CIBSE Buildi ng Cooling L oad

************ ************ ***

Name      : A Student
Job       : Example 3.2  
Job ref   : Offices phas e 3
Date      : 26­Mar­08   
Time      : 12:00:00 AM 
 
File      : A:HGAINQ.WKS

Walls are ta ken as    : light colour ed


Flat roof ta ken as    : dark coloure d

New data is entered unde r column hea dings underl ined with ========.


All data is calculated w hen columns are headed w ith ********.

Cooling load  due to sola r gain throu gh glazing, W/m2


­­­­­­­­­­­­ ­­­­­­­­­­­­ ­­­­­­­­­­­­ ­­­­­­­­­­­­ ­­­­

CIBSE Table A9.15, 51.7o N latitude, intermittent  use of in ternal blind

Date Orientation Sun Time, h


       1000        1200      1600
       W/m2        W/m2      W/m2
21 June   N 114  138  111 
  NE 81  151  124 
  E 254  88  125 
  SE 282  207  110 
  S 179  238  89 
  SW 105  183  261 
  W 114  139  314 
  NW 115  140  204 

Cooling load  due to sola r gain throu gh glazing, W/m2


­­­­­­­­­­­­ ­­­­­­­­­­­­ ­­­­­­­­­­­­ ­­­­­­­­­­­­ ­­­­

CIBSE Table A9.15, 51.7o N latitude, intermittent  use of in ternal blind

Date Orientation Sun Time, h


       1000        1200      1600
       W/m2        W/m2      W/m2
22 September   N 76  104  73 
  NE 89  105  74 
  E 220  52  75 
  SE 330  262  74 
  S 262  333  137 
  SW 78  237  274 
  W 75  103  258 
  NW 75  103  156 

Correction F actors to Gl azing Coolin g Load


­­­­­­­­­­­­ ­­­­­­­­­­­­ ­­­­­­­­­­­­ ­­­­­­

CIBSE Table A9.15, light weight build ing.

Closed, ligh t slatted bl inds.

Glass Type Single Glazi ng Double Gla zing


========== ============ == ========== ====
clear 6 mm 0.77  0.74 

tinted 6 mm 0.77  0.55 

tinted 10 mm 0.73  0.47 

reflecting 0.57  0.41 

mirrored 0.34  0.21 

Window Therm al Transmitt ance U W/m2 K


­­­­­­­­­­­­ ­­­­­­­­­­­­ ­­­­­­­­­­­­ ­
CIBSE Table A3.14  *
User data       **
Aluminium fr ame with the rmal break.
Frame occupi es 10% of op ening.

Glass Type Single Glazi ng Double Gla zing


========== ============ == ========== ====
clear 6 mm 5.70  3.30   *

tinted 6 mm 5.70  3.30   **

tinted 10 mm 5.70  3.30   **

reflecting 5.70  3.30   **

mirrored 5.70  3.30   **

Wall Thermal  Data
­­­­­­­­­­­­ ­­­­­
CIBSE Table A3.17
  Thermal   Admittance
No.   Type   U W/m2 K   Y W/m2 K
===   ====== ============ ============ ====   ========   ==========
1     105 mm  brick, 10 m m cavity, 40 mm batts,
      100 mm  lightweight  concrete bl ock,
      13 mm lightweight plaster 0.45  2.40 

2     200 mm  heavyweight  block, 25 m m cavity,


      10 mm foil backed plasterboard 1.50  1.90 

3     220 mm  brick, 25 mmm cavity,
      10 mm foil backed plasterboard 1.20  1.80 

4     10 mm tiles, paper , 25 mm cavi ty,


      100 mm  batts, 10 m m plasterboa rd 0.33  0.66 

Roof Thermal  Data
­­­­­­­­­­­­ ­­­­­
CIBSE Table A3.18 and A3 .19
  Thermal   Admittance
No.   Type   U W/m2 K   Y W/m2 K
===   ====== ============ ============ ====   ========   ==========
5     corrug ated asbesto s or steel s heet 6.50  6.50 

