BMT300 User Manual ver 0J Apr 13

GE Energy, Lissue Industrial Estate East, Lissue Road, Lisburn, BT28 2RE, United Kingdom Tel: +44 (0) 28 9262 2915, Fax: +44 (0) 28 9262 2202 E-mail: ge4service@ge.com, Web: www.gedigitalenergy.com/md.htm

Intellix BMT 300 User Manual

Table of Contents
INTRODUCTION ................................................................................................................................. 4 Product Overview ......................................................................................................................... 4 Scope ................................................................................................................................................ 4 Abbreviations & Definitions ...................................................................................................... 5 Warnings & Cautions .................................................................................................................. 5 Conventions ................................................................................................................................... 6 Technical Specifications ............................................................................................................ 7 Measurements ......................................................................................................................... 7 Environmental .......................................................................................................................... 7 Power........................................................................................................................................... 8 Type Tests .................................................................................................................................. 8 SOFTWARE INSTALLATION .......................................................................................................... 10 CONFIGURATION OF Intellix BMT 300 ................................................................................. 10 ROUTINE USER-LEVEL OPERATIONS WITH IntellixTM BMT 300 ....................................... 11 Connection of PC to Intellix BMT 300 .............................................................................. 12 Opening the Setup software .................................................................................................. 13 Routine Operations with the Intellix BMT 300 ............................................................. 14 Maintenance Operations with the Intellix BMT 300 .................................................. 14 MENU OPERATIONS ....................................................................................................................... 15 Communications ........................................................................................................................ 15 General Information .................................................................................................................. 18 Device Information ............................................................................................................... 18 Transformer Rating .............................................................................................................. 19 Bushing Current Settings ........................................................................................................ 21 Main Alarm Settings .................................................................................................................. 23 Alarm Settings ........................................................................................................................ 23 System Supervision .............................................................................................................. 25 Partial Discharge................................................................................................................... 27 Bushing Insulation ................................................................................................................ 29

Page 2

Intellix BMT 300 User Manual

Alarm Statuses....................................................................................................................... 31 Relay Control .......................................................................................................................... 32 Measurement .............................................................................................................................. 33 Logging Page ............................................................................................................................... 34 Log Settings ............................................................................................................................ 34 Log Data ................................................................................................................................... 35 SD Card ..................................................................................................................................... 36 APPENDIX 1: MANUAL INSTALLATION OF Intellix BMT 300 SETUP SOFTWARE .... 37 APPENDIX 2 BUSHING ADAPTER CIRCUIT INTEGRITY TEST RECORD ........................ 38 APPENDIX 3 FRONT PANEL LIGHTS....................................................................................... 41

Copyright 2013, General Electric Company. Intellix is a registered trademark of General Electric Company. This release of this document is accurate at the time of this writing. General Electric Company reserves the right to change the Intellix BMT 300 and this document without notice. General Electric Company, Lissue Industrial Estate East Lissue Road, Lisburn, BT28 2RE, United Kingdom Tel: +44 28 9262 2915 Fax: +44 28 9262 2202 e-mail: ge4service@ge.com Web: www.gedigitalenergy.com/md.htm

Related Documents
# 1 2 3 Document Title Intellix BMT 300 Installation Manual BMT 300 Required Installation Information BMT 300 Service Manual

Page 3

Intellix BMT 300 User Manual

INTRODUCTION
Product Overview
The Intellix BMT 300 is a monitoring system that continuously: Measures the condition of transformer bushings. (through changes in Capacitance and Power Factor) Detects any Partial Discharges (PD) activity in the transformer main tank; (measured as high frequency pulses).

All measurements and alarms can be reported to a remote monitoring centre via either the standard RS485 connection, one of the other communications options, or manually downloaded by a visiting service engineer. The Intellix BMT 300 is supplied with PC setup software, which is the subject of this user manual.

WARNING

If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. The Intellix BMT 300 does not require periodic maintenance. However, if the transformer bushings are replaced then the Bushing Adapter circuit integrity checks that are at Appendix 2 should be implemented and the bushing nominal parameters updated before the transformer is returned to service. If the transformer bushings are subjected to routine maintenance, then the Bushing Adapter circuit integrity checks that are at Appendix 2 should be implemented before the transformer is returned to service.

WARNING

WARNING

Scope
This user manual covers the companion Intellix BMT 300 setup software: Its installation on a PC. The configuration operations after installation of the Intellix BMT 300.

Monitoring of the data is carried out using GEs PERCEPTION software (v1.10 or above). Please refer to its own user manual.

