments 3 Gas-filled circuit-br eaker compartments

Gas-tight electrical bushing Double check valve Gas connector socket (disposal valve) Pressure gauge

WI EN

17

WI

Product description (contd.)

Gas-filled compartments of the WIA/B series panels

WIA up to 40.5 kV, single busbar

WIB up to 40.5 kV, double busbar

WIA up to 52 kV, single busbar

WIB up to 52 kV, double busbar

WIA up to 36 kV, single busbar Gas-filled circuit-breaker compartment busbar 1 compartment busbar 2 compartment 18

WIB up to 36 kV, double busbar

WI EN

WI

Standards

Regulations, provisions and standards

WI series switchgear units are metal enclosed SF6 insulated prefabricated and type-tested tested for internal faults

Ambient and operating conditions


WI switchgear units are to be operated under normal operating conditions according to the specifications EN 60694 or the IEC publication 60694 (new: IEC 62271-1). Operation under conditions other than these is only admissible upon consultation with and with the consent of the manufacturer.

Degrees of protection against foreign objects and accidental contact


Main electric circuits Drives Low-voltage cabinets and cable connection compartments (operators side with cable compartment cover and side panels)
1)

IP 65 IP 2X, IP 5X1) IP 3X, IP 5X1)

Optional

Other ambient temperatures


The rated (normal) currents IN specified in the selection tables refer to a maximum ambient switchgear temperature of 40 C. In case of different maximum ambient temperatures T of the switchgear, between +25 C and +55 C, the appropriate normal current INT can be determined from the following formula:

At 25 0 C T < 40

0C

INT = IN

105 - T 65 105 - T 65 0.7

At 40 0 C < T 55

0C

INT = IN

Ambient conditions
Temperature class Min./max. ambient temperature Average value over 24 hours (max.) Maximum installation altitude above sea level C C m "Minus 25 indoors 1) -51) / 40 2) 35 3) 1000 4)

Insulating gas
Type Design pressure pre at 20 C
1) 2)

Sulphur hexafluoride (SF6) MPa 0.03 - 0.05

Optional: minus 25 indoors Optional up to 55 C in case of reduction of normal currents 3) Optional up to 40 C in case of reduction of normal currents 4) Higher installation altitudes possible on request

WI EN

19

WI

Standards
(contd.)

Regulations, provisions and standards

Type designation
The type designation of the type-tested, prefabricated panels contains information about their design, rated voltage, insulation level, panel width and panel height. Example: Prefabricated, type-tested WI series panel with single busbar, for indoor installation, version A Rated peak withstand current 100 kA Rated voltage 12 kV; insulation level acc. to list 2 Panel width: 600 mm, panel height: 2100 mm Type designation: WI A 10 / 12-2 / 621

Type designation
Series Version WI . . . A B 8 10 Rated voltage / 12-2 / 17-2 / 24-2 / 36-2 / 38-2 / 40.5-2 / 52-2 Dimension code WI A WI A WI B WI B up to 40.5 kV / 621 up to 52 up to 52 kV / 626 kV / 633 up to 40.5 kV / 627 /..- .

Explanation
Fully insulated (SF6) switchgear panels, primarily for distribution substations, for very stringent requirements Single busbar, indoors Double busbar, indoors Rated peak withstand current 80 kA 100 kA upper rated voltage 12 24 36 38 52 kV kV kV kV kV 2664 mm 2750 mm 3314 mm 17.5 kV

40.5 kV Panel width 600 mm Panel height 2100 mm 600 mm 600 mm 600 mm

20

WI EN

WI

Standards
(contd.)

Regulations, provisions and standards

Applied norms
WI switchgear units meet the following standards and regulations:

Designation
Switchgear

IEC standard
IEC 62271-200 IEC 60694 (new IEC 62271-1)

IEC classes
Category for operating availability: LSC 2A Partition class (compartmentalization class): PM

EN standard
EN 62271-200 EN 60694 (new EN 62271-1)

Behaviour in case of internal faults Circuit-breaker Earthing switch Three position disconnector Current transformers Inductive voltage transformers Voltage detection systems Protection against accidental contact, foreign objects and water Erection Operation of electrical equipment

IEC 60298 IEC 62271-100 IEC 62271-102 IEC 62271-102 IEC 60044-1 IEC 60044-2 IEC 61243-5 IEC 60529 M2, E1, C1 E2 M1

EN 60298 EN 62271-100 EN 62271-102 EN 62271-102 EN 60044-1 EN 60044-2 EN 60529 HD 637 S1 EN 50110

WI EN

21

WI

Selection tables

WIA/WIB 12 kV
Rated insulation level

Rated peak withstand current equal to rated short-circuit making current

Ratings of isolating distance

Rated lightning impulse withstand voltage

Rated power frequency withstand voltage

Rated (normal) current

Type

1s mm WIA WIA WIA WIA WIA WIB WIB WIB WIB WIB 8/12-2/621 8/12-2/621 8/12-2/621 8/12-2/621 8/12-2/621 8/12-2/627 8/12-2/627 8/12-2/627 8/12-2/627 8/12-2/627 600 12 75 28 85/32 600 12 75 28 85/32 kV kV kV kV/kV bar 0.8 0.8 0.8 1.3 1.3 0.8 0.8 0.8 1.3 1.3 0.8 600 12 75 28 85/32 0.8 1.3 1.3 0.8 600 12 75 28 85/32 0.8 1.3 1.3 50/60 50/60 50/60 50/60 Hz A 630 1250 1600 2000 25001) 630 1250 1600 2000 25002) 1250 1600 2000 25001) 1250 1600 2000 25002) kA 80 80 80 80 80 80 80 80 80 80 100 100 100 100 100 100 100 100 kA 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 40 40 40 40 40 40 40 40