6     corrug ated asbesto s or steel s heet,


      cavity , 100 mm bat ts, 10 mm pl asterboard 0.35  0.67 

7     10 mm tile, paper,  cavity, 100  mm batts,


      10 mm plasterboard 0.35  0.67 

8     19 mm asphalt, 75 mm screed, 1 50 mm cast


      concre te, 13 mm pl aster 1.90  5.70 

9     19 mm asphalt, 13 mm particle board,


      cavity , 75 mm batt s, 10 mm pla sterboard 0.40  0.70 

Partition Th ermal Data CIBSE Table A3.20 and A3.21


­­­­­­­­­­­­ ­­­­­­­­­­
  Thermal   Admittance
No.   Type   U W/m2 K   Y W/m2 K
===   ====== ============ ============ ====   ========   ==========
10    105 mm  brickwork, 13 mm plaste red 1.80  3.60 

11    100 mm  lightweight  concrete bl ock,


      13 mm plastered 1.10  2.30 

12    25 mm plasterboard , cavity,


      25 mm plasterboard 1.40  1.10 

13    25 mm wood block f loor, 50 mm screed,


      150 mm  cast concre te:     (a) Floor 1.50  2.90 
        (b) Ceiling 1.50  6.00 
14    10 mm timber floor , cavity, 25  mm batts,
      16 mm plasterboard  ceiling:(a)  Floor 0.81  0.63 
         (b)  Ceiling 0.81  0.88 
Outside Temp eratures, Te o, Tao oC
­­­­­­­­­­­­ ­­­­­­­­­­­­ ­­­­­­­­­
Time lags, w alls 9 h, ro of 1 h.
       SOL­A IR TEMPERATU RE  Teo oC
Date Orientation Sun Time, h
       0100        0300      0700    24 h Teo
21 June   N 11.5  10.5  14.5  18.00 
  NE 11.5  10.5  24.5  19.50 
  E 11.5  10.5  28.0  20.50 
  SE 11.5  10.5  23.5  20.50 
  S 11.5  10.5  14.0  20.00 
  SW 11.5  10.5  14.0  20.50 
  W 11.5  10.5  14.0  20.50 
  NW 11.5  10.5  14.0  19.50 

       0900        1100      1500    24 h Teo


Horizontal r oof Teo oC 38.0  48.0  44.5  26.00 

       1000        1200      1600    24 h Tao


Outside Air     Tao oC 16.5  19.0  22.0  16.50 
Outside Temp eratures, Te o, Tao oC
­­­­­­­­­­­­ ­­­­­­­­­­­­ ­­­­­­­­­
Time lags, w alls 9 h, ro of 1 h.
       SOL­A IR TEMPERATU RE  Teo oC
Date Orientation Sun Time, h
       0100        0300      0700    24 h Teo
22 September   N 12.0  10.5  12.0  16.00 
  NE 12.0  10.5  16.5  16.50 
  E 12.0  10.5  20.5  18.00 
  SE 12.0  10.5  19.5  19.50 
  S 12.0  10.5  14.0  20.50 
  SW 12.0  10.5  12.0  19.50 
  W 12.0  10.5  12.0  18.00 
  NW 12.0  10.5  12.0  16.50 

       0900        1100      1500    24 h Teo


Horizontal r oof Teo oC 27.5  38.0  33.0  20.00 

       1000        1200      1600    24 h Tao


Outside Air     Tao oC 15.5  18.5  20.0  15.50 
ROOM DESIGN DATA
­­­­­­­­­­­­ ­­­­
ROOM 1   Input Data   Calculated
­­­­­­ ==========   ******** **
Site locatio n       : Portsmouth
Altitude         : 10  m
Locality         : city centre
Name         : Office 1
Floor              : top
Activity         : office work
Room air tem p   Tai : 22.0  oC d.b.
Resultant te mp  Tc  : 21.0  oC
Outdoor air te
    Tao : 30.0  oC
Infiltration       N : 0.25  air change/h
Outside air      Qo : 10.0  litre/s per person
Outside air      Qo : 1.3  litre/s per m2 floor

ROOM DESIGN DATA
­­­­­­­­­­­­ ­­­­
ROOM 1   Input Data   Calculated
­­­­­­ ==========   ******** **

Exposure            = normal

Number of oc cupants    = 4 
Occupant hea t emission = 90  Watt Sensibl e
Occupant hea t emission = 50  Watt Latent
Lighting            = 0  W/m2 floor
Electrical e quipment   = 400  Watt
Air conditio ning plant = 10  hours