Page 4

Intellix BMT 300 User Manual

Abbreviations & Definitions


Abbreviation CT BMT 300 LOTO PD PDI Meaning Current Transformer Partial Discharge and Bushing Monitor Lock Out, Tag Out procedure Partial Discharge Partial Discharge Intensity

Warnings & Cautions


The meaning of symbols used on the Intellix BMT 300 device:

Refer to the Instruction Manual to prevent injury or damage to equipment

Hazardous voltages may be present

Primary Protective earth connection

This product has been tested to the requirements of CAN/CSA-C22.2 No. 61010-1, second edition, including amendment 1, or a later version of the same standard incorporating the same level of testing requirements.

The meaning of safety messages used in this Instruction Manual:

Page 5

Intellix BMT 300 User Manual

CAUTION WARNING

A procedure, practice, or condition could cause equipment damage or permanent loss of data A procedure, practice, or condition could cause bodily injury or death

Conventions
Menu items or options displayed on the display screen are represented in the text in bold, for example Alarm Setup. Choosing several options sequentially is represented by using > between the options, for example Alarm Setup > Top Oil Alarms.

Page 6

Intellix BMT 300 User Manual

Technical Specifications
Measurements
Feature Maximum Bushing Temperature at sensor Relative Phase Angle accuracy Maximum number of PD measured Maximum PD measurable Value 90 deg C (194 deg F) 0.01 deg of angle 200 PD per cycle (50 to 60Hz) CAT III. 5Vac rms, 200mA; on each phase

Environmental
Feature Cabinet Operating Temperature Range When equipped with multimaster comms option Operating Humidity Range Maximum Operating Altitude Storage Temperature Range Minimum Ambient Temperature for Installation and Service Activities Cabinet Protection Level Bushing Sensor Protection Level BMT 300 Weight Bushing Sensor Weight Bushing Sensor Operating Temperature Value -30 to +55 deg C (-22 to +131 deg F) -20 to +55 deg C (-4 to +131 deg F)

5 to 95% RH, non condensing 2000m (6500 ft) above sea level -40 to +85 deg C (-40 to +185 deg F) -20 deg C (-4 deg F) IP55 IP66 20 kg (44lb) 350 gm (0.8 lb), typical -40 to +90 deg C (-40 to +194 deg F) at Bushing Tapping Point

Page 7

Intellix BMT 300 User Manual

Power
Feature AC power supply requirement Output Relays (quantity 3) Value 100 to 240Vac, 50 to 60Hz, 1.24 to 0.41A Single Phase Change Over (SPCO), Maximum RATED: 2A @240VAC resistive load, 2A @ 30VDC 10 x 38 mm time delay 500V, 3A

Fuse (1 each on Live & Neutral)

Type Tests
Category EMC Emissions Standard CISPR 11 FCC part 15 IEC 61000-3-2 EMC Immunity IEC 61000-4-2 IEC 61000-4-3 IEC 61000-4-4 IEC 61000-4-5 IEC 61000-4-6 IEC 61000-4-8 IEC 61000-4-11 IEC 61000-4-12 IEC 61000-3-3 Class/Level A A A IV III III III III IV & V III X 2.5kV & 1kV Pst 10min, Plt 120min 5kV, 2kV & 500Vdc -30 C 55 C Test Radiated & Conducted Emissions Radiated & Conducted Emissions Harmonic Current Emissions Limits Electrostatic Discharge Electro Magnetic Field Immunity Electrical Fast Transients Surge Immunity Conducted RF Immunity Magnetic Field Immunity Voltage Dips & Interruptions Oscillatory Wave Voltage fluctuations & flicker

IEC 60255-5 EMC Immunity IEC 60068-2-1 IEC 60068-2-2

Impulse, Dielectric & Insulation resistance testing Cold Dry Heat

Page 8

Intellix BMT 300 User Manual

Category EMC Immunity

Standard IEC 60068-2-6

Class/Level 10-500Hz, 1g operation 10-500Hz, 1g endurance

Test Vibration

IEC 60068-2-30 EN 60529

55 C, 95%RH Enclosure IP55, Adaptor IP66

Damp Heat Degree of Protection

Safety

IEC 61010-1 EN 61010-1 UL 61010-1 CSA C22.2 No 61010-1

2001 2001 2nd Edition This product has been tested to the requirements of CAN/CSA-C22.2 No. 61010-1, second edition, including Amendment 1, or later version of the same standard incorporating the same level of testing requirements