3s kA 20 31.5 31.5 31.5 31.5 20 31.5 31.5 31.5 31.5 40 40 40 40 40 40 40 40 kA 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 40 40 40 40 40 40 40 40 38 38 38 38 %

WIA 10/12-2/621 WIA 10/12-2/621 WIA 10/12-2/621 WIA 10/12-2/621 WIB 10/12-2/627 WIB 10/12-2/627 WIB 10/12-2/627 WIB 10/12-2/627

LS = Circuit-breaker TS = Three-position switch, disconnector I/O ES = Three-position switch, earthing switch I/O with cooling gas tank, panel height 2750 mm with motor-actuated fan 3) possible limits and components fitted, refer to project planning documents WI no. 49 542 4) adm. tolerance range, no manufacturing tolerance, current value of one specimen, see routine test report 5) minimum service pressure 0.3 bar at a filling pressure of 0.8 bar; 0.7 bar at a filling pressure of 1.3 bar
1) 2)

22

Percentage value of the DC component

Rated short-circuit breaking current

3)

Rated short-time current

Rated frequency

Design pressure Pr at 20 0C 5)

Rated voltage

Panel width

WI EN

WI

Selection tables (contd.)

Rated operating sequence

Number of operating cycles without overhaul mechanical Rated breaking current under out-of-phase conditions electrical

Operating times with release 25 W 160 W 160 W

Command times with release 25 W 160 W 160 W Charging time for motor drive mechanism Operating time for disconnector and earthing switch with motordrive mechanism, 160 W s s 12 18 12 18 12 18 12 18

O - 3 min - CO - 3 min - CO

O - 0.3 s - CO - 3 min - CO

with rated (normal) current

O - 0.3 s - CO - 15 s - CO

Cable breaking current

Small indirect currents

with rated short-circuit breaking current

LS, TS, E

Arc duration (max.)

4)

4)

CO - 15 s - CO

Opening time

Opening time

Closing time

4)

Off

Off On ms 20 20 20 20

Off ms

kA 8 8 10000 1000 1000 10000 100

ms

ms

ms

ms

ms

25

10

8 8

45-65

33-50

40-70

12

50

10000 1000 1000 10000 100 45-65 33-50 40-70 12 50 20

25

10

10

10000 1000 1000 10000 1000 1000 10000 100 45-65 33-50 40-70 12 50 20 10000 100 45-65 33-50 40-70 12 50 20

25

10

10 10 10 10 10 10 10

25

10

WI EN

On 20

23

WI

Selection tables (contd.)

WIA/WIB 17 kV
Rated insulation level

Rated peak withstand current equal to rated short-circuit making current

Ratings of isolating distance

1s mm WIA WIA WIA WIA WIA WIB WIB WIB WIB WIB 8/17-2/621 8/17-2/621 8/17-2/621 8/17-2/621 8/17-2/621 8/17-2/627 8/17-2/627 8/17-2/627 8/17-2/627 8/17-2/627 600 17.5 95 38 110/45 600 17.5 95 38 110/45 kV kV kV kV/kV bar 0.8 0.8 0.8 1.3 1.3 0.8 0.8 0.8 1.3 1.3 0.8 600 17.5 95 38 110/45 0.8 1.3 1.3 0.8 600 17.5 95 38 110/45 0.8 1.3 1.3 50/60 50/60 50/60 50/60 Hz A 630 1250 1600 2000 25001) 630 1250 1600 2000 25002) 1250 1600 2000 25001) 1250 1600 2000 25002) kA 80 80 80 80 80 80 80 80 80 80 100 100 100 100 100 100 100 100 kA 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 40 40 40 40 40 40 40 40

Rated short-time current

Rated lightning impulse withstand voltage

Rated power frequency withstand voltage

Rated (normal) current

Type

3s kA 20 31.5 31.5 31.5 31.5 20 31.5 31.5 31.5 31.5 40 40 40 40 40 40 40 40 kA 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 40 40 40 40 40 40 40 40 38 38 38 38 %

WIA 10/17-2/621 WIA 10/17-2/621 WIA 10/17-2/621 WIA 10/17-2/621 WIB 10/17-2/627 WIB 10/17-2/627 WIB 10/17-2/627 WIB 10/17-2/627

LS = Circuit-breaker TS = Three-position switch, disconnector I/O ES = Three-position switch, earthing switch I/O with cooling gas tank, panel height 2750 mm with motor-actuated fan 3) possible limits and components fitted, refer to project planning documents WI no. 49 542 4) adm. tolerance range, no manufacturing tolerance, current value of one specimen, see routine test report 5) minimum service pressure 0.3 bar at a filling pressure of 0.8 bar; 0.7 bar at a filling pressure of 1.3 bar
1) 2)

24

Percentage value of the DC component

Rated short-circuit breaking current

Rated frequency

Design pressure Pr at 20 0 C 5)

Rated voltage

Panel width

3)

WI EN

WI

Selection tables (contd.)

