You are on page 1of 7

PROJECT .

A 1 CHILLER ROOM Transmision load Q Wall QRoof Q Floor Q Door Total Safety ( 20 %) Total Q Transmission Product Load Mass product Cp DT Q product Infiltration Door Infiltration / unit 2 Total Lingting Q Lighting Person number of Person 6 Q person Forklift Capasity 1800 Q forklift

DIMENSION 50.000 x 36.000x 14.000 17.33 12.96 13.9 0.018 44.2080 8.8416 53.0496 kW kW kW kW kW kW kW

No

Summary Load Calculation 1 Q Transmission Q product Q Infiltration Q Lingting Q Person Q Forklift Subtotal Safety ( 10 %) Total Load

Load ( kW) 53.0496 17.3 33.06 19.44 0.4125 0.03125 123.2820 12.33 135.61

86117.0 kg 3.2 kJ / kg K 5.0 17.3 kW

SELECETION COMPRESSOR Total Load Design room temp Evaporating temp Condensing temp Refrigerant

135.61 0 degC - 5deg C 40 degC R-22

16.53 Kw 33.06 Kw 19.44 Kw working hour / day temp / kW 6 275 0.4125 kW

Type Compressor KC2 / KCX2

Qe kW 161, 3 kW

warking hours 6 0.03125 kW

PROJECT .A 2 CHILLER ROOM Transmision load Q Wall QRoof Q Floor Q Door Total Safety ( 20 %) Total Q Transmission Product Load Mass product Cp DT Q product Infiltration Door Infiltration / unit 2 Total Lingting Q Lighting Person number of Person 6 Q person Forklift Capasity 1800 Q forklift

DIMENSION 50.000 x 36.000x 14.000 17.33 12.96 13.9 0.018 44.2080 8.8416 53.0496 kW kW kW kW kW kW kW

No

Summary Load Calculation 1 Q Transmission Q product Q Infiltration Q Lingting Q Person Q Forklift Subtotal Safety ( 10 %) Total Load

Load ( kW) 53.0496 17.3 33.06 19.44 0.4125 0.03125 123.2820 12.33 135.61

86117.0 kg 3.2 kJ / kg K 5.0 17.3 kW

SELECETION COMPRESSOR Total Load Design room temp Evaporating temp Condensing temp Refrigerant

135.61 0 degC - 5deg C 40 degC R-22

16.53 Kw 33.06 Kw 19.44 Kw working hour / day temp / kW 6 275 0.4125 kW

Type Compressor KC2 / KCX2

Qo kW 161, 3 kW

warking hours 6 0.03125 kW

PROJECT .A 3 CHILLER ROOM Transmision load Q Wall QRoof Q Floor Q Door Total Safety ( 20 %) Total Q Transmission Product Load Mass product Cp DT Q product Infiltration Door Infiltration / unit 1 Total Lingting

DIMENSION 72.000 x 18.000x 14.000 16.84 6.02 4.19 0.018 27.0680 5.4136 32.4816 kW kW kW kW kW kW kW

No

Summary Load Calculation 1 Q Transmission Q product Q Infiltration Q Lingting Q Person Q Forklift Subtotal Safety ( 10 %) Total Load

Load ( kW) 32.4816 7.9 16.53 19.44 0.4125 0.03125 76.7789 7.68 84.46

39269.0 kg 3.2 kJ / kg K 5.0 7.9 kW

SELECETION COMPRESSOR Total Load Design room temp Evaporating temp Condensing temp Refrigerant

84.46 0 degC - 15 deg C 40 degC R-22

16.53 Kw 16.53 Kw Kw temp / kW 275 kW

Type Compressor KC2 / KCX2

Qo kW 104, 19 kW

Q Lighting 19.44 Person number of Person working hour / day 6 6 Q person 0.4125 Forklift Capasity warking hours 1800 6 Q forklift 0.03125

kW

PROJECT .A 4 CHILLER ROOM Transmision load Q Wall QRoof Q Floor Q Door Total Safety ( 20 %) Total Q Transmission Product Load Mass product Cp DT Q product Infiltration Door Infiltration / unit 2 Total Lingting

DIMENSION 55.000 x 18.000x 14.000 14.7 7.1 7.67 0.018 29.4880 5.8976 35.3856 kW kW kW kW kW kW kW

No

Summary Load Calculation 1 Q Transmission Q product Q Infiltration Q Lingting Q Person Q Forklift Subtotal Safety ( 10 %) Total Load

Load ( kW) 35.3856 9.5 33.06 19.44 0.4125 0.03125 97.8380 9.78 107.62

47364.0 kg 3.2 kJ / kg K 5.0 9.5 kW

SELECETION COMPRESSOR Total Load Design room temp Evaporating temp Condensing temp Refrigerant

