Professional Documents
Culture Documents
www.laticrete.com
India: +91.40.3041.3100
Latin America: +1.203.393.0010
Middle East: +971.7.244.6396
South East Asia: +65.6515.3028
DS–125.0–1109
©2009 LATICRETE International, Inc.
LATICRETE, LATAPOXY, SPECTRALOCK and the logo are Registered Trademarks of LATICRETE International, Inc.
Microban is a registered trademark of Microban Products Company.
Kevlar is a registered trademark of Dupont Products Company.
GREENGUARD Indoor Air Quality Certified® Product. 9
©2009 LATICRETE International, Inc. All rights reserved. No part of this publication (except for previously
published articles and industry references) may be reproduced or transmitted in any form or by any
means, electronic or mechanical, without the written permission of LATICRETE International, Inc.
The information and recommendations contained herein are based on the experience of the author
and LATICRETE International, Inc. While we believe the information presented in these documents to be
correct, LATICRETE International, Inc. and its employees assume no responsibility for its accuracy or for
the opinions expressed herein. The information contained in this publication should not be used or relied
upon for any specific application or project without competent examination by qualified professionals
and verification of its accuracy, suitability, and applicability. Users of information from this publication
assume all liability arising from such use.
Preface..................................................................................................................................................5
Section 1: Introduction
1.1 Steam Room Facts......................................................................................................................9
1.2 Tile Installations in Steam Rooms – Materials and Methods....................................................9
1.3 Summary . ................................................................................................................................13
Section 6: Appendix.............................................................................................................................
6.1 Steam Room Frequently Asked Questions............................................................................. 78
6.2 Resource Guide – Trade Organizations and Technical Resources......................................... 80
6.3 Glossary................................................................................................................................... 82
LATICRETE International, Inc., a world leader in the manufacturing of ceramic tile and stone
installation systems, has long recognized the need for a technical design manual to provide
guidelines and recommendations for the design, specification and installation of tile and
stone in steam room/steam shower applications. Improved technology in steam room
construction and equipment has made steam rooms and steam showers readily available
to anyone. In keeping with our position as an industry leader, LATICRETE International
is publishing this Tiled Steam Room and Steam Shower Technical Design Manual to
provide information and guidelines to architects, design professionals, construction
professionals, tile installation professionals, and the tile and stone distribution industry.
It is the goal of this manual to provide the necessary information to help ensure a proper
and long-lasting tile installation in a steam room or steam shower environment.
Steam generation units create a great deal of 1. The first design incorporates steel or wood
moisture; this moisture initially takes the form framing and a concrete, slab-on-grade
of water vapor (steam). This water vapor is sub-floor. The ceiling should be sloped
highly penetrative and any room not properly at least 2" minimum per foot (50 mm per
prepared may be exposed to damage caused 300 mm) to prevent water from dripping
by excessive moisture. Proper measures must on steam room occupants (per Tile Council
be taken to prevent moisture transgression of North America recommendations). The
into or through walls, ceiling and floor. floor should be pre-pitched (prior to the
installation of the shower pan liner) at the
These preventive measures include a properly
rate of 1/4" per foot (6 mm per 300 mm)
placed, suitable vapor barrier and/or an
to make sure that water flows toward the
acceptable waterproofing membrane.
drain. Keep in mind that a shower pan is
LATICRETE International, Inc. always
required in all steam room/steam shower
recommends using both a vapor barrier, placed
installations!
on the framing or on the concrete/concrete
masonry units prior to further construction,
and LATICRETE® Hydro Ban™ or LATICRETE
The installation begins with the proper choice must be installed onto the ceiling as well as
and placement of a two-part clamping-ring- the walls because steam can certainly escape
style drain with weepers as per ASME A112.6.3. through the ceiling. It is imperative that this
Place tile spacers or gravel around weep holes, vapor barrier be placed so that it laps into the
as detailed by the design professional, to shower pan liner! This way any moisture that
prevent mortar from clogging the weep holes comes in contact with the vapor barrier will
and should be installed by a qualified plumber drain into the shower pan and through the
in accord with International Residential Code weep holes of the drain.
(IRC) P2709.4. The pipes and drain should Next, install a 2" (50 mm) thick (minimum)
be properly supported to prevent problems wire-reinforced, mortar bed comprised of
in the future. A suitable primary shower pan LATICRETE 3701 Fortified Mortar Bed; or,
liner, complying with ASTM D 4068, D 4551 LATICRETE 226 Thick Bed Mortar gauged
or other International Code Council (ICC) with LATICRETE 3701 Mortar Admix onto the
and International Association of Plumbing shower floor. The wire-reinforcement should
and Mechanical Officers (IAPMO) approved be 2" x 2" (50 mm x 50 mm), 16 gauge,
material, would then be installed to tie into galvanized, welded wire mesh and should be
the bottom flange of the drain (without placed at half the depth of the mortar bed.
blocking the weep holes). The liner must be Make sure that the mortar bed maintains the
turned up the walls to a point at least 3" (75 1/4" per foot (6 mm per 300 mm) slope to
mm) above the top of the curb or 6" (150 drain which was established by the pre-pitch
mm) above the floor in steam rooms or steam in the sub-floor. After the mortar bed has
showers without curbs. The shower pan must cured, the installation of the cement backer
be properly formed and fastened to prevent board on the walls and ceiling can begin.
problems. Check with local building code
The addition of a suitable insulation material
to help determine what shower pan liner is
between the wall and ceiling framing should
acceptable in your area. This pan will act as
be done before installation of the cement
your vapor barrier on the floor. Curbs must be
backer board. Insulation will help keep the
sloped to drain back into the steam room for
heat in the steam room, cool air out, and helps
condensation runoff. Perform a flood test to
to control the dew point (the temperature
determine integrity of the pan liner and make
where condensation takes place) within
repairs as necessary before proceeding.
the wall. The cement backer board used
After the shower pan liner is in place, install must be acceptable for steam room use
the vapor barrier directly onto the side of the and installed per the board manufacturer’s
wall and ceiling framing that will be exposed to written installation instructions; this includes
the steam room. The vapor barrier should be taping of all board joints. Use LATICRETE
4 – 6 mil thick polyethylene (cross laminated 254 Platinum and 2" (50 mm) wide, alkali-
virgin polyethylene is excellent) and, if resistant fiberglass mesh tape to treat the
possible, should be one piece that can fit into board joints. Be sure to allow space at the
the entire area. Fasten the vapor barrier to ceiling/wall transition for the insertion of
the studs with corrosion-resistant fasteners. a slip joint to allow for proper expansion/
A spot of LATICRETE® Latasil™ (100% silicone contraction to take place.
sealant) onto the fasteners will help prevent
Pipes and penetrations through board should
moisture penetration through the fastener
be accounted for and space between board
holes. Make sure that the vapor barrier is
and penetration should be kept to a minimum.
properly formed and is tight to the studs of
Allow the mortar used to tape the board
the walls and ceiling. Yes – the vapor barrier
joints to harden and then commence with
waterproofing the entire inside area of the 2. The second design involves installation over
steam room with LATICRETE Hydro all other substrates including concrete or
Ban™ or LATICRETE 9235 Waterproofing masonry walls. Again, the ceiling should be
Membrane. The entire steam room should sloped at least 2" minimum per foot (50 mm
be waterproofed, including the ceiling, walls, per 300 mm) to prevent water from dripping
floor, seat, and any other exposed area; on steam room occupants (per Tile Council
this will help improve the functionality of of North America recommendations).
the vapor barrier and inhibit the passage of The floor should be pre-pitched (prior
most of the moisture through the system. to the installation of the shower pan)
Loop the LATICRETE Hydro Ban or LATICRETE at the rate of 1/4" per foot (6 mm per
9235 Waterproofing Membrane into the slip 300 mm) to make sure that water flows
joints to allow for movement in these areas. toward the drain. Also, a shower pan is
Any vapor transpiring through the LATICRETE required in ALL steam room/steam shower
9235 Waterproofing Membrane should easily installations!
be handled by the vapor barrier. For more The installation begins with the proper
information on the installation of LATICRETE choice and placement of a two-part clamping
Hydro Ban or LATICRETE 9235 Waterproofing ring style drains with weepers as per ASME
Membrane, please refer to www.laticrete.com. A112.6.3. Place tile spacers or gravel around
Make sure that ANY and ALL penetrations are weep holes, as detailed by the design
properly waterproofed and sealed tightly with professional, to prevent mortar from clogging
LATICRETE Latasil! the weep holes, they should be installed by a
Tile can be installed directly onto the qualified plumber in accord with IRC P2709.4.
LATICRETE Hydro Ban or LATICRETE 9235 The pipes and drain should be properly
Waterproofing Membrane as soon as it is supported to prevent problems in the future.
dry to the touch. LATICRETE 254 Platinum For this type of steam room construction,
is the thin-set of choice for steam room/ LATICRETE Hydro Ban or LATICRETE 9235
steam shower installations. Check with the Waterproofing Membrane can be used as the
manufacturer of the tile to make sure that it primary shower pan liner. A suitable primary
is compatible in steam room applications. shower pan liner material, complying with
Once the tiles have set firm, grout the
installation with LATICRETE SpectraLOCK®†
PRO Grout for best performance. Alternative
grouting choices would be LATICRETE
PermaColor™ Grout^. Use LATICRETE Latasil,
with LATICRETE 9118 Primer, in slip joints,
steam jets, movement joints, around the
drain, to seal lighting fixtures, access panels
(if present), or at any change of plane. The
use of LATICRETE SpectraLOCK PRO Grout will
add to the performance of the tile installation
because it has an absorption rate of <.5%.
It will be necessary to wait for 14 days for
LATICRETE PermaColor Grout, and 10 days for
LATICRETE SpectraLOCK PRO Grout to cure
at 70°F (21°C) before turning on the steam
generation unit.
ASTM D4068, D4551 or other ICC and IAPMO imperative that this vapor barrier be placed
approved material may also be used as the so that it laps into the shower pan liner! This
primary shower pan liner. No matter which of way any moisture that comes in contact with
the approved materials is used as the shower the vapor barrier will drain into the shower
pan liner, it must be tied into the bottom pan and through the weep holes of the drain.
flange of the drain properly. The liner is Once the vapor barrier has been properly
applied directly onto the concrete or masonry installed, application of the insulation panels
walls and concrete floor. The liner must be can commence. These panels are typically
turned up the walls to a point at least 3" fastenedmechanicallythroughtothesubstrate
(75 mm) above the top of the curb or 6" through the vapor barrier; check with the
(150 mm) above the floor in steam rooms or insulation manufacturer for proper installation
steam showers without curbs. The shower instructions for their product in this
pan must be properly formed and fastened to application. A dab of LATICRETE Latasil
prevent problems. Check with local building can help prevent moisture from getting
code to help determine what shower pan through the fastener holes. Install galvanized
liner is acceptable in your area. This pan will diamond metal lath, complying with ASTM
act as your vapor barrier on the floor. Curbs C847, according to the current revision of
must be sloped to drain back into the steam ANSI A108.1 (1.1 and 1.2). Make sure that no
room for condensation runoff. Perform a fasteners penetrate the shower pan liner.
flood test to determine integrity of the pan Pencil rods and tie wires may also be used to
liner and make repairs as necessary before secure the metal lath in place.
proceeding. Allow 2 2 hour cure period at
Apply a mortar bed consisting of LATICRETE
70°F (21°C) prior to flood testing LATICRETE®
3701 Fortified Mortar Bed; or, LATICRETE 226
Hydro Ban™ a 7 day cure at 70°F (21°C) prior to
Thick Bed Mortar gauged with LATICRETE
flood testing LATICRETE 9235 Waterproofing
3701 Mortar Admix as scratch and leveling
Membrane. For more information on flood
coats, in compliance with ANSI A108.1A (1.3
testing requirements and procedures, please
and 1.4) over the wire lath on the walls and
refer to TDS 169 “Flood Testing Procedures”
ceiling. The scratch and float coats can be
at www.laticrete.com.
installed in lifts up to 5/8" (13 mm) thick and
After the shower pan liner is in place, install should be floated to be plumb and true.
the vapor barrier directly onto the concrete/
Next, install a 2" (50 mm) thick (minimum)
masonry walls making sure that the vapor
wire-reinforced, mortar bed comprised of
barrier laps into the shower pan liner. The vapor
LATICRETE 3701 Fortified Mortar Bed; or,
barrier should be 4 – 6 mil polyethylene (cross
LATICRETE 226 Thick Bed Mortar gauged
laminated virgin polyethylene is excellent)
with LATICRETE 3701 Mortar Admix onto the
and, if possible, should be one piece that can
shower floor. The wire-reinforcement should
fit into the entire area. Fasten the vapor barrier
be 2" x 2" (50 mm x 50 mm), 16 gauge,
to the wall with corrosion resistant fasteners.
galvanized, welded wire mesh and should be
A spot of LATICRETE Latasil™ (100% silicone)
placed at half the depth of the mortar bed.
onto the fasteners will help prevent moisture
Make sure that the mortar bed maintains the
penetration through the fastener holes. Make
1/4" per foot (6 mm per 300 mm) slope to
sure that the vapor barrier is properly formed
drain which was established by the pre-pitch
and is tight to the walls and ceiling. Yes
in the sub-floor.
the vapor barrier must be installed onto the
ceiling as well as the walls because steam
can certainly escape through the ceiling. It is
Allow the floor mortar bed to set until firm 1.3 Summary
and then commence with waterproofing the Expansion joints are generally placed at
inside area of the steam room with LATICRETE the wall/floor and wall/ceiling transitions.