Calculation Date       = 22 September

Outside air for people = 40.0  litre/s


Outside air for floor  = 32.5  litre/s
Design Outsi de air  Qo = 40.0  litre/s

Room Surface  & Volume Da ta
­­­­­­­­­­­­ ­­­­­­­­­­­­ ­­
Office 1   Input Data   Calculated
­­­­­­­­­­­­ ==========   ******** **
Room area &  volume calcu lation:
Area 1  : length  m  = 5.00 
  width   m  = 5.00   
height  m  = 3.00 
volume     = 75.00  m3
floor area = 25.00  m2
Area 2  : length   m = 0.00 
  width   m  = 0.00   
height  m  = 0.00 
volume     = 0.00  m3
floor area = 0.00  m2

Total room v olume   V  = 75.00  m3


Total floor area    Af = 25.00  m2
Window & Doo r Data
­­­­­­­­­­­­ ­­­­­­

Input Data
==========
Window          U = 3.30  W/m2 K
Door          U = 3.30  W/m2 K
Rooflight          U = 0.00  W/m2 K

Solar Gain D ata
============ ===
Wall 1: Input Data Calculated
­­­­­­­ ========== **********
Date           : 22 September
Orientation           : S
Thermal Tran smittance    U      : 0.45  W/m2 K
Admittance    Y      : 2.40  W/m2 K
Solar gain t hrough windo w         : 333  W/m2
Window solar  transmissio n factor  : 0.74 
Peak window solar gain t ime       : 12  hours
Wall time la g           : 9  hours
Time of heat  gain to wal l         : 3 
Wall decreme nt factor           : 0.42 
Mean 24 hour  Teo           : 25.0  oC
Teo at     : 3.00  hours     : 10.5  oC
Swing in Teo  from 24 h m ean       : ­14.5 
Mean 24 hour  Tao           : 15.5  oC
Tao at     : 12.00  hours     : 18.5  oC
Swing in Tao  from 24 h m ean       : 3.0 
Solar Gain D ata
============ ===
Wall 2 Input Data Calculated
­­­­­­­ ========== **********
Date           : 22 September
Orientation           : E
Thermal Tran smittance    U      : 0.00  W/m2 K
Admittance    Y      : 2.30  W/m2 K
Solar gain t hrough windo w         : 260  W/m2
Window solar  transmissio n factor  : 0.74 
Peak window solar gain t ime       : 9  hours
Wall time la g           : 9  hours
Time of heat  gain to wal l         : 0 
Wall decreme nt factor           : 0.42 
Mean 24 hour  Teo           : 20.5  oC
Teo at     : 0.00  hours     : 13.0  oC
Swing in Teo  from 24 h m ean       : ­7.5 
Mean 24 hour  Tao           : 15.5  oC
Tao at     :: 9.00  hours     : 14.0  oC
Swing in Tao  from 24 h m ean       : ­1.5 
Solar Gain D ata
============ ===
Wall 3 Input Data Calculated
­­­­­­­ ========== **********
Date           : 22 September
Orientation           : W
Thermal Tran smittance    U      : 0.00  W/m2 K
Admittance    Y      : 2.30  W/m2 K
Solar gain t hrough windo w         : 258  W/m2
Window solar  transmissio n factor  : 0.74 
Peak window solar gain t ime       : 16  hours
Wall time la g           : 9  hours
Time of heat  gain to wal l         : 7 
Wall decreme nt factor           : 0.42 
Mean 24 hour  Teo           : 20.5  oC
Teo at     : 7.00  hours     : 13.0  oC
Swing in Teo  from 24 h m ean       : ­7.5 
Mean 24 hour  Tao           : 15.5  oC
Tao at    : 16.00  hours     : 20.0  oC
Swing in Tao  from 24 h m ean       : 4.5 
Solar Gain D ata
============ ===
Wall 4 Input Data Calculated
­­­­­­­ ========== **********
Date           : 22 September
Orientation           : N
Thermal Tran smittance    U      : 0.00  W/m2 K
Admittance    Y      : 2.30  W/m2 K
Solar gain t hrough windo w         : 107  W/m2
Window solar  transmissio n factor  : 0.74 
Peak window solar gain t ime       : 13  hours
Wall time la g           : 9  hours
Time of heat  gain to wal l         : 4 
Wall decreme nt factor           : 0.42 
Mean 24 hour  Teo           : 17.0  oC
Teo at     : 4.00  hours     : 10.5  oC
Swing in Teo  from 24 h m ean       : ­6.5 
Mean 24 hour  Tao           : 15.5  oC
Tao at     : 13.00  hours     : 19.5  oC
Swing in Tao  from 24 h m ean       : 4.0 
Solar Gain D ata
============ ===
Horizontal R oof Input Data Calculated
­­­­­­­­­­­­ ­­­ ========== **********
Date           : 22 September
Orientation           :   horizontal
Thermal Tran smittance    U      : 0.40  W/m2 K
Admittance    Y      : 0.70  W/m2 K
Solar gain t hrough roofl ight      : 0  W/m2
Window solar  transmissio n factor  : 0.00  hours
Peak solar g ain time            : 12  hours
Roof time la g           : 1  hours
Time of heat  gain to wal l         : 11 
Roof decreme nt factor           : 0.70 
Mean 24 hour  Teo           : 20.0  oC
Teo at     : 11.00  hours     : 38.0  oC
Swing in Teo  from 24 h m ean       : 18.0 
Mean 24 hour  Tao           : 15.5  oC
Tao at     : 12.00  hours     : 18.5  oC
Swing in Tao  from 24 h m ean       : 3.0 
Heat Gain Da ta
============ ==
Internal Wal ls Input Data Calculated
­­­­­­­­­­­­ ­­ ========== **********
Date 22 September
Orientation           : internal
Thermal Tran smittance  U           : 1.1  W/m2 K
Admittance            Y           : 2.3  W/m2 K
Surface Fact or         F           : 0.88 
Time Lag          phi           : 1  hours
Temperature other side     Tc2   : 21.0  oC