107.62 0 degC - 10deg C 40 degC R-22

16.53 Kw 33.06 Kw Kw temp / kW 275 kW

Type Compressor KC2 / KCX2

Qo kW 130, 81 kW

Q Lighting 19.44 Person number of Person working hour / day 6 6 Q person 0.4125 Forklift Capasity warking hours 1800 6 Q forklift 0.03125

kW

NOTE : CAPASITY CHILLER ROOM 4 = CHILLER ROOM ( 5, 6,7,8)

PROJECT .A 9 CHILLER ROOM Transmision load Q Wall QRoof Q Floor Q Door Total Safety ( 20 %) Total Q Transmission Product Load Mass product Cp DT Q product Infiltration Door Infiltration / unit 2 Total Lingting

DIMENSION 60.000 x 18.000x 14.000 15.72 7.77 8.32 0.018 31.8280 6.3656 38.1936 kW kW kW kW kW kW kW

No

Summary Load Calculation 1 Q Transmission Q product Q Infiltration Q Lingting Q Person Q Forklift Subtotal Safety ( 10 %) Total Load

Load ( kW) 38.1936 10.4 33.06 19.44 0.4125 0.03125 101.5105 10.15 111.66

51670.0 kg 3.2 kJ / kg K 5.0 10.4 kW

SELECETION COMPRESSOR Total Load Design room temp Evaporating temp Condensing temp Refrigerant

111.66 0 degC - 10deg C 40 degC R-22

16.53 Kw 33.06 Kw Kw temp / kW 275 kW

Type Compressor KC2 / KCX2

Qo kW 130, 81 kW

Q Lighting 19.44 Person number of Person working hour / day 6 6 Q person 0.4125 Forklift Capasity warking hours 1800 6 Q forklift 0.03125

kW

PROJECT .B 1 CHILLER ROOM Transmision load Q Wall QRoof Q Floor Q Door Total Safety ( 20 %) Total Q Transmission Product Load Mass product Cp DT Q product Infiltration Door Infiltration / unit 2 Total Lingting

DIMENSION 44.000 x 36.000x 12.000 13.939 20.9 21.8 0.018 56.6570 11.3314 67.9884 kW kW kW kW kW kW kW

No

Summary Load Calculation 1 Q Transmission Q product Q Infiltration Q Lingting Q Person Q Forklift Subtotal Safety ( 10 %) Total Load

Load ( kW) 67.9884 40.2 33.06 19.44 0.4125 0.03125 161.0837 16.11 177.19

100000.0 kg 3.2 kJ / kg K 10.0 40.2 kW

SELECETION COMPRESSOR Total Load Design room temp Evaporating temp Condensing temp Refrigerant

177.19 - 25deg C - 25deg C 40 degC R-22

16.53 Kw 33.06 Kw Kw temp / kW 275 kW

Type Compressor KC 42

Qo kW 191, 9 kW

Q Lighting 19.44 Person number of Person working hour / day 6 6 Q person 0.4125 Forklift Capasity warking hours 1800 6 Q forklift 0.03125

kW

NOTE : CAPASITY COLD STORAGE ROOM 1 =COLD STORAGE ROOM ( 2, 3, 4)

PROJECT .B 5 CHILLER ROOM Transmision load Q Wall QRoof Q Floor Q Door Total Safety ( 20 %) Total Q Transmission Product Load Mass product Cp DT Q product Infiltration Door Infiltration / unit 1 Total Lingting

DIMENSION 70,300 x 12.000x 12.000 17.3 5.06 6.5 0.018 28.8780 5.7756 34.6536 kW kW kW kW kW kW kW

No

Summary Load Calculation 1 Q Transmission Q product Q Infiltration Q Lingting Q Person Q Forklift Subtotal Safety ( 10 %) Total Load

Load ( kW) 34.6536 10.0 16.53 19.44 0.4125 0.03125 81.1052 8.11 89.22

50000.0 kg 3.2 kJ / kg K 5.0 10.0 kW

SELECETION COMPRESSOR Total Load Design room temp Evaporating temp Condensing temp Refrigerant

89.22 0 degC - 10deg C 40 degC R-22

16.53 Kw 16.53 Kw Kw temp / kW 275 kW

Type Compressor KC2 / KCX2

Qo kW 130, 81 kW

Q Lighting 19.44 Person number of Person working hour / day 6 6 Q person 0.4125 Forklift Capasity warking hours 1800 6 Q forklift 0.03125

kW

You might also like