Page 9

Intellix BMT 300 User Manual

SOFTWARE INSTALLATION
The Intellix BMT 300 setup software is supplied on a CD. To install the software, load the CD into your PCs DVD/CD drive, and the installer package should run automatically. If the installer does not run automatically, then use Windows Explorer to view the CDs directory structure. Select and double click on setup.exe in the root directory of the CD to start the Intellix BMT 300 Monitor installer. Note: the installation of a third-party run-time library requires the existence of a My Documents folder. If this folder does not exist the installation will fail. This error can also happen if your My Documents folder is on a network location which is not accessible at installer runtime. This issue can be fixed by assigning the My Documents folder. This can be done by either: a) Right-click on My Documents from the Start Menu or Desktop, select Properties, and edit the Target folder location field; or b) Edit the My Documents registry location directly. The key value can be found at HKEY_CURRENT_USER\Software\Microsoft\Windows\CurrentVersion\Explorer \Shell Folders. If manual assignment of the My Documents folder doesn't solve the issue, then creating a temporary user account in Windows and running the installer from that location should. Editing the registry carries inherent risks. Make sure you are familiar with the registry before editing the registry, manually or programmatically. It is highly recommended to create a backup of the registry before modifying it.

CONFIGURATION OF Intellix BMT 300


Once the Intellix BMT 300 cabinet has been installed and all the sensors connected, the Intellix BMT 300 should be configured. Service-level access to the BMT 300 setup software is required; please refer to the companion BMT 300 Service Manual for instructions.

Page 10

Intellix BMT 300 User Manual

ROUTINE USER-LEVEL OPERATIONS WITH IntellixTM BMT 300


A typical installation layout is shown at Figure 1 below. CAUTION WARNING
The external LED provide information about the BMT300 status, please refer to Appendix 3 The transformer will still be live during this process. Ensure that you are aware of the safe working zone and that the Bushing sensor cables are undamaged before approaching the Intellix BMT 300 cabinet. If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. All user-access activity should take place in ambient temperatures greater than -20 deg C (-4 deg F) to prevent damage to connectors and cabling as they may become brittle at extreme low temperatures.

WARNING

CAUTION

BMT 300

Figure 1: General Installation Layout

Page 11

Intellix BMT 300 User Manual

WARNING

During user access: Note that this unit may have more than one source of supply, eg the alarm relays may be from an independent AC supply. Disconnect all supplies at their source before servicing. Apply LOTO protocols. Do not open the BMT 300 cabinet during rain or snow storms.

WARNING

Connection of PC to Intellix BMT 300


Even if the Intellix BMT 300 has been wired to utilise a local Transfix as its communications method, the first configuration must be carried out by a direct connection of Intellix Setup software to the Intellix BMT 300. To connect a laptop with the Intellix Setup software directly to the Intellix BMT 300 use the provided USB to mini-USB cable to connect your laptop to the mini-USB connector on the Intellix BMT 300 motherboard.

WARNING

The BMT 300 is required to be live during the connection.

Acrylic cover

Plastic cover

Figure 2: Intellix BMT 300 Cabinet Internal Layout

Page 12

Intellix BMT 300 User Manual

Opening the Setup software


Launch the Intellix BMT 300 setup software, at the login screen shown below, select Customer or Service from the drop down as appropriate: Customer requires no password; you can navigate around the side tabs immediately, though you are offered a restricted selection. Service requires you to sign in using the credentials provided with the installation CD. Refer to the BMT 300 Service Manual for the service options available.

Figure 3: Monitor Sign On Screen

A full description of each side button and tab within that button is overleaf. Communications button on page 15. This allows alteration of the BMT 300 setup software basic communication settings to communicate with the BMT 300. General Information button on page 18. This displays the key serial number for the BMT 300 and the ratings of the monitored transformer. Bushing Current Settings button on page 21. This allows the entry of the basic modelling parameters. Alarm button on page 23. This gives allows entry of the alarm thresholds and gives access to and reset of the current alarm status. Measurement button on page 33. This displays the current values of the monitored parameters. Logging button on page 34. This configures the rate and type of data logging to SD card.

Page 13

Intellix BMT 300 User Manual

Routine Operations with the Intellix BMT 300


Most monitoring of the BMT 300 parameters would be carried out by use of the remotely connected Perception suite software. Direct connection to the BMT 300 by this setup software enables you to: Reset Alarms directly, go to page 31 for the Alarm Statuses. Alarm Settings. View the instantaneous readings of BMT 300 parameters; go to page 33. Clear or copy the log file; go to page35 Change Alarm thresholds; go to page 23 for the

Maintenance Operations with the Intellix BMT 300


Whenever the Bushings are serviced, the Bushing adapter sensor connections must be checked for continuity and proper connection. See Appendix 2 for the full procedure. The changing of a bushing must be reflected on the bushing configuration as shown in Bushing Current Settings.