Surface Orientation Cooling W/m2   Correction    length m   height m


******* *********** ************   **********    ========   ========
wall 1 S 0  0.00  5.00  3.00 
window 1 S 333  0.74  3.00  2.00 
window 2 S 333  0.74  0.00  0.00 
door 1 S 333  0.74  0.00  0.00 
     Nett wall area  =

wall 2 E 0  0.00  5.00  3.00 


window 3 E 260  0.74  0.00  0.00 
window 4 E 260  0.74  0.00  0.00 
door 2 E 260  0.74  0.00  0.00 
     Nett wall area  =
Surface Orientation Cooling W/m2   Correction    length m   height m
******* *********** ************   **********    ========   ========

wall 3 W 0  0.00  5.00  3.00 


window 5 W 258  0.74  0.00  0.00 
window 6 W 258  0.74  0.00  0.00 
door 3 W 258  0.74  0.00  0.00 
     Nett wall area  =

wall 4 N 0  0.00  5.00  3.00 


window 7 N 107  0.74  0.00  0.00 
window 8 N 107  0.74  0.00  0.00 
door 4 N 107  0.74  0.00  0.00 
     Nett wall area  =

Surface Orientation Cooling W/m2   Correction    length m   width m


******* =========== ============   ==========    ========   ========

floor 1 internal 0  0.00  5.00  5.00 


floor 2 0  0  0.00  0.00  0.00 
ceiling 1 0  0  0.00  0.00  0.00 
ceiling 2 0  0  0.00  0.00  0.00 
roof 1 flat 0  0.00  5.00  5.00 
roof 2 0  0  0.00  0.00  0.00 

Output Data    Results
***********    *******
Summation of  room surfac e areas  A = 110.000  m2
Check surfac e area         A2 = 110.000  m2
Error in are as         A3 = 0.000  m2
Summation of    (A x U) = 33.85  W/K
Summation of    (A x Y) = 234.90  W/K
Infiltration  rate          Q = 0.0052  m3/s
Factor         Fv = 0.9907  dimensionles
s
Factor         Fu = 0.9832 
factor         Fy = 0.8939 
factor         F2 = 1.0504 
Fu/Fv Fu/Fv      = 0.9924 
Fy/Fv Fy/Fv      = 0.9023 
(AxU)/(A) (AxU)/(A)  = 0.31  W/m2 K
(NxV)/3xA) (NxV/3xA)  = 0.06  m/h
 