Hydro Ban or LATICRETE 9235 Waterproofing Larger steam rooms may require additional
Membrane. The entire steam room should be expansion joints to allow for movement. The
waterproofed, including the ceiling, walls, project design professional should indicate
floor, seat, and any other exposed area; this where these expansion joints are placed. Refer
will help improve the functionality of the vapor to the Tile Council of North America Handbook
barrier and inhibit the passage of most of for Ceramic Tile Installation EJ-171 for more
the moisture through the system. Any vapor information and details.
transpiring through the LATICRETE Hydro Ban Once the steam room is ready…ENJOY!!
or LATICRETE 9235 Waterproofing Membrane
Please refer to the proper execution statement
should easily be handled by the vapor barrier.
located at the back of this guide for more
Make sure that any and all penetrations and
detailed instructions and details on these
fixtures are properly waterproofed and sealed
steam room installations.
tightly with LATICRETE Latasil.
Just keep in mind, it would be beneficial for all
Tile can now be installed directly onto the
concerned to make sure that the steam room
LATICRETE Hydro Ban or LATICRETE 9235
construction and installation is done right the
Waterproofing Membrane once it has
first time. Any mistake can lead to structural
sufficiently cured. LATICRETE 254 Platinum
damage, mold, water infiltration issues, and
is the thin-set of choice for steam room/
more.
steam shower installations. Check with the
manufacturer of the tile to make sure that it Repairs can be extensive, and the steam room
is compatible in steam room applications. would be far more costly to repair than to do it
right the first time!!
Once the tiles have set firm, grout the
installation with LATICRETE SpectraLOCK®†
PRO Grout for best performance. Alternative
grouting choices would be LATICRETE
PermaColor™ Grout^. Use LATICRETE Latasil,
with LATICRETE 9118 Primer, in slip joints,
steam jets, movement joints, around the
drain, or at any change in plane. The use of
LATICRETE SpectraLOCK PRO Grout will add
to the performance of the tile installation
because it has an absorption rate of <.5%.
It will be necessary to wait for 14 days for
LATICRETE PermaColor Grout, and 10 days for
LATICRETE SpectraLOCK PRO Grout to cure
at 70°F (21°C) before turning on the steam
generation unit.
†
United States Patent No.: 6,881,768 (and other Patents).
^ United States Patent No.: 6,784,229 B2 (and other Patents.)
NOTE: For complete application information and As a professional courtesy, LATICRETE offers
limitations consult related Product Data Sheets technical services free of charge. The user maintains
and Execution Statements related to this detail and all responsibility for verifying the applicability and
applicable industry standards. suitability of the technical service or information
provided.
†
United States Patent No.: 6881768 (and other Patents).
©2009 LATICRETE INTERNATIONAL, INC. All rights reserved. The right to utilize LATICRETE details for commercial purposes is granted exclusively to contractors, architects, quantity
surveyors, engineers, and specifications writers. LATICRETE®, LATAPOXY®, SPECTRALOCK® are registered trademarks of LATICRETE International, Inc. U.S. and Foreign Patent and Trademark
Offices, Marca Registrada. All other trademarks are property of their respective companies.
L. American Society For Testing And Materials W. American Society For Testing And Materials
(ASTM) C144 Standard Specification for (ASTM) C905 Standard Test Method for
Aggregate for Masonry Mortar Apparent Density of Chemical-Resistant
Mortars, Grouts, and Monolithic Surfacings
X. American Society For Testing And Materials II. American Society For Testing And Materials
(ASTM) C920 Standard Specification for (ASTM) E84 Standard Test Method for
Elastomeric Joint Sealants Surface Burning Characteristics of Building
Y. American Society For Testing And Materials Materials
(ASTM) C955 Standard Specification for Load JJ. American Society For Testing And Materials
Bearing (Transverse and Axial) Steel Studs, (ASTM) E90 Standard Test Method for
Runners (Tracks), and Bracing or Bridging Laboratory Measurement of Airborne Sound
for Screw Application of Gypsum Board and Transmission Loss of Building Partitions
Metal Plaster Bases KK. American Society For Testing And Materials
Z. American Society For Testing And Materials (ASTM) E96 Standard Test Methods for
(ASTM) D226 Standard Specification for Water Vapor Transmission of Materials
Asphalt-Saturated Organic Felt Used in LL. American Society For Testing And Materials
Roofing And Waterproofing (ASTM) E413 Standard Classification for
AA. American Society For Testing And Materials Rating Sound Insulation
(ASTM) D227 Standard Specification for MM. American Society For Testing And Materials
Coal-Tar Saturated Organic Felt Used in (ASTM) E492 Standard Test Method
Roofing and Waterproofing for Laboratory Measurement of Impact
BB. American Society For Testing And Materials Sound Transmission Through Floor-Ceiling
(ASTM) D751 Standard Test Method for Assemblies Using the Tapping Machine
Coated Fabrics NN. American Society For Testing And Materials
CC. American Society For Testing And Materials (ASTM) E989 Standard Classification for
(ASTM) D751 Standard Test Method for Determination of Impact Insulation Class
Rubber Property - Durometer Hardness (IIC)
DD. American Society For Testing And Materials OO. American Society of Mechanical Engineers
(ASTM) D1248 Standard Test Method for (ASME) – ASME A112.6.3 Floor and Trench
Staining of Porous Substances by Joint Drains
Sealants PP. Canadian Sheet Steel Building Institute
EE. American Society For Testing And Materials (CSSBI) Lightweight Steel Framing Binder
(ASTM) D2240 Standard Test Method for {Publication 52M}
Coated Fabrics QQ. Federal Housing Administration (FHA)
FF. American Society For Testing And Materials Bulletin No. 750 Impact Noise Control in
(ASTM) D4263 Standard Test Method for Multifamily Dwellings
Indicating Moisture in Concrete by The RR. Housing and Urban Development (HUD)
Plastic Sheet Method TS 28 A Guide to Airborne, Impact
GG. American Society For Testing And Materials and Structure-borne Noise-Control in
(ASTM) D4397 Standard Specification for Multifamily Dwellings
Polyethylene Sheeting for Construction, SS. Materials And Methods Standards
Industrial and Agricultural Applications Association (MMSA) Bulletins 1 – 16
HH. American Society For Testing And Materials TT. Metal Lath/Steel Framing Association
(ASTM) D4716 Standard Test Method for (ML/SFA) 540 Lightweight Steel Framing
Determining the (In Plane) Flow Rate Per Systems Manual
Unit Width and Hydraulic Transmissivity of
a Geo-synthetic Using a Constant Head
1.15 Delivery, Storage and Handling and 90°F (32°C) at time of installation. It is
A. AcceptanceatSite:deliverandstorepackaged the General Contractor’s responsibility to
materials in original containers with seals maintain temperature control.
unbroken and labels, including grade seal, 1.17 Sequencing and Scheduling
intact until time of use, in accordance with A. Coordinate installation of tile work with
manufacturer’s instructions. related work.
B. Store ceramic tile and installation system B. Proceed with tile work only after curbs,
materials in a dry location; handle in a vents, drains, piping, and other projections
manner to prevent chipping, breakage, and through substrate have been installed and
contamination. when substrate construction and framing of
C. Protect latex additives, organic adhesives, openings have been completed.
epoxy adhesives and sealants from NOTES FOR SPECIFIER: Edit for project specific sequence
freezing or overheating in accordance with and scheduling.
manufacturer’s instructions; store at room
temperature when possible. 1.18 Warranty
The Contractor warrants the work of this
D. Store portland cement mortars and grouts
Section to be in accordance with the Contract
in a dry location.
Documents and free from faults and defects
1.16 Project/Site Conditions in materials and workmanship for a period
A. Provide ventilation and protection of 25 years. The manufacturer of adhesives,
of environment as recommended by mortars, grouts and other installation materials
manufacturer. shall provide a written twenty five (25) year
B. Prevent carbon dioxide damage to ceramic warranty, which covers materials and labor
tile, mosaics, pavers, trim, thresholds, as – reference LATICRETE Warranty Data Sheet
well as adhesives, mortars, grouts and other 025.0 for complete details and requirements.
installation materials, by venting temporary For exterior facades over steel or wood framing,
heaters to the exterior. the manufacturer of adhesives, mortars, grouts
and other installation materials shall provide
C. Maintain ambient temperatures not less
a written ten (10) year warranty, which covers
than 50°F (10°C) or more than 100°F (38°C)
replacement of LATICRETE products only –
during installation and for a minimum of
reference LATICRETE Warranty Data Sheet
seven (7) days after completion. Setting
230.15 for complete details and requirements.
of portland cement is retarded by low
temperatures. Protect work for extended 1.19 Maintenance
period of time and from damage by other Submit maintenance data under provisions
trades. Installation with latex portland of Section 01730. Include cleaning methods,
cement mortars requires substrate, ambient cleaning solutions recommended, stain
and material temperatures at least 37°F removal methods, as well as polishes and
(3°C). There should be no ice in slab. waxes recommended.
Freezing after installation will not damage 1.20 Extra Materials Stock
latex portland cement mortars. Protect Upon completion of the work of this Section,
portland cement based mortars and grouts deliver to the Owner 2% minimum additional
from direct sunlight, radiant heat, forced tile and trim shape of each type, color, pattern
ventilation (heat and cold) and drafts until and size used in the Work, as well as extra
cured to prevent premature evaporation of stock of adhesives, mortars, grouts and other
moisture. Epoxy mortars and grouts require installation materials for the Owner’s use in
surface temperatures between 60°F (16°C)
C. Crack Suppression Membrane to be thin, cold NOTE TO SPECIFIER: Edit applicable tile installation
accessories.
applied, single component liquid and load
bearing. Reinforcing fabric (if required or 2.6 Performance Specification – Tile
used) to be non-woven, rot-proof specifically Installation Materials
intended for crack suppression membrane. A. Sound Abatement and Crack Isolation Mat
Materials to be non-toxic, non-flammable, shall be load bearing, shock and vibration
and non-hazardous during storage, resistant. It shall be certified by independent
mixing, application and when cured. Crack laboratory testing to meet the specified
Suppression Membrane shall also meet the acoustical performance when installed in a
following physical requirements: Floor Assembly with a 6" (150 mm) concrete
1. E
longation at break (ASTM D751): 20 – slab, as well as meet the following physical
30% requirements:
2. System Crack Resistance (ANSI A118.12) 1. Service Rating (ASTM C627): Light
Pass (High) 2. Point Load (ANSI A118.12-5.2): >1250 psi
3. 7 day Tensile Strength (ANSI A118.10): (8.6 MPa)
265 – 300 psi (1.8 – 2.0 MPa) 3. Installed Weight (ASTM C905 Modified):
4. 7 day Shear Bond Strength (ANSI A118.10) 2.6 lbs/ft2 (12.8 kg/m2)
200 – 275 psi (1.4 – 1.9 MPa) 4. Delta Impact Insulation Class (ΔIIC; ASTM
5. 28 Day Shear Bond Strength (ANSI E2179): 20
A118.4): >214 – 343 psi (1.48 – 2.4 MPa) B. Sound Abatement and Crack Suppression
6. S
ervice Rating (TCA/ASTM C627): Extra Adhesive shall comply with ANSI A118.12,
Heavy provide an Extra Heavy rating and provide a
7. Total VOC Content: < 0.05 mg/m3 minimum ΔIIC of 15:
D. Wire Reinforcing: 2" x 2" (50 x 50 mm) x 16 1. Service Rating (ASTM C627): Extra Heavy
ASW gauge or 0.0625" (1.6 mm) diameter 2. Delta Impact Insulation Class (ΔIIC; ASTM
galvanized steel welded wire mesh E2179): 15
complying with ANSI A108.02 3.7, ASTM 3. Point Load (ANSI A118.12 5.2): >1000 psi
A185 and ASTM A82. (6.9 MPa)
E. Cleavage membrane: 15 pound asphalt 4. Minimum Shear Bond Strength (ANSI
saturated, non-perforated roofing felt A118.12): 100psi (0.7 MPa)
complying with ASTM D226, 15 pound coal
C. Moisture Vapor Reduction to be epoxy based
tar saturated, non-perforated roofing felt
and GreenGuard compliant as well as
complying with ASTM D227 or 4.0 mils
meet the following physical requirements:
(0.1 mm) thick polyethylene plastic film
complying with ASTM D4397. 1. Shear Bond to Concrete (ANSI A118.12 –
5.1.5): >285 psi (2.0 MPa)
F. C
ementitious backer board units: size and
thickness as specified, complying with ANSI 2. Alkalinity Resistance (ASTM C267): Pass
A118.9. 3. Permeability (ASTM F1869): 9.7 lbs/1,000
G. Thresholds: Provide marble saddles ft2/ 24 hours down to 0.2 lbs/1,000 ft2/24
complying with ASTM C241 for abrasion hours (248 µg/s•m2 down to 11 µg/s•m2)
resistance and ASTM C503 for exterior
use, in color, size, shape and thickness as
indicated on drawings.
D. Latex Portland Cement Mortar for thick 6. Total VOC Content: <0.05 mg/m3
beds, screeds, leveling beds and scratch/ 7. Cured Epoxy Adhesive to be chemically and
plaster coats to be weather, frost, shock stain resistant to ketchup, mustard, tea,
resistant and meet the following physical coffee, milk, soda, beer, wine, bleach (5%
requirements: solution), ammonia, juices, vegetable oil,
1. C
ompressive Strength (ANSI A118.4 detergents, brine, sugar, cosmetics and
Modified): >4000 psi (27.6 MPa) blood, as well as chemically resistant to
2. Water Absorption (ANSI A118.6): ≤ 5% dilute food acids, dilute alkalis, gasoline,
turpentine and mineral spirits.