Page 14

Intellix BMT 300 User Manual

MENU OPERATIONS
Communications
Click on the Communications side button, as shown below.

Figure 4: Communications Page

If the Intellix BMT 300 is to use an adjacent Transfix for its communications, then the settings from the Transfix column in Table 1 overleaf must be used. If the Intellix BMT 300 is to use another communications link, then select the most suitable. Note: Communication over modem requires ASCII transmission mode due to the low speed of the connection. Note 2: The settings in the Communications Settings tab are used to ensure that the Intellix BMT 300 setup software is attempting the communication with the correct protocol settings. It is required that the MODBUS protocol settings on the Intellix BMT 300 are to be changed, then Service user access rights are required to get access to the Utilities >MODBUS Slave Settings tab; refer to the BMT 300 Service Manual. If you change the MOBUS settings, then you will have to come back to this Communications Settings tab to enter the new protocol setting for the Setup software to use.

Page 15

Intellix BMT 300 User Manual

Serial Modbus Setting to be used when interfacing a TransFix family device In range 3 to 247. default value 3 COM port NB: This will only have to be changed if the Transfix is already using dev3 for another purpose 9600 Even RTU

Baud Rate Parity Check Transmission Mode

Table 1: Communications Settings whilst interfacing a TransFix family device

If a serial connection is selected the flow control must be off. Please refer to the serial hardware documentation. For a modem this may be done either via AT commands (see below) of the modem drivers interface. To validate the communications settings, click the Ping button.

If there is doubt about the existing communications settings, or the Ping fails, then the basic ModBus settings can be found by the following method: Connect the laptop to the main PCB USB port. Use a terminal application, such as Hyperterminal. Configure the terminal as: baud=115200, 8-N-1. Use the command, mbs You should get a report like this:

To reset the communication port to its default use mbsr. The default port is the serial port/USB (as opposed to the serial fibreoptic port), with address=3, baud rate=9600, Parity=Even and Protocol=RTU.

Page 16

Intellix BMT 300 User Manual

Once the settings are confirmed, it is suggested that they are saved for future reference, by pressing the Save Setting to File button. A Windows File Dialogue will open, to allow you to name the settings file (in configuration, cfg, format) and set the save location, as shown in Figure 5 below. Note: Most pages/ tabs have a Save Setting to File button. In each case, it will save just the configuration settings from that page/tab only. The option to save all configuration settings in one file requires the Service Function to obtain access to the Utilities>Program Setting tab; refer to the companion BMT 300 Service Manual.

Figure 5: Save Communications Settings

NB: to send commands directly to the modem: Use atd#, where # is the telephone number. Some modems require a specific command to open the data connection: atdt#. Use ath to terminate the communication. The modems escape sequence (by default +++) prior ath is usually required whilst connected in data mode. The list of supported flow control modes is read by at&k=?. The current mode is read by at&k? and set by at&kN or at&k=N, where N is 0 : no flow control 1 :hardware mono-directional flow control (only CTS active) 2: software mono directional flow control (XON/XOFF) 3: hardware bi-direction flow control 4: software bi-directional with filtering

Page 17

Intellix BMT 300 User Manual

5: pass through (software bi-directional without filtering) 6: both hardware bi-directional and software bi-directional flow control with filtering The AT commands above and flow control modes are widely accepted as standard but may differ for a particular modem. Please refer to the modem documentation.

General Information
The General Information Window has 2 tabs: Device Information. Transformer Rating.

Device Information
The Device Information tab has general identity data fields: Device type: either stand-alone or attached to a TransFix Device Serial: it is a 32 bit unsigned integer (2 Modbus registers). This is greyed out in the Customer user access as it is set at the factory and is used by Perception software to identify the device. Device ID: string, (32 characters). Enter a meaningful name to identify the device. Time zone: Define the GMT time zone with this drop-down menu. Sync Time: synchronises the BMT 300 time to the PC time. Read: read the current BMT 300 settings into the application. Write: write the application settings to BMT 300. Save Settings to File: saves settings from both the Device Information and Transformer Ratings tabs to file. Load Settings form File: loads settings for both the Device Information and Transformer Ratings tabs from file.

The button functions are:

Page 18

Intellix BMT 300 User Manual

Figure 6: General Information page > Device Information tab

Transformer Rating
The Transformer Rating fields to be completed as follows: Transformer Rated primary voltage: enter the nominal peak-to-ground line-to-line voltage (kV). Used to calculate IHVref. Both primary and secondary voltages can be given as peak-to-ground (amplitude) or RMS. The right unit must be selected from the associated drop-down menu. Transformer Rated secondary voltage: enter the nominal peak-to-ground line-to-line voltage (kV). Used to calculate ILVref. Transformer rated current: info only not used. Neutral type: select from drop down menu with 2 options: available, not available. If available, PD polarity discrimination is made available in System Configuration. Power System frequency: 50Hz or 60Hz. Used to calculate IHVref and ILVref. Transformer Top Oil Rise temperature: info only; usually 50-60C. Transformer temperature rise time: info only not used. Transformer forced cooling rating: info only not used.