Rated operating sequence

Number of operating cycles without overhaul mech. electrical

Operating times with release 25 W 160 W 160 W

Command times with release 25 W 160 W 160 W Operating time for disconnector and earthing switch with motor drive mechanism, 160 W s 18 18 18 18

Rated breaking current under out-of-phase conditions

LS, TS, E

On A

Off ms s

kA 8 8 10000 1000 1000 10000 100

ms

ms

ms

ms

ms

ms

25

10

8 8 8 8 8

45-65

33-50

40-70

14

50

20

20

10000 1000 1000 10000 100 45-65 33-50 40-70 14 50 20 20 12

25

10

8 8 8 10

10000 1000 1000 10000 1000 1000 10000 100 45-65 33-50 40-70 14 50 20 20 12 10000 100 45-65 33-50 40-70 14 50 20 20 12

25

10

10 10 10 10 10 10 10

25

10

WI EN

Charging time for motor drive mechanism 12

O - 3 min - CO - 3 min - CO

O - 0.3 s - CO - 3 min - CO

with rated (normal) current

O - 0.3 s - CO - 15 s - CO

Cable breaking current

Small indirect currents

with rated short-circuit breaking current

Opening time

Opening time

Arc duration (max.)

CO - 15 s - CO

4)

4)

Closing time

4)

On

Off

Off

25

WI

Selection tables (contd.)

WIA/WIB 24 kV
Rated insulation level

Rated peak withstand current equal to rated short-circuit making current

Ratings of isolating distance

1s mm WIA WIA WIA WIA WIA WIB WIB WIB WIB WIB 8/24-2/621 8/24-2/621 8/24-2/621 8/24-2/621 8/24-2/621 8/24-2/627 8/24-2/627 8/24-2/627 8/24-2/627 8/24-2/627 600 24 125 50 145/60 600 24 125 50 145/60 kV kV kV kV/kV bar 0.8 0.8 0.8 1.3 1.3 0.8 0.8 0.8 1.3 1.3 0.8 600 24 125 50 145/60 0.8 1.3 1.3 0.8 600 24 125 50 145/60 0.8 1.3 1.3 50/60 50/60 50/60 50/60 Hz A 630 1250 1600 2000 25001) 630 1250 1600 2000 25002) 1250 1600 2000 25001) 1250 1600 2000 25002) kA 80 80 80 80 80 80 80 80 80 80 100 100 100 100 100 100 100 100 kA 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 40 40 40 40 40 40 40 40

Rated short-time current

Rated lightning impulse withstand voltage

Rated power frequency withstand voltage

Rated (normal) current

Type

3s kA 20 31.5 31.5 31.5 31.5 20 31.5 31.5 31.5 31.5 40 40 40 40 40 40 40 40 kA 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 40 40 40 40 40 40 40 40 38 38 38 38 %

WIA 10/24-2/621 WIA 10/24-2/621 WIA 10/24-2/621 WIA 10/24-2/621 WIB 10/24-2/627 WIB 10/24-2/627 WIB 10/24-2/627 WIB 10/24-2/627

LS = Circuit-breaker TS = Three-position switch, disconnector I/O ES = Three-position switch, earthing switch I/O with cooling gas tank, panel height 2750 mm with motor-actuated fan 3) possible limits and components fitted, refer to project planning documents WI no. 49 542 4) adm. tolerance range, no manufacturing tolerance, current value of one specimen, see routine test report 5) minimum service pressure 0.3 bar at a filling pressure of 0.8 bar; 0.7 bar at a filling pressure of 1.3 bar
1) 2)

26

Percentage value of the DC component

Rated short-circuit breaking current

Rated frequency

Design pressure Pr at 20 0C 5)

Rated voltage

Panel width

3)

WI EN

WI

Selection tables (contd.)

Rated operating sequence

Number of operating cycles without overhaul mech. electrical

Operating times with release 25 W 160 W 160 W

Command times with release 25 W 160 W 160 W


Operating time for disconnector and earthing switch with motor drive mechanism, 160 W

Rated breaking current under out-of-phase conditions

LS, TS, E

On A

Off ms s s

kA 8 8 10000 1000 1000 10000 100

ms

ms

ms

ms

ms

ms

31.5

10

8 8 8 8 8

45-65

33-50

40-70

14

50

20

20

Charging time for motor drive mechanism 12 12 12 12

O - 3 min - CO - 3 min - CO

O - 0.3 s - CO - 3 min - CO

with rated (normal) current

O - 0.3 s - CO - 15 s - CO

Cable breaking current

Small indirect currents

with rated short-circuit breaking current

Opening time

Opening time

Arc duration (max.)

CO - 15 s - CO

4)

4)

Closing time

4)

On

Off

Off

18

10000 1000 1000 10000 100 45-65 33-50 40-70 14 50 20 20 18

31.5

10

8 8 8

10000 1000 1000 10000 1000 1000 10000 100 45-65 33-50 40-70 14 50 20 20 18 10000 100 45-65 33-50 40-70 14 50 20 20 18

31.5

10

31.5

10

WI EN

27

WI

Selection tables (contd.)