3. S
ervice Rating (TCA/ASTM C627): Extra
Heavy G. L atex Portland Cement Thin Bed Mortar for
thin set and slurry bond coats to be weather,
4. Smoke and Flame Contribution (ASTM
frost, shock resistant, non-flammable and
E84 Modified): 0
meet the following physical requirements:
5. Total VOC Content: < 0.05 mg/m3
1. Compressive strength (ANSI A118.4):
E. Self-Leveling Underlayment shall be >2500 psi (17.2 MPa)
mixed with water to produce a pumpable,
2. Bond strength (ANSI A118.4): >450 psi
fast setting, free flowing cementitious
(3.1 MPa)
underlayment which can be poured from a
feather-edge to 1-1/2" (38 mm) thick in one 3. Smoke and Flame Contribution (ASTM
pour. E84 Modified): 0
1. 4 Hour Compressive Strength (ANSI A118.4 4. Total VOC Content: <0.05 mg/m3
Mod.): >1500 psi (10.3 MPa) H. Organic Adhesive shall be non-flammable,
2. 1 Day Compressive Strength (ANSI A118.4 water resistant, latex adhesive and shall
Mod.): >2800 psi (19.3 MPa) meet the following physical requirements:
3. 2
8 Day Compressive Strength (ANSI 1. Open Time (ANSI A136.1): 70 minutes at
A118.4 Mod.): >4300 psi (29.7 MPa) 75°F (24°C)
4. Tensile Strength (ANSI A118.7): >500 psi 2. Color: White
(3.5 MPa) 3. Density (ANSI A136.1): 13.2 lbs/gal
5. Time To Foot Traffic: 3 – 4 Hours (1.6 kg/l)
6. Total VOC Content: <0.05 mg/m3 I. Epoxy Grout (Industrial) to be non-flammable,
chemical resistant 100% solids epoxy with
F. Epoxy Adhesive to be chemical resistant
high temperature resistance and meeting the
100% solids epoxy with high temperature
following physical requirements:
resistance and meet the following minimum
physical requirements: 1. Initial Set Time (ANSI A118.5): Pass
(4 hours)
1. Compressive strength (ANSI A118.3):
>5000 psi (34.4 MPa) 2. Service Set Time (ANSI A118.5): Pass
(<7 days)
hear Bond Strength (ANSI A118.3): >1250
2. S
psi (8.6 MPa) 3. Shrinkage (ANSI A118.3): Pass (0.07%)
3. Thermal Shock Resistance (ANSI A118.3): 4. Sag (ANSI A118.3): Pass (no sag)
>600 psi (4.1 MPa) 5. Shear Bond Strength (ANSI A118.3; quarry
4. Tensile Strength (ANSI A118.3): >1400 psi tile): 1000 psi (6.9 MPa)
(9.6 MPa) 6. Compressive Strength (ANSI A118.3):
5. Shrinkage (ANSI A118.3): 0 – 0.1% 15500 psi (107 MPa)
7. Tensile Strength (ANSI A118.5): 2600 psi 3. F lexural Strength (ANSI A118.7): >1250 psi
(18.0 MPa) (8.6 MPa)
8. Thermal Shock Resistance (ANSI A118.3): 4. Water Absorption (ANSI A118.7): <5%
500 psi (3.4 MPa) 5. L inear Shrinkage (ANSI A118.7): <0.05 %
9. Cured Epoxy Grout to be chemically and 6. Smoke and Flame Contribution (ASTM
stain resistant to ketchup, mustard, tea, E84 Modified): 0
coffee, milk, soda, beer, wine, bleach (3%
7. Total VOC Content: <0.05 mg/m3
solution), ammonia, juices, vegetable
oil, detergents, brine, sugar, cosmetics L. Expansion and Control Joint Sealant to be a
and blood, as well as being chemically one component, neutral cure, exterior grade
resistant to dilute food/mineral acids, silicone sealant and meet the following
gasoline and mineral spirits. requirements:
J. Epoxy Grout (Commercial/Residential) shall 1. Tensile Strength (ASTM C794): 280 psi
be non-toxic, non-flammable, non-hazardous (1.9 MPa)
during storage, mixing, application and when 2. Hardness (ASTM D751; Shore A):
cured and shall meet the following physical 25 (colored sealant) /15 (clear sealant)
requirements: 3. Weather Resistance (QUV Weather-
1. Compressive Strength (ANSI A118.3): 3500 ometer): 10000 hours (no change)
psi (24 MPa) M. R
oof Decks (and other exterior paving
2. Shear Bond Strength (ANSI A118.3): 1000 applications over occupied/storage spaces)
psi (6.9 MPa) shall consist of a Primary Roofing/
3. Tensile Strength (ANSI A118.3): 1100 psi Waterproofing Membrane, as specified in
(7.6 MPa) Section 0700 (q.v.), and a lightweight, frost/
weather resistant installation system for
4. Thermal Shock (ANSI A118.3): >500 psi
tile, pavers, brick and stone that provides
(3.5 MPa)
integral subsurface drainage and meets the
5. Water Absorption (ANSI A118.3): <0.5 % following physical requirements:
6. Vertical Joint Sag (ANSI A118.3): Pass 1. Compressive Strength (ASTM C109
7. Total VOC Content: <0.05 mg/m3 Modified): 3000 psi (20.7 MPa)
8. Cured Epoxy Grout to be chemically and 2. Hydraulic Transmissivity (ASTM D4716):
stain resistant to ketchup, mustard, tea, 1.6 gal/minute (6.1 l/minute)
coffee, milk, soda, beer, wine, bleach (5% 3. Service Rating (ASTM C627): Extra Heavy
solution), ammonia, juices, vegetable oil,
N. Spot Bonding Epoxy Adhesive for installing
brine, sugar, cosmetics, and blood, as well
tile, brick and stone over vertical and
as chemically resistant to dilute acids and
overhead surfaces shall be high strength,
dilute alkalis.
high temperature resistant, non-sag
K. Latex Portland Cement Grout to be weather, and shall meet the following physical
frost and shock resistant, as well as meet requirements:
the following physical requirements:
1. Thermal Shock Resistance (ANSI A118.3):
1. Compressive Strength (ANSI A118.7): 4500 >1000 psi (6.9 MPa)
psi (31 MPa)
2. Water Absorption (ANSI A118.3): 0.1 %
2. Tensile Strength (ANSI A118.7): >500 psi
3. Compressive Strength (ANSI A118.3):
(3.45 MPa)
>8300 psi (57.2 MPa)
installation; follow method ESB414. For more B. Lath and Plaster Method: Install prior to
information on the wall and ceiling installation; installing the waterproofing membrane:
follow method ES-W221(I). Install cleavage membrane complying
Structure to receive the installation assembly with current revision of ANSI A108.02 (3.8
must be sound, solid, well bonded, stripped Membrane or cleavage membrane). Install
clean and free from dust, wax, grease, sealer metal lath complying with the current
and all other contamination which may reduce revision of ANSI A108.1 (3.3 Requirements
or prevent adhesion. for lathing and portland cement plastering,
ANSI A108.02 (3.6 Metal lath) and A108.1A
B. Bonded Thick Bed – Pitch Layer Over Floor
(1.0 – 1.2, 1.4, and 5.1). Apply latex-portland
Substrate – To provide pitch over a concrete
cement mortar as scratch/leveling coat over
deck, prepare a LATICRETE® latex leveling
wire lath, concrete or masonry in compliance
bed mix (see § 3.4D thick bed mortar
with current revision of ANSI A108.01
material below applied over a slurry bond
(3.3.5.1) and A108.1A (1.4). Float surface of
coat consisting of LATICRETE 254 Platinum).
scratch/leveling coat plumb, true and allow
Apply mortar over dampened substrate.
mortar to set until firm. For installation of
Pitch layer 1/4" per 1' (6 mm per 0.3 m) per
tile, brick or stone, follow Thin Bed Method
ANSI A108.1A (2.3.4).
(§ 3.4E).
C. List other Substrates as required and means
Use the following LATICRETE® System Materials
of preparation as required)
LATICRETE 3701 Fortified Mortar Bed
(Insert any Special Means of Preparation –
LATICRETE 254 Platinum
In addition to the surface preparation
requirements listed above; …) References
LATICRETE Data Sheets: 100.0; 677.0
NOTE TO SPECIFIER: The above are example surface
categories; edit for project specific surfaces and conditions. LATICRETE MSDS: 3701FMB; 254
Use the following LATICRETE System Materials LATICRETE Technical Data Sheets: 105, 118,
LATICRETE 3701 Fortified Mortar Bed 199, 209
1. C
hemical Resistant, Water Cleanable Tile- sponge into the bucket and then wring out
Grouting Epoxy (ANSI A118.3): Follow cleaning solution until sponge is damp.
manufacturer‘s recommendations for Using a circular motion, lightly scrub
minimum cure time prior to grouting. grouted surfaces with the damp sponge
Store liquid components of LATICRETE to dissolve grout film/haze. Then drag
SpectraLOCK® PRO Grout† for 24 hours sponge diagonally over the scrubbed
at 70 – 80°F (21 – 27°C) prior to use surfaces to remove froth. Rinse sponge
to facilitate mixing and application. frequently and change cleaning solution
Substrate temperature must be 40 – 95°F at least every 50 ft2 (4.7 m2). Discard
(4 – 35°C). Verify joints are free of dirt, sponges as they become “gummy” with
debris or grout spacers. Sponge or wipe residue. Within one (1) hour of finishing
dust/dirt off tile faces and remove water first cleaning, clean the same area again
standing in joints. Apply grout release to following the same procedure but utilizing
face of absorptive, abrasive, non-slip or a clean white scrub pad and fresh cleaning
rough textured ceramic tile, pavers, bricks, solution. Rinse scrub pad frequently.
stone or trim units that are not hot paraffin Drag a clean sponge diagonally over the
coated to facilitate cleaning. Cut open scrubbed surfaces to remove froth. Use
pouch and pour LATICRETE SpectraLOCK each side of sponge only once before
PRO Grout Part A Liquid into a clean rinsing and change cleaning solution at
mixing pail. Then open pouch and pour least every 50 ft2 (4.7 m2). Allow cleaned
LATICRETE SpectraLOCK PRO Grout Part B areas to dry and inspect tile/stone surface.
Liquid into the mixing pail. Mix by hand or For persistent grout film/haze (within 24
with a slow speed (<300 rpm) mixer until hours), repeat scrubbing procedure with
the two liquids are well blended. Then, undiluted white vinegar and clean pad.
while mixing, add LATICRETE SpectraLOCK Rinse with clean water and allow surface
PRO Grout Part C Powder and blend until to dry. Inspect grout joint for pinholes/
uniform. Install LATICRETE SpectraLOCK voids and repair them with freshly mixed
PRO Grout in compliance with current LATICRETE SpectraLOCK PRO Grout.
revisions of ANSI A108.02 (3.13) and ANSI Cautions: Do not use undiluted white
A108.6 (3.0 – 4.0). Spread using a sharp vinegar on polished marble or limestone
edged, hard rubber float and work grout unless a test spot in an inconspicuous area
into joints. Using strokes diagonal (at indicates no change in finish appearance;
45° angle) to the grout lines, pack joints do not use acid cleaners on epoxy grout
full and free of voids/pits. Then hold float less than 7 days old.
face at a 90° angle to grouted surface and Use the following LATICRETE System Materials
use float edge to “squeegee” off excess LATICRETE SpectraLOCK PRO Grout
grout, stroking diagonally to avoid pulling
References
grout out of filled joints. Once excess
LATICRETE Data Sheets: 685.0, 685.5
grout is removed, a thin film/haze will
be left. Initial cleaning of the remaining LATICRETE MSDS: Pro Part A, Pro Part B,
film/haze can begin approximately 20 – Part C Powder, Cleaning Additive
30 minutes after grouting (wait longer at GREENGUARD Certificate: PRO
colder temperatures). Begin by mixing LATICRETE Technical Data Sheets: 111, 198,
cleaning additive packet with 2 gallons 212, 400
(7.6 l) of clean water in a clean bucket
to make cleaning solution. Dip a clean
2. Polymer Fortified Cement Grout (ANSI veneer face to remove any grout haze left
A118.7): Allow ceramic tile, mosaics, after “squeegeeing.” Rinse towel/sponge
pavers, brick or stone installation to cure frequently and change rinse water at least
a minimum of 24 hours at 70°F (21°C). every 200 ft2 (19 m2). Repeat this cleaning
Verify grout joints are free of dirt, debris sequence again if grout haze is still
or tile spacers. Sponge or wipe dust/dirt present. Allow grout joints to become firm.
off veneer face and remove any water Buff surface of grout with clean coarse
standing in joints. Apply grout release to cloth. Inspect joint for pinholes/voids
face of absorptive, abrasive, non-slip or and repair them with freshly mixed grout.
rough textured ceramic tile, pavers, bricks, Within 24 hours, check for remaining
or trim units that are not hot paraffin haze and remove it with warm soapy
coated to facilitate cleaning. Surface water and a nylon scrubbing pad, using a
temperature must be between 40–90°F circular motion, to lightly scrub surfaces
(4–32°C). Pour approximately 64 oz. (1.9 and dissolve haze/film. Do not use acid
l) of clean, potable water into a clean cleaners on latex portland cement grout
mixing container. Add a 25 lb (11.3 kg) less than 10 days old.
bag of LATICRETE® PermaColor™ Grout^ to NOTE TO SPECIFIER: Select one of following and specify
the container while mixing. Mix by hand color for each type/color of ceramic tile, mosaic, paver, trim
or with a slow speed mixer to a smooth, unit:
stiff consistency. Install latex fortified 1. Latex-portland cement sanded floor grout for joint widths
≥1/16" (1.5 mm ) and ≤1/2" (12 mm);
cement grout in compliance with current
2. Latex-portland cement unsanded grout for soft glazed
revisions of ANSI A108.1A (7.0 Grouting tiles and soft/polished stone with joints widths ≤1/8"
of tile), ANSI A108.02 (4.5 Cleaning tile) (3 mm).
and ANSI A108.10. Dampen dry surfaces Use the following LATICRETE® System Materials
with clean water. Spread using a sharp LATICRETE PermaColor Grout
edged, hard rubber float and work grout
References
into joints. Using diagonal (at 45° angle to
LATICRETE Data Sheets: 250.0
direction of grout line) strokes, pack joints
full and free of voids/pits. Hold float face LATICRETE MSDS: 2500
at a 90° angle to grouted surface and use GREENGUARD Certificates: 2500
float edge to “squeegee” off excess grout, LATICRETE Technical Data Sheets: 201, 400
stroking diagonally to reduce pulling grout
G. Expansion and Control Joints: Provide control
out of filled joints. Initial cleaning can
or expansion joints as located in contract
begin as soon as grout has become firm,
drawings and in full conformity, especially in
typically 15 – 20 minutes after grouting
width and depth, with architectural details.
at 70°F (21°C). Higher temperatures may
require faster time to initial cleaning; wider 1. Substrate joints must carry through, full
joints or lower temperatures may require a width, to surface of tile, brick or stone.
longer time to initial cleaning. Begin initial 2. Install expansion joints in tile, brick or
cleaning by lightly dampening the entire stone work over construction/cold joints
grouted area with a damp sponge. Then or control joints in substrates.
wash clean the entire area with a damp 3. Install expansion joints where tile, brick or
(not wet) sponge. Drag a clean towel, stone abut restraining surfaces (such as
dampened with water, or wipe a clean, perimeter walls, curbs, columns), changes
dampened sponge, diagonally over the in plane and corners.