Once all the settings have been entered, press the Write button to load the settings into the Intellix BMT 300. It is advisable to update the configuration file by pressing the Save Settings To File button.

Page 19

Intellix BMT 300 User Manual

Figure 7: General Information page > Transformer Rating tab

Page 20

Intellix BMT 300 User Manual

Bushing Current Settings

Figure 8: Bushings Current Settings Page

Parameter Off-line Power Factor value phase A, B & C Off-line capacitance value A, B, & C Temperature off-line measurement

Source/ Suggested Value Nominal value of Power Factor x100 (or PF%) Nominal value of C1 Temperature at which the above values where measured Calculated current in mA expected at each tapping point. Default 10%

Units % pF deg C

Calc bushing tap current phase A, B & C (greyed out as for info)

mA

Yellow Alarm (sets value at which background colour of Bushing Current Amplitude fields in Measurement page changes: Green - OK; Yellow beyond yellow alarm; red no signal)

Page 21

Intellix BMT 300 User Manual

Parameter Calc. Phase Angle A-B & A-C

Source/ Suggested Value Expected angle between phases A-B and A-C based on nominal PF%1, default values of 120 and -120. See note 1 below

Units

Bushing type

Select from drop down menu. Sets temperature correction for PF% and C1% for either OilImpregnated Paper Bushing (OIPB) or ResinImpregnated Paper Bushing (RIPB) The load across which the voltage is measured to calculate the capacitive current (I=V/R).
Table 2: Bushing Parameters

N/A

Shunt Resistance A, B & C

Ohm

After entering settings for Primary bushings, repeat procedure and enter settings for Secondary bushings if applicable. Once all the settings have been entered, press the Write button to load the settings into the Intellix BMT 300. It is advisable to update the configuration file by pressing the Save Settings To File button.

The expected angles are calculated as A-B=120+PF%B100-PF%A100

and A-C=-120+PF%C100-PF%A100

Page 22

Intellix BMT 300 User Manual

Main Alarm Settings


There are 5 tabs in the Alarm page: Alarm Settings, go to page 23. System Supervision, go to page 25. Partial Discharge, go to page 27. Bushing Insulation, go to page 29. Alarm Statuses, go to page 31. Note: If the Alarms are set to manual acknowledgement in the Alarm Settings tab, then alarms have to be manually acknowledged and reset in this tab. Relay Control, go to page 32

Alarm Settings

Figure 9: Alarm Page> Alarm Settings Tab

Page 23

Intellix BMT 300 User Manual

Parameter System status enable Primary voltage data enable Secondary voltage data enable PD Status Enable Hysteresis on alarms

Suggested Value Checked Checked Checked if secondary set of bushings is monitored, unchecked otherwise. Default is unchecked. Checked Default is 5%. Alarm triggered if parameter is above threshold. Trigger armed as long as parameter >100Hysteresis on alarms % of the threshold value. Value is advised to be 10% or less. Default is 60s, allowable range is 0 to 3600s. Period at the end of which the parameters are sampled and compared against their respective alarm thresholds. If a consecutive number of samples of a particular parameter are above its alarm threshold is equal or greater than the Alarm & trend required samples then the alarm trigger is armed (see below). Once the trigger is armed it will not be disarmed until this particular parameter is below its hysteresis-corrected threshold (see above). If the Alarm Status is Auto the alarm will switch off if the trigger is disarmed. If it is Manual the alarm will be on independently of the trigger status until it is acknowledge, at which time the alarm will switch off if the trigger is unarmed. Default=60, allowable range is 0 to 3600. Required number of consecutive samples above the given threshold to arm the alarm trigger. See above. Choice of Auto or Manual (see above): Default is Auto. Auto the alarms switch off once the parameter goes back into the acceptable range. Manual the alarm is maintained until it is manually acknowledged, see the Alarm Statuses tab on page 31
Table 3: General Alarm Settings

Alarm & trend sampling period

Alarm & trend required samples

Alarm Status

Once all the settings have been entered, press the Write button to load the settings into the Intellix BMT 300. It is advisable to update the configuration file by pressing the Save Settings To File button.