Heat Gain Ou tput Data
************ *********

Solar gain t hrough windo ws    Qs  = 1479  W

Occupancy se nsible heat       Qo  = 360  W

Lighting hea t gain       Ql  = 0  W

Equipment he at gain       Qe  = 400  W

24 hour mean  conduction gain  Qu  = ­102  W

Net swing in  conduction gain  Qu~ = 192  W

Infiltration  heat gain       Qv  = 58  W

************ ************ ************ ************ **********


** Sensible heat gain      Qps  = 2387  Watts   **
************ ************ ************ ************ **********

Occupancy la tent heat ga in    Qpl = 200  W

############ ############ ############ ############ ####


####   Qps = 2387  Watts    sensible ####
####   Qps = 2.387  kW sensible ####
####   Qps = 31.8  W/m3 sensible ####
####   Qps = 95.5  W/m2 sensible ####
####   Qpl = 200  W latent ####
####   Qpl = 0.200  kW latent ####
####   Qp  = 2.587  kW total ####
####   Qp  = 103.5  W/m2 total ####
############ ############ ############ ############ ####
BUILDING COO LING LOAD
============ =========  
Enter the se nsible and l atent heat g ains from th e file for
each room of  the whole b uilding.
Totals are a utomatically  calculated.

Spreadsheet file Sensible kW    Latent kW   Total kW


============ ===== ===========    =========   ********
A:HGAIN1.WKS 2.387  0.200  2.587 
A:HGAIN2.WKS 0.000  0.000  0.000 
A:HGAIN3.WKS 0.000  0.000  0.000 
A:HGAIN4.WKS 0.000  0.000  0.000 
A:HGAIN5.WKS 0.000  0.000  0.000 
A:HGAIN6.WKS 0.000  0.000  0.000 
A:HGAIN7.WKS 0.000  0.000  0.000 
A:HGAIN8.WKS 0.000  0.000  0.000 
A:HGAIN9.WKS 0.000  0.000  0.000 
A:HGAIN10.WK S 0.000  0.000  0.000 
A:HGAIN11.WK S 0.000  0.000  0.000 
A:HGAIN12.WK S 0.000  0.000  0.000 
Plant Load S ummary
­­­­­­­­­­­­ ­­­­­­ Input Data
==========
Heat Gains a re summed fo r the buildi ng.
Percentage t o be added f or duct heat  gain     = 5  %
Percentage t o be added f or plant mar gin       = 10  %
Surplus sens ible plant c apacity           = 0.000  kW
Surplus late nt plant cap acity           = 0  W

Sensible kW    Latent kW   Total kW


*********** *********** ********** **
Heat Gains = 2.387  0.200  2.587 
5  % gain     = 0.119  0.000  0.119 
10  % margin   = 0.239  0.000  0.239 
+ surplus  = 0.000  0.000  0.000 
*********** *********** ********** **
Total Qp   = 2.745  0.200  2.945  kW
*********** *********** ********** **

AIR HANDLING  REQUIREMENT
============ ============
Input Data Calculated
========== **********
Room name            : Office 1
Room air tem p.     Tai : 22.0  oC d.b.
Room volume        V   : 75.00  m3
Supply air t emp.   Ts  : 12.0  oC d.b.
Room sensibl e gain Qps : 2.745  kW
Air duct lea kage     L : 5  %
Supply air q uantity  Q : 0.234  m3/s
Supply air q uantity  Q : 234  litre/s
Room air cha nge rate N : 11.2  air change/h
Duct air vel ocity    V : 5.0  m/s
Duct diamete r        D : 244  mm
   

s.
  Decrement    Time Lag
  Factor f    phi h
  =========    =========

0.42  9 

0.33  7 

0.37  7 

0.99  1 

  Decrement    Time Lag
  Factor f    phi h
  =========    =========
1.00  0 

1.00  1 

1.00  1 

0.34  8 

0.99  1 

  Surface    Time Lag
  Factor F    omega h
  =========    =========
0.72  2 

0.88  1 

0.97  1 

0.70  1 
0.42  3 
1.00  0 
0.99  0 
hours

oC

oC
hours

oC

oC

hours

oC

oC

hours

oC

oC
hours

oC

oC

   gross m2     Teo oC     U W/m2K    (AxU) W/K     Y W/m2K    (AxY) W/K


   ********     ******     *******    *********     *******    *********
15.0         
6.0  15.5  3.30  19.80  3.30  19.8 
0.0  15.5  3.30  0.00  3.30  0.0 
0.0  15.5  3.30  0.00  3.30  0.0 
9.0  15.5  0.45  4.05  2.40  21.6 