4. Joint width and spacing depends on H. Adjusting: Correction of defective work for a
application – follow TCNA “Handbook period of one (1) year following substantial
for Ceramic Tile Installation” Detail “EJ- completion, return to job and correct all
171 Expansion Joints” or consult sealant defective work. Defective work includes,
manufacturer for recommendation based without limitation, tiles broken in normal
on project parameters. abuse due to deficiencies in setting bed,
5. Joint width: ≥1/8" (3 mm) and ≤1" (25 mm). loose tiles or grout, and all other defects
which may develop as a result of poor
6. Joint width: depth ~2:1 but joint depth
workmanship.
must be ≥1/8" (3 mm) and ≤1/2" (12 mm).
7. Layout (field defined by joints): 1:1 3.5 Cleaning
length: width is optimum but must be Clean excess mortar/epoxy from veneer
≤ 2:1. Remove all contaminants and surfaces with water before they harden and
foreign material from joint spaces/ as work progresses. Do not contaminate open
surfaces, such as dirt, dust, oil, water, grout/caulk joints while cleaning. Sponge and
frost, setting/grouting materials, sealers wash veneers diagonally across joints. Do not
and old sealant/backer. Use LATICRETE use acids for cleaning. Polish with clean dry
Latasil™ 9118 Primer for underwater and cloth. Remove surplus materials and leave
permanent wet area applications, or for premises broom clean.
porous stone (e.g. limestone, sandstone 3.6 Protection
etc…) installations. Install appropriate A. Protect finished installation under provisions
backing material (e.g. closed cell backer of §01500 and §01535. Close areas to other
rod) based on expansion joint design and trades and traffic until tile being installed has
as specified in § 07920. Apply masking set firmly. Keep traffic off horizontal portland
tape to face of tile, brick or stone veneer. cement thick bed mortar installations for at
Use caulking gun, or other applicator, to least 72 hours at 70°F (21°C)
completely fill joints with sealant. Within B. Keep floors installed with epoxy adhesive
5 – 10 minutes of filling joint, ‘tool’ sealant closed to foot traffic for 24 hours at 70°F
surface to a smooth finish. Remove (21°C), and to heavy traffic for 48 hours at
masking tape immediately after tooling 70°F (21°C) unless instructed differently
joint. Wipe smears or excess sealant off by manufacturer. Use kneeling boards, or
the face of non-glazed tile, brick, stone or equivalent, to walk/work on newly tiled
other absorptive surfaces immediately. floors. Cure tile work in swimming pools,
Use the following LATICRETE System Materials fountains and other continuous immersion
LATICRETE Latasil applications for 10 days at 70°F (21°C) for
LATICRETE Latasil 9118 Primer epoxy based grout and 14 days at 70°F
References (21°C) for latex portland cement based grout
LATICRETE Detail Drawings: WP300, WP301, before flood testing or filling installation
WP302, WP303, EJ-01, EJ-02, EJ-03, EJ-04, with water. Extend period of protection
EJ-05, EJ-06, EJ-07, EJ-08, EJ-09, EJ-10, EJ- of tile work at lower temperatures, below
11, EJ-12, EJ-13, EJ-14, EJ-15, P605 (Sealant 60°F (15°C), and at high relative humidity
treatments only) (>70% RH) due to retarded set times of
mortar/adhesives. Replace or restore work
LATICRETE Data Sheets: 6200.1, 6528.1
of other trades damaged or soiled by work
LATICRETE MSDS: Latasil, Primer under this section.
LATICRETE Technical Data Sheets: 211, 252
†
United States Patent No.: 6881768 (and other Patents).
^ United States Patent No.:6784229 B2 (and other Patents).
** GREENGUARD Indoor Air Quality Certified® and GREENGUARD
for Schools & Children Indoor Air Quality Certified Product.
NOTE: For complete application information and As a professional courtesy, LATICRETE offers
limitations consult related Product Data Sheets technical services free of charge. The user maintains
and Execution Statements related to this detail and all responsibility for verifying the applicability and
applicable industry standards. suitability of the technical service or information
†
United States Patent No.: 6881768 (and other Patents). provided.
^
United States Patent No.: 6784229 B2 (and other Patents).
©2009 LATICRETE INTERNATIONAL, INC. All rights reserved. The right to utilize LATICRETE details for commercial purposes is granted exclusively to contractors, architects, quantity
surveyors, engineers, and specifications writers. LATICRETE®, LATAPOXY®, SPECTRALOCK® are registered trademarks of LATICRETE International, Inc. U.S. and Foreign Patent and Trademark
Offices, Marca Registrada. All other trademarks are property of their respective companies.
W. American Society For Testing And Materials HH. American Society For Testing And Materials
(ASTM) C905 Standard Test Method for (ASTM) D4716 Standard Test Method for
Apparent Density of Chemical-Resistant Determining the (In Plane) Flow Rate Per
Mortars, Grouts, and Monolithic Surfacings Unit Width and Hydraulic Transmissivity of
X. American Society For Testing And Materials a Geo-Synthetic Using a Constant Head
(ASTM) C920 Standard Specification for II. American Society For Testing And Materials
Elastomeric Joint Sealants (ASTM) E84 Standard Test Method for
Y. American Society For Testing And Materials Surface Burning Characteristics of Building
(ASTM) C955 Standard Specification for Load Materials
Bearing (Transverse and Axial) Steel Studs, JJ. American Society For Testing And Materials
Runners (Tracks), and Bracing or Bridging (ASTM) E90 Standard Test Method for
for Screw Application of Gypsum Board and Laboratory Measurement of Airborne Sound
Metal Plaster Bases Transmission Loss of Building Partitions
Z. American Society For Testing And Materials KK. American Society For Testing And Materials
(ASTM) D226 Standard Specification for (ASTM) E96 Standard Test Methods for
Asphalt–Saturated Organic Felt Used in Water Vapor Transmission of Materials
Roofing And Waterproofing LL. American Society For Testing And Materials
AA. American Society For Testing And Materials (ASTM) E413 Standard Classification for
(ASTM) D227 Standard Specification for Rating Sound Insulation
Coal-Tar Saturated Organic Felt Used in MM. American Society For Testing And Materials
Roofing and Waterproofing (ASTM) E492 Standard Test Method
BB. American Society For Testing And Materials for Laboratory Measurement of Impact
(ASTM) D751 Standard Test Method for Sound Transmission Through Floor-Ceiling
Coated Fabrics Assemblies Using the Tapping Machine
CC. American Society For Testing And Materials NN. American Society For Testing And Materials
(ASTM) D751 Standard Test Method for (ASTM) E989 Standard Classification for
Rubber Property – Durometer Hardness Determination of Impact Insulation Class
DD. American Society For Testing And Materials (IIC)
(ASTM) D1248 Standard Test Method for OO. American Society of Mechanical Engineers
Staining of Porous Substances by Joint (ASME) – ASME A112.6.3 Floor and Trench
Sealants Drains
EE. American Society For Testing And Materials PP. Canadian Sheet Steel Building Institute
(ASTM) D2240 Standard Test Method for (CSSBI) Lightweight Steel Framing Binder
Coated Fabrics {Publication 52M}
FF. American Society For Testing And Materials QQ. Federal Housing Administration (FHA)
(ASTM) D4263 Standard Test Method for Bulletin No. 750 Impact Noise Control in
Indicating Moisture in Concrete by The Multifamily Dwellings
Plastic Sheet Method RR. Housing and Urban Development (HUD)
GG. American Society For Testing And Materials TS 28 A Guide to Airborne, Impact
(ASTM) D4397 Standard Specification for and Structure-borne Noise-Control in
Polyethylene Sheeting for Construction, Multifamily Dwellings
Industrial and Agricultural Applications
I. S
ubmit list from manufacturer of installation 1.13 Mock-Ups
system/adhesive/mortar/grout identifying a A. Provide mock–up of each type/style/finish/
minimum of three (3) similar projects, each size/color of ceramic tile, mosaics, pavers,
with a minimum of ten (10) years service. trim unit and threshold, along with respective
J. F or alternate materials, at least thirty (30) installation adhesives, mortars, grouts and
days before bid date submit independent other installation materials, under provisions
laboratory test results confirming of Section (01400) (01405).
compliance with specifications listed in Part 1.14 Pre-Installation Conference
2 – Products. Pre-installation conference: At least three
1.12 Quality Assurance weeks prior to commencing the work attend a
A. Tile Manufacturer (single source meeting at the job site to discuss conformance
responsibility): Company specializing in with requirements of specification and job
ceramic tile, mosaics, pavers, trim units site conditions. Representatives of owner,
and/or thresholds with three (3) years architect, general contractor, tile subcontractor,
minimum experience. Obtain tile from a Tile Manufacturer, Installation System
single source with resources to provide Manufacturer and any other parties who are
products of consistent quality in appearance involved in the scope of this installation must
and physical properties. attend the meeting.
B. Installation System Manufacturer 1.15 Delivery, Storage and Handling
(single source responsibility): Company A. Acceptance at Site: deliver and store
specializing in adhesives, mortars, grouts packaged materials in original containers with
and other installation materials with ten (10) seals unbroken and labels, including grade
years minimum experience and ISO 9001 seal, intact until time of use, in accordance
certification. Obtain installation materials with manufacturer’s instructions.
from single source manufacturer to insure B. Store ceramic tile and installation system
consistent quality and full compatibility. materials in a dry location; handle in a
C. Submit laboratory confirmation of adhesives, manner to prevent chipping, breakage, and
mortars, grouts and other installation contamination.
materials: C. Protect latex additives, organic adhesives,
1. Identify proper usage of specified materials epoxy adhesives and sealants from
using positive analytical method. freezing or overheating in accordance with
2. Identify compatibility of specified materials manufacturer’s instructions; store at room
using positive analytical method. temperature when possible.
3. Identify proper color matching of specified D. Store portland cement mortars and grouts
materials using a positive analytical in a dry location.
method. 1.16 Project/Site Conditions
D. Installer qualifications: company A. Provide ventilation and protection
specializing in installation of ceramic tile, of environment as recommended by
mosaics, pavers, trim units and thresholds manufacturer.
with five (5) years documented experience B. Prevent carbon dioxide damage to ceramic
with installations of similar scope, materials tile, mosaics, pavers, trim, thresholds, as
and design. well as adhesives, mortars, grouts and other
installation materials, by venting temporary
heaters to the exterior.
C. Maintain ambient temperatures not less and other installation materials shall provide
than 50°F (10°C) or more than 100°F (38°C) a written ten (10) year warranty, which covers
during installation and for a minimum of replacement of LATICRETE products only –
seven (7) days after completion. Setting reference LATICRETE Warranty Data Sheet
of portland cement is retarded by low 230.15 for complete details and requirements.
temperatures. Protect work for extended
1.19 Maintenance
period of time and from damage by other
Submit maintenance data under provisions
trades. Installation with latex portland
of Section 01730. Include cleaning methods,
cement mortars requires substrate, ambient
cleaning solutions recommended, stain
and material temperatures at least 37°F
removal methods, as well as polishes and
(3°C). There should be no ice in slab.
waxes recommended.
Freezing after installation will not damage
latex portland cement mortars. Protect 1.20 Extra Materials Stock
portland cement based mortars and grouts Upon completion of the work of this Section,
from direct sunlight, radiant heat, forced deliver to the Owner 2% minimum additional
ventilation (heat and cold) and drafts until tile and trim shape of each type, color, pattern
cured to prevent premature evaporation of and size used in the Work, as well as extra
moisture. Epoxy mortars and grouts require stock of adhesives, mortars, grouts and other
surface temperatures between 60°F (16°C) installation materials for the Owner’s use in
and 90°F (32°C) at time of installation. It is replacement and maintenance. Extra stock is
the General Contractor’s responsibility to to be from same production run or batch as
maintain temperature control. original tile and installation materials.