Page 24

Intellix BMT 300 User Manual

System Supervision

Figure 10: Alarm Page>System Supervision Tab

Parameter High Comm CPU temperature (sets the alarm trigger value) High FPGA temperature (sets the alarm trigger value) Field devices comm. Error

Suggested Value or Source of Data Default= 75 deg C; (usual operating range -40 to 70 deg C) Default= 75 deg C; (usual operating range -40 to 70 deg C) Number of continuous failed comms attempts before triggering alarm. Default=50 Number of continuous failed comms attempts before attempting to recover the inter CPU communication. If unsuccessful the alarm will be triggered. Default=100 Number of continuous failed comms attempts with bushing data before triggering alarm. Default=50. Number of continuous failed comms attempts with PD data before triggering alarm. Default=250

Inter CPU comm. error

Rejected phase packet

Rejected PD packet

Page 25

Intellix BMT 300 User Manual

Parameter Low bushing current warning

Suggested Value or Source of Data Default 30%. Current % drop from expected current before this service alarm is triggered. Default value 90 deg C. Alarm threshold for top oil temperature. Percentage change in nominal frequency which triggers an alarm, default=2% Number of continuous errors in the internal RS485 line which triggers an alarm, default=50 Default = 10%. The percentage of Iref below which this alarm is triggered. The percentage increase in bushing adapter sampling current from one sampling period to the next that triggers an alarm. An increase in current is indicative of a failure in one of the resistors, either in the bushing adapter or the BMT 300 motherboard input. Default = 10%, to be set according the expected current and the inputs load.
Table 4: System Supervision Alarm Settings

High top oil temperature Power system frequency warning

Modbus comm. error No Signal Warning

Bushing R Failure Warning

Once all the settings have been entered, press the Write button to load the settings into the Intellix BMT 300. It is advisable to update the configuration file by pressing the Save Settings To File button.

Page 26

Intellix BMT 300 User Manual

Partial Discharge

Figure 11: Alarm Page> Partial Discharge Tab

Suggested Value or Source of Data2 Parameter Default Period to calculate PD trend High noise level high PD max level warning PD max level alarm PD average warning PD average level alarm PD average trend warning 24 h 0 (disabled) 8000 pC 12000 pC 1000 pC 2000 pC 0 (disabled) Allowable range3 0 to 720 Not in use 0 to 65000 0 to 65000 0 to 65000 0 to 65000 0 to 65000

Alarm limits and settings must be revised a few weeks after installation by customer depending on bushing behaviour. 3 Value of zero disables this particular alarm.

Page 27

Intellix BMT 300 User Manual

Suggested Value or Source of Data2 Parameter Default PD average trend alarm PD count average warning PD count average alarm PD count trend warning PD count trend alarm PDI level warning PDI level alarm PDI trend warning PDI trend alarm 0 (disabled) 0 (disabled) 0 (disabled) 0 (disabled) 0 (disabled) 1000 mW 2000 mW 0 (disabled) 0 (disabled)
Table 5: Partial Discharge Alarm Settings

Allowable range3 0 to 65000 0 to 65000 0 to 65000 0 to 65000 0 to 65000 0 to 65000 0 to 65000 0 to 65000 0 to 65000

Page 28

Intellix BMT 300 User Manual

Bushing Insulation

Figure 12: Alarm Page > Bushing Insulation Tab

Enter settings for Primary bushings:


Suggested Value for both Primary & Secondary4 Parameter Default Period to calculate PF% trend Period to calculate C1% trend Phase A C1% level warning Phase A C1% level alarm Phase A C1 trend warning Phase A C1 trend alarm 168h 168h 5% 10% 0 (disabled) 0 (disabled) Allowable range5 0 to 720 h 0 to 720 h 0 to 100 % 0 to 100 % 0 to 100 %/day 0 to 100 %/day

Alarm limits and settings must be revised few weeks after installation by customer depending on bushing behaviour. 5 Value of zero disables this particular alarm.

Page 29

Intellix BMT 300 User Manual

Suggested Value for both Primary & Secondary4 Parameter Default PF% level warning PF% level alarm Phase B C1% level warning Phase B C1% level alarm Phase B C1 trend warning Phase B C1 trend alarm PF% trend warning PF% trend alarm Phase C C1% level warning Phase C C1% level alarm Phase C C1% trend warning Phase C C1% trend alarm 150% 200% 5% 10% 0 (disabled) 0 (disabled) 0 (disabled) 0 (disabled) 5% 10% 0 (disabled) 0 (disabled)
Table 6: Bushing Insulation Alarm Settings

Allowable range5 0 to 600% 0 to 600% 0 to 100 % 0 to 100 % 0 to 100%/day 0 to 100%/day 0 to 600%/day 0 to 600%/day 0 to 100 % 0 to 100 % 0 to 100 %/day 0 to 100 %/day

After entering settings for Primary bushings, repeat procedure and enter settings for Secondary bushings if applicable. Write the alarm settings to the Intellix BMT 300 by pressing the Write button. It is advisable to update the configuration file by pressing the Save Settings To File button.