WIA/WIB 36 kV
Rated insulation level

Rated peak withstand current equal to rated short-circuit making current

Ratings of isolating distance

1s mm WIA WIA WIA WIA WIA WIB WIB WIB WIB WIB 6/36-2/621 6/36-2/621 6/36-2/621 6/36-2/621 6/36-2/621 6/36-2/627 6/36-2/627 6/36-2/627 6/36-2/627 6/36-2/627 600 36 170 70 195/80 600 36 170 70 195/80 kV kV kV kV/kV bar 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 600 36 170 70 195/80 1.3 1.3 1.3 1.3 600 36 170 70 195/80 1.3 1.3 1.3 50/60 50/60 50 50 Hz A 630 1250 1600 2000 2500 630 1250 1600 2000 25002) 1250 1600 2000 2500 1250 1600 2000 25002)
1) 1)

Rated short-time current

Rated lightning impulse withstand voltage

Rated power frequency withstand voltage

Rated (normal) current

Type

3s kA 20 25 25 25 25 20 25 25 25 25 40 40 40 40 40 40 40 40 kA 25 25 25 25 25 25 25 25 25 25 40 40 40 40 40 40 40 40 % 42 42 42 42 42 42 42 42 42 42 31 31 31 31 31 31 31 31

kA 63 63 63 63 63 63 63 63 63 63 100 100 100 100 100 100 100 100

kA 25 25 25 25 25 25 25 25 25 25 40 40 40 40 40 40 40 40

WIA 10/36-2/621 WIA 10/36-2/621 WIA 10/36-2/621 WIA 10/36-2/621 WIB 10/36-2/627 WIB 10/36-2/627 WIB 10/36-2/627 WIB 10/36-2/627

LS = Circuit-breaker TS = Three-position switch, disconnector I/O ES = Three-position switch, earthing switch I/O with cooling gas tank, panel height 2750 mm with motor-actuated fan 3) possible limits and components fitted, refer to project planning documents WI no. 49 542 4) adm. tolerance range, no manufacturing tolerance, current value of one specimen, see routine test report 5) minimum service pressure 0.7 bar
1) 2)

28

Percentage value of the DC component

Rated short-circuit breaking current

Design pressure Pr at 20 0C 5)

Rated frequency

Rated voltage

Panel width

3)

WI EN

WI

Selection tables (contd.)

Rated operating sequence

Number of operating cycles without overhaul mech. electrical

Operating times with release 25 W 160 W 160 W

Command times with release 25 W 160 W 160 W


Operating time for disconnector and earthing switch with motor drive mechanism, 160 W

Rated breaking current under out-of-phase conditions

LS, TS, E

On A

Off ms s s

kA 6.3 6.3 10000 1000 1000 10000 100

ms

ms

ms

ms

ms

ms

50

10

6.3 6.3 6.3 6.3 6.3

43-65

29-50

40-65

14

50

20

20

Charging time for motor drive mechanism

O - 3 min - CO - 3 min - CO

O - 0.3 s - CO - 3 min - CO

with rated (normal) current

O - 0.3 s - CO - 15 s - CO

Cable breaking current

Small indirect currents

with rated short-circuit breaking current

Opening time

Opening time

Arc duration (max.)

CO - 15 s - CO

4)

4)

Closing time

4)

On

Off

Off

12

18

10000 1000 1000 10000 100 43-65 29-50 40-65 14 50 20 20 12 18

50

10

6.3 6.3 6.3 6.3

10000 1000 1000 10000 1000 1000 10000 100 43-65 40-65 14 50 20 12 18 10000 100 43-65 40-65 14 50 20 12 18

50

10

6.3 6.3 6.3 6.3 6.3 6.3 6.3

50

10

WI EN

29

WI

Selection tables (contd.)

WIA/WIB 38 kV
Rated insulation level

Rated peak withstand current equal to rated short-circuit making current

Ratings of isolating distance

1s mm WIA WIA WIA WIA WIA WIB WIB WIB WIB WIB 8/38-2/621 8/38-2/621 8/38-2/621 8/38-2/621 8/38-2/621 8/38-2/627 8/38-2/627 8/38-2/627 8/38-2/627 8/38-2/627 600 38 200 80 220/90 600 38 200 80 220/90 kV kV kV kV/kV bar 1.45 1.45 1.45 1.45 1.45 1.45 1.45 1.45 1.45 1.45 1.45 600 40.5 185 (200) 85 215/90 (220/90) 1.45 1.45 1.45 1.45 600 40.5 185 (200) 85 215/90 (220/90) 1.45 1.45 1.45 50 50 50/60 50/60 Hz A 630 1250 1600 2000 2500 630 1250 1600 2000 25002) 1250 1600 2000 2500 1250 1600 2000 25002)
1) 1)

Rated short-time current

Rated lightning impulse withstand voltage

Rated power frequency withstand voltage

Rated (normal) current

Type

3s kA 20 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 kA 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 % 31 31 31 31 31 31 31 31 31 31 31 31 31 31 31 31 31 31

kA 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80

kA 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5

WIA 8/40.5-2/621 WIA 8/40.5-2/621 WIA 8/40.5-2/621 WIA 8/40.5-2/621 WIB 8/40.5-2/627 WIB 8/40.5-2/627 WIB 8/40.5-2/627 WIB 8/40.5-2/627

LS = Circuit-breaker TS = Three-position switch, disconnector I/O ES = Three-position switch, earthing switch I/O with cooling gas tank, panel height 2750 mm with motor-actuated fan 3) for possible limit values and components fitted, refer to the project planning documents WI no. 49 542 4) adm. tolerance range, is not a manufacturing tolerance, for the current value of a specimen, refer to the routine test report 5) minimum service pressure at 20 C = 1.0 bar (overpressure)
1) 2)

30

Percentage value of the DC component

Rated short-circuit breaking current

Rated frequency

Design pressure Pr at 20 0C 5)

Rated voltage

Panel width

3)

WI EN

WI

Selection tables (contd.)