2.3 Floor Tile Materials 5. 7 day Shear Bond Strength (ANSI A118.10)
NOTE TO SPECIFIER: Edit for each tile type. >200 psi (1.4 MPa)
A. Ceramic Tile 6. 28 Day Shear Bond Strength (ANSI
A118.4): >214 psi (1.48 – 2.4 MPa)
B. Grade:
7.Service Rating (TCA/ASTM C627):
C. Size:
Extra Heavy
D. Edge
8. Total VOC Content: <0.05 mg/m3
E. Finish:
B. Epoxy Waterproofing Membrane to be 3
F. Color component epoxy, trowel applied specifically
G. Special shapes designed to be used under ceramic tile,
H. Location: stone or brick and requires only 24 hours
prior to flood testing:
2.4 Ceramic Tile Installation Materials
Manufacturer 1. B
reaking Strength (ANSI A118.10): 450–
A. L ATICRETE International, Inc., 530 psi (3.1–3.6 MPa)
1 Laticrete Park North, 2. Waterproofness (ANSI A118.10): No Water
Bethany, CT 06524-3423 USA penetration
Phone +1.800.243.4788, +1.203.393.0010 3. 7 day Shear Bond Strength (ANSI A118.10):
support@laticrete.com, 110–150 psi (0.8–1 MPa)
www.laticrete.com;
4. 28 Day Shear Bond Strength (ANSI
www.laticrete.com/green
A118.10): 90–120 psi (0.6–0.83 MPa)
NOTE TO SPECIFIER: Use either the following performance
specification or the proprietary specification.
5. 12 Week Shear Bond Strength (ANSI
A118.10): 110–130 psi (0.8–0.9 MPa)
2.5 Performance Specification –Tile 6. Total VOC Content: <3.4 g/l
Installation Accessories
C. Crack Suppression Membrane to be thin, cold
A. Waterproofing Membrane to be thin, cold
applied, single component liquid and load
applied, single component liquid and
bearing. Reinforcing fabric (if required or
load bearing. Reinforcing fabric to be non-
used) to be non-woven, rot-proof specifically
woven rot-proof specifically intended for
intended for crack suppression membrane.
waterproofing membrane. Waterproofing
Materials to be non-toxic, non-flammable,
Membrane to be non-toxic, non-flammable,
and non-hazardous during storage,
and non-hazardous during storage, mixing,
mixing, application and when cured. Crack
application and when cured. It shall be
Suppression Membrane shall also meet the
certified by IAPMO and ICC approved as a
following physical requirements:
shower pan liner and shall also meet the
following physical requirements: 1. E
longation at break (ASTM D751):
20–30%
1. Hydrostatic Test (ASTM D4068): Pass
2. System Crack Resistance (ANSI A118.12)
2. Elongation at break (ASTM D751):
Pass (High)
20–30%
3. 7 day Tensile Strength (ANSI A118.10):
3. System Crack Resistance (ANSI A118.12):
265 – 300 psi (1.8 – 2.0 MPa)
Pass (High)
4. 7 day Shear Bond Strength (ANSI A118.10)
4. 7 day Tensile Strength (ANSI A118.10):
200 – 275 psi (1.4 – 1.9 MPa)
>265 psi (1.8 MPa)
5. 28 Day Shear Bond Strength (ANSI 4. Delta Impact Insulation Class (ΔIIC; ASTM
A118.4): >214 – 343 psi (1.48 – 2.4 MPa) E2179): 20
6. Service Rating (TCA/ASTM C627): B. Sound Abatement and Crack Suppression
Extra Heavy Adhesive shall comply with ANSI A118.12,
provide an Extra Heavy rating and provide a
7. Total VOC Content: <0.05 mg/m3
minimum ΔIIC of 15:
D. Wire Reinforcing: 2" x 2" (50 x 50 mm)
1. Service Rating (ASTM C627): Extra Heavy
x 16 ASW gauge or 0.0625" (1.6 mm)
diameter galvanized steel welded wire mesh 2. Delta Impact Insulation Class (ΔIIC; ASTM
complying with ANSI A108.02 3.7, ASTM E2179): 15
A185 and ASTM A82. 3. Point Load (ANSI A118.12 5.2): >1000 psi
E. Cleavage membrane: 15 pound asphalt (6.9 MPa)
saturated, non-perforated roofing felt 4. Minimum Shear Bond Strength (ANSI
complying with ASTM D226, 15 pound coal A118.12): 100psi (0.7 MPa)
tar saturated, non-perforated roofing felt C. Moisture Vapor Reduction to be epoxy based
complying with ASTM D227 or 4.0 mils and GreenGuard compliant as well as meet
(0.1 mm) thick polyethylene plastic film the following physical requirements:
complying with ASTM D4397.
1. Shear Bond to Concrete (ANSI A118.12–
F. C
ementitious backer board units: size and 5.1.5): >285 psi (2.0 MPa)
thickness as specified, complying with ANSI
2. Alkalinity Resistance (ASTM C267): Pass
A118.9.
3. Permeability (ASTM F1869): 9.7 lbs/1,000
G. Thresholds: Provide marble saddles
ft2/24 hours down to 0.2 lbs/1,000 ft2/24
complying with ASTM C241 for abrasion
hours (248 µg/s•m2 down to 11 µg/s•m2)
resistance and ASTM C503 for exterior
use, in color, size, shape and thickness as D. Latex Portland Cement Mortar for thick
indicated on drawings. beds, screeds, leveling beds and scratch/
plaster coats to be weather, frost, shock
NOTE TO SPECIFIER: Edit applicable tile installation
accessories. resistant and meet the following physical
requirements:
2.6 Performance Specification – Tile
1. Compressive Strength (ANSI A118.4
Installation Materials
Modified): >4000 psi (27.6 MPa)
A. S
ound Abatement & Crack Isolation Mat
shall be load bearing, shock and vibration 2. Water Absorption (ANSI A118.6): ≤ 5%
resistant. It shall be certified by independent 3. S
ervice Rating (TCA/ASTM C627): Extra
laboratory testing to meet the specified Heavy
acoustical performance when installed in a 4. Smoke and Flame Contribution (ASTM
Floor Assembly with a 6" (150 mm) concrete E84 Modified): 0
slab, as well as meet the following physical
5. Total VOC Content: <0.05 mg/m3
requirements:
E. Self-Leveling Underlayment shall be
1. Service Rating (ASTM C627): Light
mixed with water to produce a pumpable,
oint Load (ANSI A118.12–5.2): >1250 psi
2. P fast setting, free flowing cementitious
(8.6 MPa) underlayment which can be poured from a
3. Installed Weight (ASTM C905 Modified): feather-edge to 1-1/2" (38 mm) thick in one
2.6 lbs/ft2 (12.8 kg/m2) pour.
1. 4 Hour Compressive Strength (ANSI A118.4 3. Smoke and Flame Contribution (ASTM
Mod.): >1500 psi (10.3 MPa) E84 Modified): 0
2. 1 Day Compressive Strength (ANSI A118.4 4. Total VOC Content: <0.05 mg/m3
Mod.): >2800 psi (19.3 MPa) H. O
rganic Adhesive shall be non–flammable,
3. 2
8 Day Compressive Strength (ANSI water resistant, latex adhesive and shall
A118.4 Mod.): >4300 psi (29.7 MPa) meet the following physical requirements:
4. Tensile Strength (ANSI A118.7): >500 psi 1. Open Time (ANSI A136.1): 70 minutes at
(3.5 MPa) 75°F (24°C)
5. Time To Foot Traffic: 3 – 4 Hours 2. Color: White
6. otal VOC Content: <0.05 mg/m 3
3. Density (ANSI A136.1): 13.2 lbs/gal
F. Epoxy Adhesive to be chemical resistant (1.6 kg/l)
100% solids epoxy with high temperature I. Epoxy Grout (Industrial) to be non–flammable,
resistance and meet the following minimum chemical resistant 100% solids epoxy with
physical requirements: high temperature resistance and meeting the
1. Compressive strength (ANSI A118.3): following physical requirements:
>5000 psi (34.4 MPa) 1. Initial Set Time (ANSI A118.5): Pass
hear Bond Strength (ANSI A118.3): >1250
2. S (4 hours)
psi (8.6 MPa) 2. Service Set Time (ANSI A118.5): Pass
3. Thermal Shock Resistance (ANSI A118.3): (<7 days)
>600 psi (4.1 MPa) 3. Shrinkage (ANSI A118.3): Pass (0.07%)
4. Tensile Strength (ANSI A118.3): >1400 psi 4. Sag (ANSI A118.3): Pass (no sag)
(9.6 MPa) 5. Shear Bond Strength (ANSI A118.3; quarry
5. Shrinkage (ANSI A118.3): 0 – 0.1% tile): 1000 psi (6.9 MPa)
6. Total VOC Content: <0.05 mg/m3 6. Compressive Strength (ANSI A118.3):
7. C
ured Epoxy Adhesive to be chemically and 15500 psi (107 MPa)
stain resistant to ketchup, mustard, tea, 7. Tensile Strength (ANSI A118.5): 2600 psi
coffee, milk, soda, beer, wine, bleach (5% (18.0 MPa)
solution), ammonia, juices, vegetable oil, 8. Thermal Shock Resistance (ANSI A118.3):
detergents, brine, sugar, cosmetics and 500 psi (3.4 MPa)
blood, as well as chemically resistant to
9. Cured Epoxy Grout to be chemically and
dilute food acids, dilute alkalis, gasoline,
stain resistant to ketchup, mustard, tea,
turpentine and mineral spirits.
coffee, milk, soda, beer, wine, bleach (3%
G. Latex Portland Cement Thin Bed Mortar for solution), ammonia, juices, vegetable
thin set and slurry bond coats to be weather, oil, detergents, brine, sugar, cosmetics
frost, shock resistant, non–flammable and and blood, as well as being chemically
meet the following physical requirements: resistant to dilute food/mineral acids,
1. Compressive strength (ANSI A118.4): gasoline and mineral spirits.
>2500 psi (17.2 MPa) J. Epoxy Grout (Commercial/Residential) shall
ond strength (ANSI A118.4): >450 psi
2. B be non-toxic, non-flammable, non-hazardous
(3.1 MPa) during storage, mixing, application and when
cured and shall meet the following physical
requirements:
B. E
poxy Waterproofing Membrane: LATAPOXY® H. Organic Adhesive: LATICRETE 15 Premium
24hr HydroProofing™ as manufactured by Mastic as manufactured by LATICRETE
LATICRETE International, Inc. International, Inc.
C. Crack Suppression Membrane: LATICRETE® I. Epoxy Grout (Industrial): LATAPOXY 2000
Blue 92 Anti–Fracture Membrane** as Industrial Grout** as manufactured by
manufactured by LATICRETE International, LATICRETE International, Inc.
Inc. J. Epoxy Grout (Commercial/Residential):
NOTE TO SPECIFIER: Edit applicable tile installation LATICRETE SpectraLOCK® PRO Grout†** as
accessories. manufactured by LATICRETE International,
2.8 Proprietary Specification – Tile Inc.
Installation Materials K. Latex Portland Cement Grout: LATICRETE
Installation materials as manufactured by PermaColor™ Grout** as manufactured by
LATICRETE International, Inc., LATICRETE International, Inc.
1 LATICRETE Park North, L. Expansion and Control Joint Sealant:
Bethany, CT 06524-3423 USA. LATICRETE Latasil™ as manufactured by
Phone +1.800.243.4788, LATICRETE International, Inc.
www.laticrete.com; www.laticrete.com/green
M. Roof Deck: LATICRETE Plaza & Deck
A. S
ound Control Underlayment: LATICRETE System as manufactured by LATICRETE
170 Sound & Crack Isolation Mat (Standard International, Inc.
or PLUS Configurations) as manufactured by
N. Spot Bonding Epoxy Adhesive: LATAPOXY
LATICRETE International, Inc.
310 Stone Adhesive (Standard or Rapid
B. Latex-Portland Cement Mortar for thick Grade) as manufactured by LATICRETE
beds, screeds, leveling beds and scratch/ International, Inc.
plaster coats: LATICRETE 3701 Fortified
Mortar Bed** as manufactured by LATICRETE
Part 3 – Execution
International, Inc. 3.1 Substrate Examination
A. Verify that surfaces to be covered with
C. Self-Leveling Underlayment: LATICRETE 86
ceramic tile, mosaics, pavers, brick, stone,
LatiLevel™** as manufactured by LATICRETE
trim or waterproofing are:
International, Inc.
1. Sound, rigid and conform to good design/
D. Moisture Vapor Reduction: LATAPOXY
engineering practices;
312 Vapor Reduction Membrane** as
manufactured by LATICRETE International, 2. Systems, including the framing system
Inc. and panels, over which tile or stone will
be installed shall be in conformance
E. Epoxy Adhesive: LATAPOXY 300 Adhesive**
with the International Residential Code
as manufactured by LATICRETE International,
(IRC) for residential applications, the
Inc.
International Building Code (IBC) for
F. Latex Portland Cement Thin Bed Mortar: commercial applications, or applicable
LATICRETE 254 Platinum** as manufactured building codes. The project design should
by LATICRETE International, Inc. include the intended use and necessary
G. Sound & Crack Isolation Adhesive: allowances for the expected live load,
LATICRETE 125 Sound & Crack Adhesive^** concentrated load, impact load, and dead
as manufactured by LATICRETE International, load including the weight of the finish and
Inc. installation materials;
3. Clean and free of dust, dirt, oil, grease, C. Advise General Contractor and Architect of
sealers, curing compounds, laitance, any surface or substrate conditions requiring
efflorescence, form oil, loose plaster, correction before tile work commences.
paint, and scale; Beginning of work constitutes acceptance of
4. Thin–set tile installations have a specified substrate or surface conditions.
subsurface tolerance, for instance 1/4" 3.2 Surface Preparation
in 10' (6 mm in 3 m) and 1/16" in 1' A. Requirements
(1.5 mm in 300 mm), to conform with the
Steam Rooms require a waterproofing
ANSI specifications. Because thin-set
membrane on all surfaces to prevent
is not intended to be used in truing or
moisture from penetrating adjoining spaces.
leveling the work of others, the subsurface
Additionally, a vapor barrier (6 mil thick
typically should not vary by more than
polyethylene sheeting or #15 Builders Felt)
1/16" over 1' (1.5 mm over 300 mm),
must be installed over the steel framing and
nor more than 1/32" (0.8 mm) between
behind the cement backer board. Vapor barrier
adjoining edges where applicable (e.g.
shall be designed for relative temperature
between sheets of exterior glue plywood
exposure. Install vapor barrier so that it laps
or between adjacent concrete masonry
over the shower pan waterproofing membrane
units). Should the architect/designer
so that condensation can drain into the
require a more stringent tolerance (e.g.
shower pan (not behind it) – see associated
1/8" in 10' [3 mm in 3 m]), the subsurface
detail SR-614B. All steam rooms will require
specification must reflect that tolerance,
adequate insulation on walls and ceilings to
or the tile specification must include a
reduce moisture condensation at temperature
specific and separate requirement to bring
variations. Slope ceilings 2" per foot (50 mm
the 1/4" (6 mm) subsurface tolerance
per 300 mm) minimum to avoid condensation
into compliance with the 1/8" (6 mm)
from dripping onto occupants. Install open slip
tolerance desired;
joints in all corners between walls and ceiling
5. Not leveled with gypsum or asphalt based and to divide areas that exceed 16' (480 cm)
compounds; in length.