15.0         
0.0  15.5  3.30  0.00  3.30  0.0 
0.0  15.5  3.30  0.00  3.30  0.0 
0.0  15.5  3.30  0.00  3.30  0.0 
15.0  13.0  0.00  0.00  2.30  34.5 
0.0 
   gross m2     Teo oC     U W/m2K    (AxU) W/K     Y W/m2K    (AxY) W/K
   ********     ******     *******    *********     *******    *********

15.0         
0.0  15.5  3.30  0.00  3.30  0.0 
0.0  15.5  3.30  0.00  3.30  0.0 
0.0  15.5  3.30  0.00  3.30  0.0 
15.0  13.0  0.00  0.00  2.30  34.5 

15.0         
0.0  15.5  3.30  0.00  3.30  0.0 
0.0  15.5  3.30  0.00  3.30  0.0 
0.0  15.5  3.30  0.00  3.30  0.0 
15.0  10.5  0.00  0.00  2.30  34.5 

   gross m2     Teo oC     U W/m2K    (AxU) W/K     Y W/m2K    (AxY) W/K


   ********     ======     =======    *********     =======    *********

25.0  21.0  0.00  0.00  2.90  72.5 


0.0  0.0  0.00  0.00  0.00  0.0 
0.0  0.0  0.00  0.00  0.00  0.0 
0.0  0.0  0.00  0.00  0.00  0.0 
25.0  20.0  0.40  10.00  0.70  17.5 
0.0  0.0  0.00  0.00  0.00  0.0 

 
 Decrement f       Lag h  24 h Teo oC  24 h Tao oC     Time h     Teo oC
 ***********       *****  ***********  ***********     ********     ******

1.00  0  0.0  15.5  12  18.5 


1.00  0  0.0  15.5  12  18.5 
1.00  0  0.0  15.5  12  18.5 
0.42  9  25.0  15.5  3  10.5 

1.00  0  0.0  15.5  9  14.0 


1.00  0  0.0  15.5  9  14.0 
1.00  0  0.0  15.5  9  14.0 
0.42  9  20.5  15.5  0  13.0 
 Decrement f       Lag h  24 h Teo oC  24 h Tao oC     Time h     Teo oC
 ***********       *****  ***********  ***********     ********     ******

1.00  0  0.0  15.5  16  20.0 


1.00  0  0.0  15.5  16  20.0 
1.00  0  0.0  15.5  16  20.0 
0.42  9  20.5  15.5  7  13.0 

1.00  0  0.0  15.5  13  19.5 


1.00  0  0.0  15.5  13  19.5 
1.00  0  0.0  15.5  13  19.5 
0.42  9  17.0  15.5  4  10.5 

 Decrement f       Lag h  24 h Teo oC  24 h Tao oC     Time h     Teo oC


 ===========       =====  ===========  ===========     ========     ======

0.70  1  21.0  21.0  3  21.0 


0.70  1  25.0  15.5  3  10.5 
0.99  1  25.0  15.5  3  10.5 
0.99  1  25.0  15.5  3  10.5 
0.99  1  20.0  15.5  1  38.0 
0.99  1  25.0  15.5  3  10.5 
Swing Teo oC      Qu W   Swing Qu W    Glazing s olar gain W
************      *******   **********    ********* ***********

3.0  ­108  54  1479 


3.0  0  0  0 
3.0  0  0 
­14.5  16  ­22 

­1.5  0  0  0 
­1.5  0  0  0 
­1.5  0  0 
­7.5  0  0 
Swing Teo oC      Qu W   Swing Qu W    Glazing s olar gain W
************      *******   **********    ********* ***********

4.5  0  0  0 
4.5  0  0  0 
4.5  0  0 
­7.5  0  0 

4.0  0  0  0 
4.0  0  0  0 
4.0  0  0 
­6.5  0  0 

Swing Teo oC      Qu W   Swing Qu W    Glazing s olar gain W


************      *******   **********    ********* ***********

0.0  0  0 
­14.5  0  0 
­14.5  0  0  0 
­14.5  0  0  0 
18.0  ­10  161  0 
­14.5  0  0  0 

Totals    = ­102  192  1479 