Rated operating sequence

Number of operating cycles without overhaul mech. electrical

Operating times with release 25 W 160 W 160 W

Command times with release 25 W 160 W 160 W Operating time for disconnector and earthing switch with motor drive mechanism, 160 W s 18 18 18 18

Rated breaking current under out-of-phase conditions

LS, TS, E

On A

Off ms s

kA 10000 1000 1000 10000 100

ms

ms

ms

ms

ms

ms

50

10

43-65

40-65

14

50

20

10000 1000 1000 10000 100 43-65 40-65 14 50 20 12

50

10

10000 1000 1000 10000 1000 1000 10000 100 43-65 40-65 14 50 20 12 10000 100 43-65 40-65 14 50 20 12

50

10

50

10

WI EN

Charging time for motor drive mechanism 12

O - 3 min - CO - 3 min - CO

O - 0.3 s - CO - 3 min - CO

with rated (normal) current

O - 0.3 s - CO - 15 s - CO

Cable breaking current

Small indirect currents

with rated short-circuit breaking current

Arc duration (max.)

4)

CO - 15 s - CO

4)

Opening time

Opening time

Closing time

4)

On

Off

Off

31

WI

Selection tables (contd.)

WIA/WIB 40.5 up to 52 kV
2 vacuum interrupter chambers per conductor
Rated insulation level

Rated peak withstand current equal to rated short-circuit making current

Ratings of isolating distance

1s mm WIA 10/40.5-2/626 WIA 10/40.5-2/626 WIB 10/40.5-2/633 WIB 10/40.5-2/633 WIA WIA WIB WIB 8/52-2/626 8/52-2/626 8/52-2/633 8/52-2/633 600 kV 40.5 kV 200 kV 80 kV/kV 220/90 bar 1.45 1.45 1.45 1.45 290/110 2.2 2.2 290/110 2.2 2.2 Hz 50 A 1250 25001) 1250 2500
2)

Rated short-time current

Rated lightning impulse withstand voltage

Rated power frequency withstand voltage

Rated (normal) current

Type

3s kA 40 40 40 40 31.5 31.5 31.5 31.5 kA 40 40 40 40 31.5 31.5 31.5 31.5 % 26

kA 100 100 100 100 82 82 82 82

kA 40 40 40 40 31.5 31.5 31.5 31.5

600

40.5

200

80

220/90

50

600

52 (60)

250 (110)

95

50/60

1250 25001) 1250 25002)

600

52 (60)

250 (110)

95

50/60

LS = Circuit-breaker TS = Three-position switch, disconnector I/O ES = Three-position switch, earthing switch I/O with cooling gas tank, panel height 3314 mm and with motor-actuated fans with motor-actuated fan 3) possible limits and components fitted, refer to project planning documents WI no. 49 542 4) adm. tolerance range, no manufacturing tolerance, current value of one specimen, see routine test report 5) minimum service pressure at 20 C: 0.1 bar at a filling pressure of 1.45 bar; 1.8 bar at a filling pressure of 2.2 bar
1) 2)

32

Percentage value of the DC component 26 26 26

Rated short-circuit breaking current

Rated frequency

Design pressure Pr at 20 0C 5)

Rated voltage

Panel width

3)

WI EN

WI

WI EN
O - 3 min - CO - 3 min - CO O - 0.3 s - CO - 3 min - CO CO - 15 s - CO O - 0.3 s - CO - 15 s - CO A 50 50 50 A Small indirect currents kA Rated breaking current under out-of-phase conditions LS, TS, E mech. 50 10000 10000 1000 1000 1000 10000 1000 1000 1000 10000 10000 10000 with rated (normal) current with rated short-circuit breaking current Opening time
4)

Rated operating sequence

Cable breaking current

10000

Number of operating cycles without overhaul

1000 10000 100 100 100 100 ms 50-80 50-80 50-80 50-80 ms 40-65 40-65 40-65 40-65 14 14 50 50 20 12 18 20 12 18 14 50 20 12 18 14 50 20 12 18 ms ms ms ms On Off ms s s Off Off On Opening time
4)

1000 Closing time


4)

electrical 25 W 160 W 160 W

with release

Operating times

Selection tables (contd.)

Arc duration (max.)

Command times with release

25 W 160 W 160 W

Charging time for motor drive mechanism Operating time for disconnector and earthing switch with motor drive mechanism, 160 W

33

WI

Selection tables (contd.)

WIA/WIB 1 and 2-POLE, for stationary railway traction power supply 50/60 Hz
with 2 vacuum interrupter chambers per conductor
Rated insulation level

Rated peak withstand current equal to rated short-circuit making current

Ratings of isolating distance

Rated short-circuit breaking current 3s kA kA 25 25 25 25 31.5

1s mm WIA WIA WIA WIA WIA-Z 6/55-S/626 6/55-S/626 6/55-T/626 6/55-T/626 600 kV 27.5 kV 52 kV 250 kV 95 kV/kV 290/110 bar 2.2 Hz 50/60 A 1250 2000 1250 2000 1250 kA 65 65 65 65 80 kA 25 25 25 25 31.5

Rated short-time current

Rated (normal) curren 3)

Rated lightning impulse withstand voltage

Rated voltage U acc. to EN 60 694

Rated power frequency withstand voltage

Type

600

27.5

52

250

95

290/110

2.2

50/60

600

17.5

36

170

70

195/110

2.2

16 2/3

LS = Circuit-breaker TS = Three-position switch, disconnector I/O ES = Three-position switch, earthing switch I/O S = 1-pole T = 2-pole
3) 4) 5)

without cooling gas tank and heat sink adm. tolerance range, no manufacturing tolerance, current value of one specimen, see routine test report minimum service pressure at 20 C 1.8 bar