6. Dry as per American Society for Testing Structure to receive the installation assembly
and Materials (ASTM) D4263 “Standard must be sound, solid, well bonded, stripped
Test for Determining Moisture in Concrete clean and free from dust, wax, grease, sealer
by the Plastic Sheet Method.” and all other contamination which may reduce
B. Concrete surfaces shall also be: or prevent adhesion per ANSI A108.02 (4.0).
1. Cured a minimum of 28 days at 70°F (21°C), B. B
onded Thick Bed – Pitch Layer Over Floor
including an initial seven (7) day period of Substrate – To provide pitch over a concrete
wet curing; deck, prepare a LATICRETE Latex Leveling
NOTE TO SPECIFIER: LATICRETE® latex portland cement
Bed mix (see § 3.4 C thick bed mortar
mortars do not require a minimum cure time for concrete material below applied over a slurry bond
substrates or mortar beds; coat consisting of LATICRETE 254 Platinum).
2. Wood float finished, or better, if the Apply mortar over dampened substrate.
installation is to be done by the thin bed Pitch layer 1/4" per 1' (6 mm per 0.3 m) per
method; ANSI A108.1A (2.3.4).
C. ( List other Substrates as required and (50 mm) for overlap at ends and sides to fit
means of preparation as required) the areas as required. Roll up the pieces for
(Insert any Special Means of Preparation easy handling and placement. Shake or stir
– In addition to the surface preparation LATICRETE Hydro Ban™ before using.
requirements listed above; …) Pre-Treat Cracks and Joints – Fill all substrate
NOTE TO SPECIFIER: The above are example surface cracks, cold joints and control joints to a smooth
categories; edit for project specific surfaces and conditions. finish using a LATICRETE latex-fortified thin-
set. Alternatively, a liberal coat* of LATICRETE
3.3 Installation – Accessories
Hydro Ban applied with a paint brush or trowel
(edit as required)
may be used to fill in non-structural joints and
3.4 Installation – Tile, Brick and Stone cracks. Apply a liberal coat* of LATICRETE
A. General: Install in accordance with current Hydro Ban approximately 8" (200 mm) wide
versions of American National Standards over substrate cracks, cold joints, and control
Institute, Inc. (ANSI) “A108 American joints using a paint brush or heavy napped
National Standard Specifications for paint roller.
Installation of Ceramic Tile” and TCNA Pre-Treat Coves and Floor/Wall Intersections –
“Handbook for Ceramic Tile Installation.” Fill all substrate coves and floor/wall
Cut and fit ceramic tile, brick or stone neatly transitions to a smooth finish and changes in
around corners, fittings, and obstructions. plane using a LATICRETE latex–fortified thin–
Perimeter pieces to be minimum half tile, set. Alternatively, a liberal coat* of LATICRETE
brick or stone. Chipped, cracked, split Hydro Ban™ applied with a paint brush or
pieces and edges are not acceptable. Make trowel may be used to fill in cove joints and
joints even, straight, plumb and of uniform floor/wall transitions <1/8" (3 mm) in width.
width to tolerance +/– 1/16" over 8' (1.5 mm Apply a liberal coat* of LATICRETE Hydro Ban
in 2.4 m). Install divider strips at junction of approximately 8" (200 mm) wide over substrate
flooring and dissimilar materials. cracks, cold joints, and control joints using a
B. Waterproofing Membrane installed over paint brush or heavy napped paint roller.
pre-sloped floor substrate and all walls and Pre-Treat Drains – Drains must be of the
ceilings. Membrane must be used on all clamping ring type, with weepers as per ASME
areas in the steam room. Loop membrane A112.6.3. Apply a liberal coat* of LATICRETE
into all slip joints to allow for movement in Hydro Ban around and over the bottom half
these areas. of drain clamping ring. Cover with a second
NOTE TO SPECIFIER: Adhesives/mastics, mortars and grouts liberal coat of LATICRETE Hydro Ban. When
for ceramic tile, mosaics, pavers, brick and stone are not
the LATICRETE Hydro Ban dries, apply a bead
replacements for waterproofing membranes and will not
prevent water penetration into occupied or storage spaces of LATICRETE Latasil™ where the LATICRETE
below. Drains must be a two-part clamping ring style drains Hydro Ban meets the drain throat. Install the
with weepers and as per ASME A112.6.3. Place tile spacers
top half of drain clamping ring.
or gravel around weep holes to prevent mortar from clogging
the weep holes. Pre-Treat Penetrations – Allow for a minimum
Install the waterproofing membrane in 1/8" (3 mm) space between drains, pipes,
compliance with current revisions of ANSI lights, or other penetrations and surrounding
A108.1 (2.7 Waterproofing) and ANSI A108.13. ceramic tile, stone or brick. Pack any gaps
Review the installation and plan the application around pipes, lights or other penetrations with
sequence. Pre-cut LATICRETE® Waterproofing/ a LATICRETE latex-fortified thin-set. Apply a
Anti-Fracture Fabric (if required), allowing 2" liberal coat* of LATICRETE Hydro Ban around
penetration opening. Cover the first coat with conditions will require a longer curing time.
a second liberal coat* of LATICRETE Hydro Ban. For temperatures between 50°F and 69°F (10°C
Bring LATICRETE Hydro Ban up to level of tile or to 21°C) allow a minimum 24 hour cure period
stone. When LATICRETE Hydro Ban has dried prior to flood testing.
to the touch seal with LATICRETE Latasil. Use the following LATICRETE® System Materials
Main Application – Allow any pre-treated LATICRETE Hydro Ban
areas to dry to the touch. Apply a liberal References
coat* of LATICRETE Hydro Ban with a paint LATICRETE Data Sheets: 663.0, 663.5
brush or heavy napped roller over substrate
LATICRETE MSDS: Hydro Ban, Fabric
including pre–treated areas and allow to dry
to the touch. Install another liberal coat* of GREENGUARD Certificate: Hydro Ban
LATICRETE Hydro Ban over the first coat. Let LATICRETE Technical Data Sheets: 188, 189,
the top coat of LATICRETE Hydro Ban dry to the 203, 169
touch approximately 1 – 2 hours at 70°F (21°C) C. Bonded Thick Bed Method: Apply a slurry
and 50% RH. When the top coat has dried to bond coat consisting of LATICRETE® 254
the touch inspect the surface for pinholes, Platinum. Apply mortar over dampened
voids, thin spots or other defects. LATICRETE substrate. Pitch layer 1/4" per 1' (6 mm
Hydro Ban will dry to an olive green color when per 300 mm) to comply with ANSI A108.1A
fully cured. Use additional LATICRETE Hydro (2.3.4). While slurry bond coat is wet and
Ban to seal any defects. tacky, embed the mortar bed consisting
Movement Joints – Apply a liberal coat* of of LATICRETE 3701 Fortified Mortar Bed
LATICRETE Hydro Ban, approximately 8" mixed with water in compliance with current
(200 mm) wide over the areas. Then embed revision of ANSI A108.1A (2.2 and 5.2) and
and loop the 6" (150 mm) wide LATICRETE compact mortar by tamping with flat trowel.
Waterproofing/Anti-Fracture Fabric and allow Screed mortar bed level and provide correct
the LATICRETE Hydro Ban liquid to bleed slopes to drains.
through. Immediately apply a second coat of Use the following LATICRETE System Materials
LATICRETE Hydro Ban. LATICRETE 3701 Fortified Mortar Bed
* Dry coat thickness is 20 – 30 mil (0.02 – 0.03" or LATICRETE 254 Platinum
0.5 – 0.8 mm); consumption per coat is approximately
0.01 gal/ft2 (approx. 0.4 l/m2); coverage is approximately References
100 ft2/gal (approx. 2.5 m2/l). LATICRETE® Waterproofing/ LATICRETE Data Sheets: 100.0; 677.0
Anti-Fracture Fabric can be used to pre-treat cracks, joints,
curves, corners, drains, and penetrations with LATICRETE LATICRETE MSDS: 3701FMB; 254
Hydro Ban™.
GREENGUARD Certificates: 3701FMB; 254
Protection – Provide protection for newly LATICRETE Technical Data Sheets: 106, 114,
installed membrane, even if covered with a 118, 128, 143, 154, 199, 204
thin–bed ceramic tile, stone or brick installation
D. Secondary Waterproofing Membrane
against exposure to rain or other water for a
installed over cured mortar bed on the floor
minimum of 2 hours at 70°F (21°C) and 50%
surfaces and turned up the vertical surfaces
RH. For temperatures between 45°F and 69°F
at least 6" (150 mm) onto the existing
(7°C to 21°C) allow a minimum 24 hour cure
waterproofing membrane. Loop membrane
period.
into all slip and movement joints to allow for
Flood Testing – Allow membrane to cure fully movement in these areas.
before flood testing, typically a minimum
2 hours at 70°F (21°C) and 50% RH. Cold
NOTE TO SPECIFIER: Adhesives/mastics, mortars and grouts of LATICRETE Latasil™ where the LATICRETE
for ceramic tile, mosaics, pavers, brick and stone are not
replacements for waterproofing membranes and will not
Hydro Ban meets the drain throat. Install the
prevent water penetration into occupied or storage spaces top half of drain clamping ring.
below.
Pre-Treat Penetrations – Allow for a minimum
Install the waterproofing membrane in 1/8" (3 mm) space between drains, pipes,
compliance with current revisions of ANSI lights, or other penetrations and surrounding
A108.1 (2.7 Waterproofing) and ANSI A108.13. ceramic tile, stone or brick. Pack any gaps
Review the installation and plan the application around pipes, lights or other penetrations with
sequence. Pre-cut LATICRETE® Waterproofing/ a LATICRETE latex-fortified thin-set. Apply a
Anti-Fracture Fabric (if required), allowing 2" liberal coat* of LATICRETE Hydro Ban around
(50 mm) for overlap at ends and sides to fit penetration opening. Cover the first coat with
the areas as required. Roll up the pieces for a second liberal coat* of LATICRETE Hydro Ban.
easy handling and placement. Shake or stir Bring LATICRETE Hydro Ban up to level of tile or
LATICRETE Hydro Ban™ before using. stone. When LATICRETE Hydro Ban has dried
Pre-Treat Cracks and Joints – Fill all substrate to the touch seal with LATICRETE Latasil.
cracks, cold joints and control joints to a smooth Main Application – Allow any pre-treated
finish using a LATICRETE latex-fortified thin- areas to dry to the touch. Apply a liberal
set. Alternatively, a liberal coat* of LATICRETE coat* of LATICRETE Hydro Ban with a paint
Hydro Ban applied with a paint brush or trowel brush or heavy napped roller over substrate
may be used to fill in non-structural joints including pre–treated areas and allow to dry
and cracks. Apply a liberal coat* of LATICRETE to the touch. Install another liberal coat* of
Hydro Ban approximately 8" (200 mm) wide LATICRETE Hydro Ban over the first coat. Let
over substrate cracks, cold joints, and control the top coat of LATICRETE Hydro Ban dry to the
joints using a paint brush or heavy napped touch approximately 1 – 2 hours at 70°F (21°C)
paint roller. and 50% RH. When the top coat has dried to
Pre-Treat Coves and Floor/Wall Intersections – the touch inspect the surface for pinholes,
Fill all substrate coves and floor/wall voids, thin spots or other defects. LATICRETE
transitions to a smooth finish and changes in Hydro Ban will dry to an olive green color when
plane using a LATICRETE latex-fortified thin- fully cured. Use additional LATICRETE Hydro
set. Alternatively, a liberal coat* of LATICRETE Ban to seal any defects.
Hydro Ban™ applied with a paint brush or Movement Joints – Apply a liberal coat* of
trowel may be used to fill in cove joints and LATICRETE Hydro Ban, approximately 8"
floor/wall transitions <1/8" (3 mm) in width. (200 mm) wide over the areas. Then embed
Apply a liberal coat* of LATICRETE Hydro Ban and loop the 6" (150 mm) wide LATICRETE
approximately 8" (200 mm) wide over substrate Waterproofing/Anti-Fracture Fabric and allow
cracks, cold joints, and control joints using a the LATICRETE Hydro Ban liquid to bleed
paint brush or heavy napped paint roller. through. Immediately apply a second coat of
Pre-Treat Drains – Drains must be of the LATICRETE Hydro Ban.
clamping ring type, with weepers as per ASME * Dry coat thickness is 20 – 30 mil (0.02 – 0.03" or
A112.6.3. Apply a liberal coat* of LATICRETE 0.5 – 0.8 mm); consumption per coat is approximately
0.01 gal/ft2 (approx. 0.4 l/m2); coverage is approximately
Hydro Ban™ around and over the bottom half 100 ft2/gal (approx. 2.5 m2/l). LATICRETE® Waterproofing/
of drain clamping ring. Cover with a second Anti0Fracture Fabric can be used to pre-treat cracks, joints,
liberal coat of LATICRETE Hydro Ban. When curves, corners, drains, and penetrations with LATICRETE
Hydro Ban™.
the LATICRETE Hydro Ban dries, apply a bead
Protection – Provide protection for newly to set until firm. Clean excess latex portland
installed membrane, even if covered with a cement mortar from tile or stone face and
thin–bed ceramic tile, stone or brick installation joints between pieces.
against exposure to rain or other water for a Use the following LATICRETE System Materials
minimum of 2 hours at 70°F (21°C) and 50% LATICRETE 254 Platinum
RH. For temperatures between 45°F and 69°F
References
(7°C to 21°C) allow a minimum 24 hour cure
LATICRETE Data Sheet: 677.0
period.