Page 30

Intellix BMT 300 User Manual

Alarm Statuses

Figure 13: Alarm Statuses Tab

The Alarm Statuses tab indicates the current status of all alarms. The individual alarms can be selected in normal Windows manner (CTRL+ click for multiple selections). The actions are: Read Status refreshes the alarm status screen. Acknowledge Acknowledges the selected alarms, but leaves them at their current status as given by the alarm trigger state (see Alarm Settings) Reset Acknowledges the alarm and resets it to un tripped (Service user only)

Page 31

Intellix BMT 300 User Manual

Relay Control

Figure 14: Alarm Statuses Tab

The Relay Control tab provides the means to control the BMT300 relays. On operational mode the Active relay on alarm is enabled. Thus the relays reflect the alarm statuses: Relay 1 (Service) is energized by default. If a service alarm is on or BMT300 loses power it will switch to off. Relay 2 (Warning) and Relay 3 (Alarm) is de-energized by default. If either of their respective alarms is on, the corresponding relay will switch to on.

Relays can be manually controlled by disabling the Active relay on alarm. Then the relays are not synchronized with the alarm statuses; and the user can manually switch the relays (by clicking on the relay switch icon and then click on write).

Page 32

Intellix BMT 300 User Manual

Measurement
The Measurement page displays the instantaneous measurements taken by the BMT 300, plus CANBUS and GPS values.

Figure 15: Measurement Page

Note: The expected phase angles for AB and AC are calculated and presented in the Bushing Current Settings page, and will be around 120 and -120 respectively. The PD Max displayed on this page is the maximum PD value for the cycle. The log file PD Max is the maximum value of the PD averaged over each cycle in the logging period. The Bushing Current fields are colour coded: Their background is red if there is no signal; yellow if beyond the threshold set in the Bushing Current settings page, see description at page 21. The Start button starts polling the instantaneous results. The label of the button then changes to Stop. Pressing the Stop button will cease polling. The Clear Error button resets the error counters in the Field Sensors error box.

Page 33

Intellix BMT 300 User Manual

Logging Page
The Logging Page has 2 tabs: Log Settings, go to page 34. Log Data, go to page 35. SD Card, go to page 36.

Log Settings

Figure 16: Logging Page> Log Settings

Parameter Log Enable Log Interval

Suggested Value or Source of Data Checked/Enabled The period between log recordings. The average values are calculated for the logging period. Default is 1 hour

Page 34

Intellix BMT 300 User Manual

Parameter Log Timing

Suggested Value or Source of Data Choose CPU or GPS (if fitted) as timing stamp source. If CPU, the time can be synchronised with the PC by pressing the Sync Time button in General Information>Device Information, see page 18. Default=GPS

Log Size Max

Limits the maximum file size in the SD card where both the measurements and status events are logged Default is 2048Kb
Table 7: Log Settings Tab

Commit these entries to the Intellix BMT 300 by pressing the Write button. It is advisable to update the configuration file by pressing the Save Settings To File button. Move on to the Log Data Tab

Log Data

Figure 17: Logging Page> Log Data

Log File: enter or browse to a location to store log files.

Page 35

Intellix BMT 300 User Manual

Log Type: Select from the drop down whether you require a measurement or status log file. The file grid is populated with the chosen file type when the Get Log List button is pressed. Download Log File will download the selected files in the file grid. The download behaviour can be modified by the check boxes below the file grid: o Append: If Append to current log file is checked, then the new log file data will be appended to the log file selected by the log file browser above. o Compress: If Compress log data is checked, then the log file on the Intellix BMT 300 is compressed prior to download. o Delete: If Delete log file after download is checked, no copy is left on the Intellix BMT 300. o Log Compression: If Compress log data is checked, this field gives an indication of the estimated time for the compression to take place.

SD Card

Figure 18: Logging Page> SD Card

The drop down allows mounting (Enable) and unmounting (Disable) the SD card. It is recommended to unmount the SD card before switching off BMT300 to minimize the probability of data corruption.