34

Percentage value of the DC component % 26 26 46

Rated voltage UNM acc. to EN 50 124

Design pressur e Pr bei 20 0C 5)

Rated frequency

Panel width

WI EN

WI

WI EN
O - 3 min - CO - 3 min - CO O - 0.3 s - CO - 3 min - CO CO - 15 s - CO O - 0.3 s - CO - 15 s - CO A 50 50 A Small indirect currents kA 12.5 12.5 Rated breaking current under out-of-phase conditions LS, TS, E mech. 1000 1000 1000 10000 10000 10000 10000 1000 10000 10000 with rated (normal) current with rated short-circuit breaking current Opening time
4)

Rated operating sequence

50

Cable breaking current

Number of operating cycles without over haul

1000 100 100 ms 50-80 50-80 ms 25-35 40-50 40-50 40-50 14 6-68 20 20 12 18 50 20 12 18 14 50 20 12 18 ms ms Off ms Off ms On Off On ms s s 100 Opening time
4)

1000 Closing time


4)

electrical 25 W 160 W 160 W

with release

Operating times

Selection tables (contd.)

Arc duration (max.)

Command time with release

25 W 160 W 160 W

Charging time for motor drive mechanism Operating time for disconnector and earthing switch with motor drive mechanism, 160 W

35

WI

Range of products

Single busbar panels


Circuit-breaker panel
With inner cone-type cable connection for rated voltage up to 52 kV rated short-circuit breaking current up to 40 kA rated busbar and outgoing feeder (normal) currents up to 2500 A

Disconnector panel
With inner cone-type cable connection for rated voltage up to 52 kV rated short-time current up to 40 kA rated busbar and outgoing feeder (normal) currents up to 2500 A

Bus section coupler


for rated voltage up to 52 kV rated short-circuit breaking current up to 40 kA rated busbar (normal) currents up to 2500 A

Circuit-breaker panel
(Inner cone-type cable connection)
Busbar attachments

Bus section coupler

Panel connection variants

Panel connection attachment 1) Current transformer Current transformer

Voltage transformer, pluggable Plug-in cable single

or

Plug-in cable or single, Terminal type 3 Voltage or transformer, 1) pluggable Surge arrester, pluggable

Plug-in cable double 1) Plug-in cable triple 1) Plug-in cable quadruple 1) Busbar Surge with solid arrester, insulation pluggable 1) if a surge arrester is used, the number of cables is reduced by one

or

or

or

and

or Busbar current transformer

1)

not possible in case of 52 kV

36

WI EN

WI

Range of products (contd.)

Double busar panels


Circuit-breaker panel
With inner cone-type cable connection for rated voltage up to 52 kV rated short-circuit breaking current up to 40 kA rated busbar and outgoing feeder (normal) currents up to 2500 A

Bus section coupler


(Circuit-breaker panel and bus riser panel) With inner cone-type cable connection for rated voltage up to 52 kV rated short-circuit breaking current up to 40 kA rated busbar and outgoing feeder (normal) current up to 2500 A

Bus section coupler


for rated voltage up to 52 kV rated short-circuit breaking current up to 40 kA rated busbar (normal) current up to 2500 A

Bus coupler (transverse)


for rated voltage up to 52 kV rated short-circuit breaking current up to 40 kA rated busbar (normal) current up to 2500 A

Metering panel
for rated voltage up to 36 kV rated busbar (normal) current up to 2500 A

Circuit-breaker panel
(Inner cone-type cable connection)
Busbar attachments

SS2 SS1

Panel connection attachment variants 1) Voltage transformer, pluggable Plug-in cable single Current transformer

or

Plug-in cable single, Terminal type3

or

Plug-in cable double 1) 1) if a surge arrester is used, the number of cables is reduced by one

or

Voltage transformer, pluggable 1)

or

Plug-in cable triple 1)

or

Surge arrester, pluggable

or

Plug-in cable quadruple 1)

and

Busbar current transformer

or

Busbar with solid insulation

Surge arrester, pluggable

1)

not possible in case of 52 kV 37

WI EN

WI

Range of products (contd.)

Disconnector panel
(Inner cone-type cable connection)

Bus section coupler / riser panel

SS2 SS1

SS2 SS1

Panel connection attachment 1) Panel connection variants Plug-in cable single Voltage transformer, pluggable Panel connection variants Plug-in cable single

Panel connection attachment 1) Voltage transformer, pluggable Current transformer

or

Plug-in cable double 1) 1) if a surge arrester is used, the number of cables is reduced by one

or

Plug-in cable double 1) 1) if a surge arrester is used, the number of cables is reduced by one

or

Plug-in cable triple 1)

or

Plug-in cable triple 1)

or

Plug-in cable quadruple 1)

or

Plug-in cable quadruple 1)

or

Busbar with solid insulation

Surge arrester, pluggable

or

Busbar with solid insulation

Surge arrester, pluggable

1)

not possible in case of 52 kV

38

WI EN

WI

Range of products (contd.)