LATICRETE MSDS: 254
Flood Testing – Allow membrane to cure fully
before flood testing, typically a minimum GREENGUARD Certificate: 254
2 hours at 70°F (21°C) and 50% RH. Cold LATICRETE Technical Data Sheets: 105, 118,
conditions will require a longer curing time. 126, 129, 199, 209
For temperatures between 50°F and 69°F (10°C F. Grouting or Pointing:
to 21°C) allow a minimum 24 hour cure period
NOTE TO SPECIFIER: Select one of following and specify
prior to flood testing. color for each type/color of ceramic tile, mosaic, paver, trim
unit:
Use the following LATICRETE® System Materials
LATICRETE Hydro Ban 1. Chemical Resistant, Water Cleanable Tile-
References Grouting Epoxy (ANSI A118.3): Follow
LATICRETE Data Sheets: 663.0, 663.5 manufacturer‘s recommendations for
minimum cure time prior to grouting.
LATICRETE MSDS: Hydro Ban, Fabric
Store liquid components of LATICRETE
GREENGUARD Certificate: Hydro Ban SpectraLOCK® PRO Grout† for 24 hours at
LATICRETE Technical Data Sheets: 188, 189, 203 70–80°F (21–27°C) prior to use to facilitate
E. Thin Bed Method: Install latex portland mixing and application. Substrate
cement mortar in compliance with current temperature must be 40–95°F (4–35°C).
revisions of ANSI A108.02 (3.8 Membrane Verify joints are free of dirt, debris or grout
or cleavage membrane), A108.1B and ANSI spacers. Sponge or wipe dust/dirt off tile
A108.5. Use the appropriate trowel notch faces and remove water standing in joints.
size to ensure proper bedding of the tile, Apply grout release to face of absorptive,
brick or stone selected. Work the latex abrasive, non–slip or rough textured
portland cement mortar into good contact ceramic tile, pavers, bricks, stone or trim
with the substrate and comb with notched units that are not hot paraffin coated to
side of trowel. Spread only as much latex facilitate cleaning. Cut open pouch and
portland cement mortar as can be covered pour LATICRETE SpectraLOCK PRO Grout
while the mortar surface is still wet and Part A Liquid into a clean mixing pail.
tacky. When installing large format (>8" Then open pouch and pour LATICRETE
x 8"/200 mm x 200 mm) tile/stone, rib/ SpectraLOCK PRO Grout Part B Liquid
button/lug back tiles, pavers or sheet into the mixing pail. Mix by hand or with
mounted ceramics/mosaics, spread latex a slow speed (<300 rpm) mixer until the
portland cement mortar onto the back of (i.e. two liquids are well blended. Then, while
‘back-butter’) each piece/sheet in addition mixing, add LATICRETE SpectraLOCK
to trowelling latex portland cement mortar PRO Grout Part C Powder and blend until
over the substrate. Beat each piece/sheet uniform. Install LATICRETE SpectraLOCK
into the latex portland cement mortar with PRO Grout in compliance with current
a beating block or rubber mallet to insure revisions of ANSI A108.02 (3.13) and ANSI
full bedding and flatness. Allow installation A108.6 (3.0 – 4.0). Spread using a sharp
edged, hard rubber float and work grout Cautions: Do not use undiluted white vinegar on polished
marble or limestone unless a test spot in an inconspicuous
into joints. Using strokes diagonal (at area indicates no change in finish appearance; do not use
45° angle) to the grout lines, pack joints acid cleaners on epoxy grout less than 7 days old.
full and free of voids/pits. Then hold float
Use the following LATICRETE® System Materials
face at a 90° angle to grouted surface and
LATICRETE SpectraLOCK PRO Grout
use float edge to “squeegee” off excess
grout, stroking diagonally to avoid pulling References
grout out of filled joints. Once excess LATICRETE Data Sheets: 685.0, 685.5
grout is removed, a thin film/haze will LATICRETE MSDS: Pro Part A, Pro Part B, Part C
be left. Initial cleaning of the remaining Powder, Cleaning Additive
film/haze can begin approximately 20–30 GREENGUARD Certificate: PRO
minutes after grouting (wait longer at
LATICRETE Technical Data Sheets: 111, 198,
colder temperatures). Begin by mixing
212, 400
cleaning additive packet with 2 gallons
(7.6 l) of clean water in a clean bucket 2. Polymer Fortified Cement Grout (ANSI
to make cleaning solution. Dip a clean A118.7): Allow ceramic tile, mosaics,
sponge into the bucket and then wring out pavers, brick or stone installation to cure
cleaning solution until sponge is damp. a minimum of 24 hours at 70° F (21°C).
Using a circular motion, lightly scrub Verify grout joints are free of dirt, debris
grouted surfaces with the damp sponge or tile spacers. Sponge or wipe dust/
to dissolve grout film/haze. Then drag dirt off veneer face and remove any
sponge diagonally over the scrubbed water standing in joints. Apply grout
surfaces to remove froth. Rinse sponge release to face of absorptive, abrasive,
frequently and change cleaning solution non–slip or rough textured ceramic tile,
at least every 50 ft2 (4.7m2). Discard pavers, bricks, or trim units that are not
sponges as they become “gummy” with hot paraffin coated to facilitate cleaning.
residue. Within one (1) hour of finishing Surface temperature must be between
first cleaning, clean the same area again 40–90°F (4–32°C). Pour approximately
following the same procedure but utilizing 64 oz (1.9 l) of clean, potable water into
a clean white scrub pad and fresh cleaning a clean mixing container. Add a 25 lb
solution. Rinse scrub pad frequently. (11.3 kg) bag of LATICRETE PermaColor™
Drag a clean sponge diagonally over the Grout^ to the container while mixing. Mix
scrubbed surfaces to remove froth. Use by hand or with a slow speed mixer to a
each side of sponge only once before smooth, stiff consistency. Install latex
rinsing and change cleaning solution at fortified cement grout in compliance
least every 50 ft2 (4.7 m2). Allow cleaned with current revisions of ANSI A108.1A
areas to dry and inspect tile/stone surface. (7.0 Grouting of tile), ANSI A108.02 (4.5
For persistent grout film/haze (within 24 Cleaning tile) and ANSI A108.10. Dampen
hours), repeat scrubbing procedure with dry surfaces with clean water. Spread using
undiluted white vinegar and clean pad. a sharp edged, hard rubber float and work
Rinse with clean water and allow surface grout into joints. Using diagonal (at 45°
to dry. Inspect grout joint for pinholes/ angle to direction of grout line) strokes,
voids and repair them with freshly mixed pack joints full and free of voids/pits.
LATICRETE® SpectraLOCK® PRO Grout†. Hold float face at a 90° angle to grouted
surface and use float edge to “squeegee”
NOTE: For complete application information and As a professional courtesy, LATICRETE offers
limitations consult related Product Data Sheets technical services free of charge. The user maintains
and Execution Statements related to this detail and all responsibility for verifying the applicability and
applicable industry standards. suitability of the technical service or information
provided.
†
United States Patent No.: 6881768 (and other Patents).
^
United States Patent No.: 6784229 B2 (and other Patents).
©2009 LATICRETE INTERNATIONAL, INC. All rights reserved. The right to utilize LATICRETE details for commercial purposes is granted exclusively to contractors, architects, quantity
surveyors, engineers, and specifications writers. LATICRETE®, LATAPOXY®, SPECTRALOCK® are registered trademarks of LATICRETE International, Inc. U.S. and Foreign Patent and Trademark
Offices, Marca Registrada. All other trademarks are property of their respective companies.
NOTE: For complete application information and As a professional courtesy, LATICRETE offers
limitations consult related Product Data Sheets technical services free of charge. The user maintains
and Execution Statements related to this detail and all responsibility for verifying the applicability and
applicable industry standards. suitability of the technical service or information
provided.
†
United States Patent No.: 6881768 (and other Patents).
^
United States Patent No.: 6784229 B2 (and other Patents).
©2009 LATICRETE INTERNATIONAL, INC. All rights reserved. The right to utilize LATICRETE details for commercial purposes is granted exclusively to contractors, architects, quantity
surveyors, engineers, and specifications writers. LATICRETE®, LATAPOXY®, SPECTRALOCK® are registered trademarks of LATICRETE International, Inc. U.S. and Foreign Patent and Trademark
Offices, Marca Registrada. All other trademarks are property of their respective companies.
NOTE: For complete application information and As a professional courtesy, LATICRETE offers
limitations consult related Product Data Sheets technical services free of charge. The user maintains
and Execution Statements related to this detail and all responsibility for verifying the applicability and
applicable industry standards. suitability of the technical service or information
provided.
†
United States Patent No.: 6881768 (and other Patents).
^
United States Patent No.: 6784229 B2 (and other Patents).
©2009 LATICRETE INTERNATIONAL, INC. All rights reserved. The right to utilize LATICRETE details for commercial purposes is granted exclusively to contractors, architects, quantity
surveyors, engineers, and specifications writers. LATICRETE®, LATAPOXY®, SPECTRALOCK® are registered trademarks of LATICRETE International, Inc. U.S. and Foreign Patent and Trademark
Offices, Marca Registrada. All other trademarks are property of their respective companies.
NOTE: For complete application information and As a professional courtesy, LATICRETE offers
limitations consult related Product Data Sheets technical services free of charge. The user maintains
and Execution Statements related to this detail and all responsibility for verifying the applicability and
applicable industry standards. suitability of the technical service or information
provided.
†
United States Patent No.: 6881768 (and other Patents).
^
United States Patent No.: 6784229 B2 (and other Patents).
©2009 LATICRETE INTERNATIONAL, INC. All rights reserved. The right to utilize LATICRETE details for commercial purposes is granted exclusively to contractors, architects, quantity
surveyors, engineers, and specifications writers. LATICRETE®, LATAPOXY®, SPECTRALOCK® are registered trademarks of LATICRETE International, Inc. U.S. and Foreign Patent and Trademark
Offices, Marca Registrada. All other trademarks are property of their respective companies.
NOTE: For complete application information and As a professional courtesy, LATICRETE offers
limitations consult related Product Data Sheets technical services free of charge. The user maintains
and Execution Statements related to this detail and all responsibility for verifying the applicability and
applicable industry standards. suitability of the technical service or information
provided.
©2009 LATICRETE INTERNATIONAL, INC. All rights reserved. The right to utilize LATICRETE details for commercial purposes is granted exclusively to contractors, architects, quantity
surveyors, engineers, and specifications writers. LATICRETE®, LATAPOXY®, SPECTRALOCK® are registered trademarks of LATICRETE International, Inc. U.S. and Foreign Patent and Trademark
Offices, Marca Registrada. All other trademarks are property of their respective companies.
as each component, and it’s installation, of the Monitoring (Spreading, Thickness, Open
system. So choosing the proper products and Time, Tackiness, Beat-In, Coverage)
installing them correctly is critical to the long- Clean-Up and Protection
n
Owner
n Define Scope of Work
n Organizational Requirements
n Quality Objectives
3.2# expandable diamond metal lath fastened to rigid foam insolation board which has been
installed over a vapor barrier.
Bench/wall transition and proper placement of 3.2# expandable diamond metal lath.
Transition of walls to ceiling prior to installation of LATICRETE® 226 Thick Bed Mortar and LATICRETE
3701 Mortar Admix scratch coat.
Proper tie-in of 3.2# expandable diamond metal lath to steam room light fixture.
Ceiling (with sprinkler head) showing Tile Council of North America (TCNA) recommended pitch of
2" per foot (50 mm per 300 mm).
Pipe penetration for steam generation unit and proper tie-in of 3.2# expandable diamond metal
lath.
Installation of 3.2# expandable diamond metal lath to stainless steel door frame and flashing.
Wall partially finished with scratch coat of LATICRETE® 226 Thick Bed Mortar and LATICRETE 3701
Mortar Admix.
Finishing the application of the LATICRETE 226 Thick Bed Mortar and LATICRETE 3701 Mortar Admix
scratch coat.
Scratching the LATICRETE 226 Thick Bed Mortar and LATICRETE 3701 Mortar Admix with a piece of
metal lath.
A finished, scratch coat wall which is now ready for “the float coat.”
The steam room seats after the installation of the LATICRETE® 3701 Mortar Admix and LATICRETE
226 Thick Bed Mortar.
Pre-treatment of ceiling joint with 6" (150 mm) wide, treatment of LATICRETE 9235 Waterproofing
Membrane.
Lighting fixture waterproofing membrane pre-treatment. The vapor retarder, insulation board, mud
bed, and LATICRETE 9235 Waterproofing Membrane are all clearly visible.
Waterproofing treatment of corner and floor with LATICRETE® 9235 Waterproofing Membrane.
Completed installation of LATICRETE 9235 Waterproofing Membrane over all seat, wall, ceiling and
floor surfaces.
Installation of tile onto LATICRETE 9235 Waterproofing Membrane using LATICRETE 254 Platinum.
Continuing installation of tile onto all surfaces using LATICRETE 254 Platinum.
Finished installation of 2" x 2" (5 cm x 5 cm) vitreous tile using LATICRETE® 254 Platinum. Notice the
cut-out for the emergency call switch.