Page 36

Intellix BMT 300 User Manual

APPENDIX 1: MANUAL INSTALLATION OF Intellix BMT 300 SETUP SOFTWARE


To manually install the Intellix BMT 300 setup software package on your laptop, carry out the following actions, in the order presented: Install the LabViewRunEngine suite: o Open the Intellix BMT 300 Prereqisities directory, o Open the LabViewRunEngine directory. o Double click on the setup.exe. o After the installation decline the PC restart, opt for restart later. Install the Visa suite: o Open the Intellix BMT 300 Prereqisities directory, o Open the Volume directory. o Double click on the setup.exe. o After the installation decline the PC restart, opt for restart later. Install the USB to Serial driver: o Open the Intellix BMT 300 Prereqisities directory, o Open the USB to 232 directory. o Double click on the PL2303_Prolific_DriverInstaller.exe. After the installation: restart your PC to register all of the installed software. Copy the Intellix BMT 300 software directory to a suitable location. o Open the Intellix BMT 300 directory. o SelectBMT_300.exe. o Right click>create shortcut. o Move the shortcut to your desktop.

Page 37

Intellix BMT 300 User Manual

APPENDIX 2 BUSHING ADAPTER CIRCUIT INTEGRITY TEST RECORD


The Bushing Adapter Circuit Integrity Test is to be carried out upon installation, and any time that the Bushings or Bushing Adapters are disturbed. The test procedure is: Ensure that the Transformer is switched off. The safety switches for the sensor cables in the cabinet are to be set to closed. Disconnect ALL of the coaxial cables at the plugs shown in Figure 19.

Figure 19: Disconnection of Interconnecting Co-ax

For each phase connection, in turn: 1. Record Maker Plate information: PF%, C1, C2 and T. Confirm that the measured bushings capacitance (Cb) is within 10% of the nominal C2. 2. Test the capacitance between the cable core and shield. This should be the sum of the measured bushing adaptors capacitance and the measured bushings capacitance (Cb). 3. Test the continuity between the sensor cable shield and ground at the cabinet, as shown in Figure 20 . It should be less than 5 Ohm. 4. Test the resistance between the sensor cable core and the shield, as shown in Figure 21. It must be within 5% of the nominal value of the bushing adapter (2xR in parallel; if R=1k then the measured R must be 500 5%. Note this as [R1].

Figure 20: Continuity Check (1)

Figure 21: Continuity Check (2)

Page 38

Intellix BMT 300 User Manual

5. Measure the resistance across the screws of the terminals (ie the input resistance of the PCB circuits, as shown in Figure 22. Note this as [R2]. Reconnect the coax plug of the phase. 6. Re-test the resistance across the 2 screws. This is the measured value of [R3]. 7. Calculate the theoretical value of [R3] using: [Rc] = [R1]x[R2]/([R1]+[R2]) Rc must be within 5% of the measured value of [R3] in step 6.
Figure 22: Measuring Motherboard Input Resistance

Note all of the above test values in a copy of this sheet. Repeat for the remaining phases. Store a completed copy of this record with the transformer maintenance documents.

8. Once the transformer is energized and whilst the Isolation/ grounding block is on the operational position, measure the voltage drop across the core and the shield at the block terminals of the co-axial cables connected to the bushing adaptors and record the values. The measured values voltages must be within the 0.61.5Vrms. This doesnt apply to the CT co-axial input.

Page 39

Intellix BMT 300 User Manual

RESULTS TABLE
Date: ____________ Secondary A Secondary C Secondary B Primary A Primary C Primary B

Ser No:

Ser No:

Ser No:

Ser No:

Ser No:

STEP 1a:

Markers Plate Power Factor % [PF%] Makers Plate Capacitance [C1] Markers Plate Capacitance [C2] Temperature at which nominal values were measured [T] Bushing Adapters Capacitance [Cadaptor] Measured Bushings Capacitance [Cb] Capacitance between cable core & shield (Cadaptor+Cb) Shield to ground resistance (<5 Ohm) Cable core to shield resistance [R1] PCB input resistance [R2]

STEP 1b:

STEP 1c:

STEP 1d

STEP 2a:

STEP 2b:

STEP 2c:

STEP 3:

STEP 4:

STEP 5:

STEP 6:

Measured resistance after reconnection [R3] Calculated value [Rc]=[R1]x[R2]/([R1]+[R2]) Voltage drop across co-axial input

STEP 7:

STEP 8

Page 40

Ser No:

Intellix BMT 300 User Manual

APPENDIX 3 FRONT PANEL LIGHTS


Light Colour GREEN Light Symbol Meaning

AC power applied

BLUE

Service Required. Triggered by one of: Low Bushing current warning Power system frequency warning No signal warning Bushing Sensor Resistance failure warning

YELLOW

A measured parameter has exceeded a userprogrammed Hi alarm threshold.

RED

A measured parameter has exceeded a userprogrammed Hi-Hi alarm threshold.