Bus section coupler


SS2 SS1

Bus coupler up to 2500 A 1) Disconnector/earthing switch in line with busbar


SS2 SS1 SS2 SS1

Current transformer

Current transformer

Bus coupler up to 2000 A (1 panel width) 1)


SS2 SS1

Current transformer

1)

only up to 40.5 kV Abbreviations SS1 = Busbar 1 SS2 = Busbar 2

WI EN

39

WI

Cable connections

Cable connections in outgoing feeder block

The medium-voltage cables are connected to the switchgear panels via metal-enclosed inner cone-type plug-in terminations. The panels are equipped with inner cone-type appliance couplers according to EN 50 181. The manufacturers specifications of the regarding selection and assembly of the plug-in terminations must be adhered to. This does not only apply to the selection of size, but also to all electrical rated data, in line with the switchgears data. It is essential that all appliance couplers which are not equipped with plug-in terminations are terminated correctly using voltage-proof and fully shrouded insulating terminals/ dummy plugs. To this effect, the inner cone-type cable plug-in terminations for attachment to WI require capacitive decoupling. The coupling electrodes for the capacitive voltage detection system are an integral part of the appliance couplers installed in the switchgear panel.

Cable connections in outgoing feeder

3 phase switchgear panels

1 phase switchgear panels

2 phase switchgear panels

Inner cone acc. to EN 50181


Terminal types: size 1 size 2 size 3 (up to 40.5 kV) size 3 (> 40.5 up to 52 kV) size 4 630 A 800 A 1250 A 1250 A 2500 A

Single / double busbar Single cable, 3-phase, without outgoing voltage transformer
12-36 kV 1x size 1 1x size 2 1x size 3 1x size 4 38-40.5 kV

Size 4 with supporting structure increased in height

Single busbar Railway traction power supply with 2 vacuum interrupter chambers per phase
1-pole L1 Single cable connection 40 1x size 3/S 2-pole L1, L3 WI EN

WI

Cable connections (contd.)

Single / double busbar with 1 vacuum interrupter chamber per conductor/phase


Multi-cable, 3-phase, without outgoing voltage transformer 12 kV - 36 kV 2 x size 1 3 x size 1 2 x size 2 3 x size 2 4 x size 2 2 x size 3 3 x size 3 Multi-cable connection 4 x size 3 1 x size 1 + 2 x size 3 1 x size 2 + 2 x size 3 38 kV - 40.5 kV

Single / double busbar with 2 vacuum interrupter chambers per conductor/phase


Single- and multi-cable, 3-phase, without outgoing voltage transformer 40.5 kV BIL 200 kV 1 x size 3 1 x size 3/S 2 x size 3 2 x size 3/S 3 x size 3 3 x size 3/S 52 kV BIL 250 kV

Single busbar for stationary railway traction power supply with 2 vacuum interrupter chambers per conductor/phase
Multiple cable without voltage transformer 1-phase L1 2 x size 3/S 3 x size 3/S 4 x size 3/S 5 x size 3/S 2-phase L1 + L3

WI EN

41

WI

Cable connections (contd.)

Single / double busbar with 1 vacuum interrupter chamber per conductor/phase


Multi-cable, 3-phase with 3 outgoing voltage transformers 12 kV - 36 kV 1 x size 2 3 x size 2 4 x size 2 1 x size 3 2 x size 3 3 x size 3 4 x size 3 Multi-cable connection with voltage transformer in outgoing feeder 1 x size 2 + 1 x size 3 1 x size 2 + 2 x size 3 1 x size 2 + 3 x size 3 1 x size 2 + 4 x size 3 1 x size 1 + 3 x size 3 38 kV - 40.5 kV

Single / double busbar with 2 vacuum interrupter chambers per conductor/phase


Multi-cable, 3-phase, with 1 outgoing voltage transformer (1-phase in L2) 40.5 kV BIL 200 kV 1 x size 3 1 x size 3/S 2 x size 3 3 x size 3/S possible up to rated (normal) current in outgoing feeder of max. 1600 A 52 kV BIL 250 kV

Single busbar for stationary railway traction power supply with 2 vacuum interrupter chambers per conductor/phase
Multi-cable with 1 or 2 voltage transformers 1-phase L1 1 x size 3/S 2 x size 3/S 3 x size 3/S 4 x size 3/S 2-phase L1 + L3 Voltage transformers L3 Voltage transformers L1 + L3

42

WI EN

WI

Ecological considerations

A WI switchgear satisfies to a high degree ecological requirements in view of environmental protection thanks to optimization of material and energy consumption during manufacture compliance with all ecological requirements during its service life the use of recyclable materials for efficient disposal at the end of its service life. Our design directives regarding environmentally compatible design specify the use of materials which are easily recyclable and can be disassembled. The metals which make up approx. 90 % of the switchgear are easily recyclable. At the end of their service life, they are recycled 100 % in the form of homogenous materials. Plastics can also be recycled. Thermosetting i.e. non-melting plastics can be comminuted and reused as fillers in other plastic components; thermoplastic - i.e. melting - materials can be recycled in the form of homogenous material. This means that the material is conserved, melted down and used for the construction of new durable parts. To ensure efficient and environmentally compatible disassembly and assignment of materials by the responsible disposal experts, the switchgears plastic components have been identified accordingly. Moreover, material and utilization data sheets are available to provide the customer with an over- view about the materials used. Equally, the disposal company is provided with important information regarding the recycling process. Thus, the materials used for our products can be reused 100 %. This represents a major contribution towards saving primary energy and material resources. All materials were selected and developed so that e.g. in case of fire within buildings, affected switchgear only have a minor influence on the fire load (heat development, pollutants in the emissions). Another important ecological aspect is the longevity of our products (min. 30 to 40 years), which is an extremely long service life compared to other capital goods. Furthermore, the switchgear units have been designed so as to require little maintenance which would in turn use up energy and material, and so as to enable straightforward replacement of part components, e.g. if new controllers have been developed on the market (upgrading). In our gas-insulated switchgear WI, the majority of the switchgear panel has been sealed hermetically in an insulating inert gas (sulphur hexafluoride SF6 which is neither reactive nor toxic). Thus, all environmental influences reducing the service life are shut out. The special characteristics of the insulating gas also enable an overall size reduction by approx. 50 percent versus switchgear designed without insulating gas with comparable technical properties. This again saves a lot of material and energy required for material production. The portion of insulating gas used for WI switchgear amounts to approx. 0.5 percent by weight. Once the switchgears service life has elapsed, the gas is extracted completely via the disposal valve provided serially in each gas-filled, cladded compartment, and then recycled. The gas suppliers have developed an efficient recycling concept to this effect. During normal operation, the gas need not be replenished during the entire service life of the switchgear. The switchgear is a hermetically sealed pressure system acc. to IEC 60694 (IEC 62271-1).