Installation of LATICRETE 1500 Sanded Grout mixed with LATICRETE 1776 Grout Enhancer on ceiling,
walls and seat.
Finished floor installation of tile. Floor and seats are sloped 1/4" per foot (6 mm per 300 mm) to
the drain.
Finished wall showing door, light and emergency call switch installations.
Tile provided and installation done by: Coastal Tile and Marble, Branford, CT.
Q: Do I need a shower pan for my steam room/ Q: Should the vapor barrier drape into the
steam shower? shower pan liner?
Yes. A shower pan is an extremely important Yes. As water vapor permeates through the tile
component of any steam room, steam shower or installation and the waterproofing membrane,
regular shower and may be required per building the moisture will hit the impermeable vapor
code. A vinyl liner (or other vapor impermeable barrier. The moisture will eventually condense
material which can be used as a shower pan into water form and, by gravity, work its way
membrane) is perfectly suited for this type of down into the shower pan. A moisture barrier
application and must be properly installed to that has been improperly placed means that
protect against damage caused by water. the water will end up on the outside of the
shower pan. This can lead to structural damage
Q: Does the floor of the steam room require a and mold/health problems.
pitch to drain?
Yes. In fact, the pitch must exist in the sub-floor Q: Where should a vapor barrier be placed in a
so water that accumulates in the shower pan steam room installation?
flows towards the drain weep holes. If the sub- According to ES-SR613 the vapor barrier
floor is properly pitched then the depth of the would be placed directly onto the concrete
mortar bed can remain a consistent depth. The or masonry. In ES-SR614 the vapor barrier
pitch to drain for steam room/steam shower is placed directly onto the face of the studs
floor installations is recommended at 1/4" per (steel or wood), directly underneath (in contact
foot (6 mm per 300 mm). with) the cement backer board and fastened
with corrosion resistant fasteners. A spot of
Q: Should I conduct a flood test in my steam LATICRETE Latasil™ should then be placed
room prior to setting tile? onto each fastener to help prevent moisture
Yes. It is important to verify that the shower penetration through the fastener hole. Please
pan does not leak prior to setting tile. For more refer to the appropriate execution statement
information on flood testing requirements and located in this design manual or at www.
procedures, please refer to TDS 169 “Flood laticrete.com/ag for more information.
Testing Procedures” at www.laticrete.com.
Q: If there is no “water” in a steam room then
Q: Why do I need a vapor barrier in my why do I need a waterproofing membrane?
steam room/steam shower if I have a In actuality, there is water in a steam room; a
waterproofing membrane? significant amount of water. Water enters the
LATICRETE® Hydro Ban™ and LATICRETE room as a vapor, meaning it must be heated to a
9235 Waterproofing Membrane, like most temperature greater than 212°F (100°C). As the
waterproofing membranes, prevents water from steam enters the room it will condense when
penetrating past the membrane. However, like it hits dew point and the resulting water must
most waterproofing membranes, LATICRETE have an escape route. Directly or indirectly the
Hydro Ban and LATICRETE 9235 Waterproofing condensed water in the steam room will end
Membrane are vapor permeable. Moisture up going through the drain.
vapor will be able to permeate through the
membrane, water itself will not. In a steam Q: Do I require a waterproofing membrane on
room environment the moisture that enters the walls and ceiling?
the room is in vapor form and is also under Yes. The waterproofing membrane is required
some pressure. The vapor barrier is designed throughout the steam room/steam shower
and placed to keep the moisture vapor from installation to help limit the amount of moisture
entering into areas where the vapor will vapor that reaches the vapor barrier. The low perm
condense and possibly cause structural and rating of LATICRETE Hydro Ban and LATICRETE
mold/health problems. 9235 Waterproofing Membrane means that a
very low amount of water will come in contact
with the vapor barrier.
84 Tiled Steam Room and Steam Shower – Technical Design Manual
Section 6: Steam Room Frequently Asked Questions
Q: Does a steam room/steam shower ceiling Q: What LATICRETE grout should I use for my
require a pitch? steam room/steam shower?
Yes. The ceiling requires a pitch to prevent The ideal grout would be LATICRETE
water droplets from falling onto steam room SpectraLOCK®† PRO Grout. LATICRETE
occupants. It also prevents water from staying SpectraLOCK PRO Grout provides an extremely
on the ceiling surface for extended periods of low absorption rate, antimicrobial protection,
time. The recommended pitch for a ceiling in a a significant reduction in efflorescence
steam room is 2" per foot (50 mm per 300 mm) problems, and ease of installation making
minimum. it the ideal choice for a steam room/steam
shower environment. LATICRETE PermaColor™
Q: Do I need a vapor barrier on the ceiling? Grout^ is also suitable for steam room use.
Yes. Water vapor in a steam room will
definitely come in contact with the ceiling. Q: Does LATICRETE Latasil™ require
The vapor barrier must be placed within the the LATICRETE 9118 Primer prior to
entire confines of the steam room structure so application?
that no moisture vapor can transpire into the Yes. Due to the amount of moisture in a steam
surrounding building structure or spaces. room/steam shower, it is a good idea to treat
this type of installation the same way that you
Q: Is insulation required in my steam room/ would treat a swimming pool LATICRETE Latasil
steam shower? application.
This is a question that should be answered by
the project design professional. Applications Q: If I use a cement based grout will
and project conditions may vary and will have a efflorescence be a concern?
direct impact on the use of insulation. The use Yes. Efflorescence can be a concern when
of a suitable insulation should dramatically a portland cement based grout is used in a
improve the performance of the steam room/ steam room installation. The high amount of
steam shower and help to conserve energy. moisture and the fact that the moisture will
work its way back out through the grout can,
Q: How do I waterproof the penetrations very possibly lead to efflorescence problems.
(e.g. steam jets, pipes, drains, lights, etc…) An easy way to reduce efflorescence problems
in my steam room/steam shower? is to use LATICRETE SpectraLOCK PRO Grout.
For steam jets and pipes you can refer to Detail
ES-P605 (located in Section 4.4) for direction. Q: What regular maintenance is needed for a
For drains you can refer to detail WP302 (located steam room?
in Section 4.5). Outside of maintaining the steam generation
unit (contact steam generation unit
Q: What LATICRETE Thin-Set should I use for manufacturer for more information) a steam
my steam room installation? room requires some regular maintenance.
LATICRETE 254 Platinum, a premium Establish a suitable and consistent cleaning
multipurpose thin-set mortar is ideal for regimen for long term, safe and healthy steam
installing most types of tile or stone in a room enjoyment.
steam room/steam shower environment. For
installation of resin backed stone, moisture
sensitive tile or stone, mesh backed mosaics,
or dot mounted mosaics it is recommended
that LATAPOXY® 300 Adhesive be used. For
more information please contact LATICRETE
Technical Services at support@laticrete.com
ABSORPTION – the relationship of the weight BOND STRENGTH – a bond coat’s ability to resist
of water absorbed to the weight of the dry separating from the tile and underlayment,
specimen, expressed in percentages measured in pounds per square inch (psi)
AGGLOMERATE TILE – a man-made stone BROWN COAT – the second coat in a three-coat
product generally consisting of either crushed render or mortar application
marble, granite or quartz chips with a matrix of
resins and mineral pigments. Usually available BULLNOSE – a trim tile with a convex radius on
in assorted sizes as well as large slabs. one edge
APA – American Plywood Association CEILING SLOPE – steam rooms require ceilings
to be pitched 2" per foot (150mm per m) to
ASME – American Society of Mechanical prevent condensation from dripping on steam
Engineers room occupants
ASTM – American Society for Testing and CEMENT – binding component of mortars and
Materials concrete (usually portland cement)
BACK-BUTTER – the spreading of a bond coat CEMENT BACKER BOARD – a backer board,
to the back of ceramic tile and stone just before usually composed of cement, fillers and
the tile is placed fiberglass mesh, designed for use with ceramic
tile in wet areas
BACK MOUNTED MOSAIC TILE – mosaic tile
which may have perforated paper, fiber mesh, CEMENT GROUT – a cementitious mixture of
resin or other suitable material bonded to the portland cement, sand or other ingredients,
back of each tile which becomes an integral pigments and water, to produce a water
part of the tile installation resistant, uniformly colored material used to
fill the joints between tile units
BICOTTURA – method for producing tile by
firing it twice (first fire is for body, second is CEMENTITIOUS – having the properties of
to fuse glazes or patterns in glaze onto the cement
body).
CERAMIC TILE – a surfacing unit, usually
BISQUE – the refined mixture of clay, water and relatively thin in relation to facial area, made
additives that has been shaped into the body from clay or a mixture of clay and other
of a tile materials called the body of the tile, and having
either a glazed or unglazed face
BODY – the structural portion of a ceramic tile
CHEMICAL RESISTANCE – the resistance
BOND COAT – a material used between the offered by products to physical or chemical
back of a tile and the substrate. Suitable bond reactions as a result of contact with or
coats for a steam room application include latex immersion in various solvents, acids, alkalis,
portland cement mortar and epoxy adhesive. salts, etc…
CRAZING – the cracking that occurs in fired GLAZED TILE – tile with a fused impervious
glazes or other ceramic coatings due to critical facial finish composed of ceramic materials
tensile stresses fused to the body of the tile
CURING – maintenance of humidity and GROUT – a material used for filling the joints
temperature of freshly placed mortar or grout between tile
to assure satisfactory hydration of cement and
proper hardening of mortar or grout GROUTING – the process of filling tile joints
with grout
CUSHIONED EDGED TILE – tile on which the
facial edges have a distinct curvature that IAPMO – International Association of Plumbing
results in a slightly recessed grout joint and Mechanical Officers
EFFLORESCENCE – the residue deposited on MARBLE TILE – marble cut into tiles and
the surface of a material (usually cement grout) available in various finishes
by crystallization of soluble salts
MEDIUM BED – tile setting material that has a PLUMB – perpendicular to a true level
finished thickness between 3/8" (9 mm)
PORCELAIN TILE – a ceramic tile that is dense,
METAL LATH – expandable diamond metal impervious and has an absorption rate of
lath material which is mechanically fastened <0.5%
to a surface and onto which a mortar bed is
applied POT LIFE – the period of time during which a
material maintains its workable properties
MONOCOTTURA – method of producing tile by after it has been mixed
a single firing
SCRATCH COAT – a mortar bed, applied as the
MORTAR BED – the final coat of mortar on a first coat of a mortar on a wall or ceiling, whose
wall, floor or ceiling before the installation of surface is scratched or roughened so that
tile subsequent mortar coats will bond properly
MOSAIC TILE – any tile (ceramic, porcelain SEALANT – an elastomeric material used to fill
or stone) with a facial dimension of less than and seal expansion and control joints, prevents
6 in2 which usually comes in sheets (paper face the passage of moisture and does not allow
mounted, dot mounted, back mounted, etc…) horizontal and lateral movement to affect the
tile installation
MUD – see mortar bed
SELF-SPACING TILE – tile with lugs, spacers or
NON-VITREOUS TILE – tile with an absorption protuberances on the sides which automatically
rate greater than 7.0% space the tile for the grout joint
NOTCHED TROWEL – a trowel with a serrated SEMI-VITREOUS TILE – tile with an absorption
or notched edge which is used to gauge the rate between 3.0 – 7.0%
amount of mortar or adhesive to a specific
thickness when setting tile SHELF LIFE – the maximum period of time that
an item can be stored before it is used
OPEN TIME – the period of time that a bond
coat retains its ability to adhere to the tile and SHOWER PAN – a waterproof shower floor
bond the tile to the substrate membrane which is specifically recognized
for use in this application – required for steam
PENCIL ROD – reinforcing rod with a diameter rooms as well as showers per local building
no greater than 1/4" (6 mm) code
PINHOLES – imperfections in the surface of tile SLAKE – the process of mixing a cementitious
or grout mortar or grout, allowing it to stand for 5 – 10
minutes and then remixing. This process makes
PLASTER – a cementitious material and
sure that the moisture in the mix penetrates
aggregate that, when mixed with a gauging
lumps in the dry components, making it easier
liquid, forms a plastic mass or paste which
to complete the mixing procedure.
when applied to a surface, adheres to it and
subsequently hardens, preserving in a rigid
state the form or texture imposed during
installation
SLURRY COAT – a coat of thin-set used to bond WET AREA – surfaces that are either soaked,
a mortar bed to a cementitious substrate saturated, or regularly and frequently subjected
to moisture or liquids (usually water), such as
SPACERS – plastic or rubber units used to saunas, steam rooms, showers, swimming
separate and provide consistent spacing pools, and more
between tiles
91
92 Tiled Steam Room and Steam Shower – Technical Design Manual
©2009 LATICRETE International, Inc. All rights reserved. No part of this publication (except for previously
published articles and industry references) may be reproduced or transmitted in any form or by any
means, electronic or mechanical, without the written permission of LATICRETE International, Inc.
The information and recommendations contained herein are based on the experience of the author
and LATICRETE International, Inc. While we believe the information presented in these documents to be
correct, LATICRETE International, Inc. and its employees assume no responsibility for its accuracy or for
the opinions expressed herein. The information contained in this publication should not be used or relied
upon for any specific application or project without competent examination by qualified professionals
and verification of its accuracy, suitability, and applicability. Users of information from this publication
assume all liability arising from such use.
www.laticrete.com
India: +91.40.3041.3100
Latin America: +1.203.393.0010
Middle East: +971.7.244.6396
South East Asia: +65.6515.3028
DS–125.0–1109
©2009 LATICRETE International, Inc.
LATICRETE, LATAPOXY, SPECTRALOCK and the logo are Registered Trademarks of LATICRETE International, Inc.
Microban is a registered trademark of Microban Products Company.
Kevlar is a registered trademark of Dupont Products Company.
GREENGUARD Indoor Air Quality Certified® Product. 9