Average material distribution in gas-insulated switchgear units


Materials
Metals Steel Copper Aluminium, brass Plastics Thermosetting plastics Thermo-plastics Elastomers Electronics Insulating gas WI EN Plastics Metals Sulphur hexafluoride

Wt. %
7 6.5 2 7 2 0.5 0.5 1 0.5 43

WI

Design data

Space requirements - dimensions and weights


>500
WIA up to 40.5 kV
WIA up to 52 kV

>1000

>1500 1)
>1000
>1500 1)

view

View

>500

>500

Top view Top view

>500

>1500 1)

1692

Spacer bars

70

673

70 280 70

Flooring ducts Flooring ducts

1)

smaller gap on request approx. approx. 1000 kg 1350 kg

Weights:
WIA up to 40.5 kV WIA 52 kV

44

70

460 600

2964

>500

2400

>500

>500

WI EN

WI

Design data

Space requirements - dimensions and weights (contd.)


WIA up to 52 kV
WIA up to 40.5 kV >500
WIA up to 52 kV >500 >1500 1) 2964 >1000

2400

>500

>500

>500

View view

>500 >1500 1) >500

Top view

>500

>500

>1000

>1500 1)

1692

Spacer bars

70

673

70 280 70

Flooring ducts

1)

smaller gap on request max. approx. 1000 kg 1350 kg

Weights:
WIA up to 40.5 kV WIA 52 kV

WI EN

70

460 600

45

WI

Design data

Space requirements - dimensions and weights (contd.)


WIB up to 40.5 kV
>500
WIB bis 40,5 kV
>500

WIB bis 52 kV

3050

>500

>500

>500

>1000

>1000

>1500 1)

>1500 1)

view View

>500 >500

>500

Top view

>500

>1500

1)

1692

460 600

70

Spacer bars

70

673

70 280

70

1)

smaller gap on request


approx. approx. 1300 kg 1700 kg

Weights:
WIB up to 40.5 kV WIB Flooring ducts 52 kV

46

3614

WI EN

WI

Design data

Space requirements - dimensions and weights (contd.)


WIB up to 52 kV
>500 >1500 1)

WIB up to 40.5 kV

>500

WIB up to 52 kV

3050

>500

>500

>1000

view View

>500

>500

Top view

Top view

>500

>1500 1)

1692

70

460 600

70

Spacer bars

70

673

70 280

1)

smaller gap on request


approx. approx. 900 - 1000 kg 1100 - 1500 Kg

Weights:
WIB up to 40.5 kV WIB Flooring ducts 52 kV

Flooring ducts

WI EN

>1000

>1500 1)

3614

47

WI

Design data

Space requirements - dimensions and weights (contd.)


Busbar connection with fully insulated conductor bars

Direct transfer line. Phase exchange in Direct transfer line. Phase terminal tank in terminal tank exchange

48

WI EN

WI

Design data

Space requirements - dimensions and weights (contd.)

Transfer line at the bottom. Phase Phase exchangein transfer line transfer line Transfer line at the bottom. exchange required required in

Transfer line top bottom by means means of supplementary gas tank Transfer line top andand bottom by of supplementary gas tank

Direct transfer line. Phase exchange in tank Directtransfer line. Phase exchange in terminalterminal tank WI EN 49

WI

Shipping instructions

Transporting the switchgear unit


When transporting the switchgear unit, it is important to ensure that the transport units do not slip or tilt (if necessary, nail transport pallet down to the loading surface). Reuse the original packaging to store parts which have been unpacked for inspection.

Packaging of the switchgear


If packed for truck transport, the switchgear unit is delivered on a pallet with PE protective film. For sea-worthy transport, the units are packed in sealed aluminium film with desiccant and in a closed case with tightly closed wooden base. In case of air transport, the switchgear unit is packed in a wooden crate with closed wooden base and with a blister IPE film as dust protection or in a wooden case, also with closed wooden base.

Transport to the site of installation


Store under conditions admissible for switchgear operation. Avoid condensation. During transport to the site of installation, remember that the main weight is located in the top area of the switchgear top-heavy. Transport using a forklift truck: Only transport the switchgear on a pallet. Attention top-heavy! Transport without pallet: The crane mounting harness must be hooked into the jack rings of the switchgear.

50

WI EN

Appendices

Notes

WI EN

51

Schneider Electric 35, rue Joseph Monier CS 30323 92506 Rueil-Malmaison Cedex, France RCS Nanterre 954 503 439 Capital social 896 313 776 www.schneider-electric.com WI EN

As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication. This document has been printed on ecological paper Publishing: Schneider Electric Design: Schneider Electric Printing: 02-2011

2011 Schneider Electric - All rights reserved