Professional Documents
Culture Documents
H RA E JOURNAL
Journal’s
The following article was published in ASHRAE Journal, April 2000. © Copyright 2000 American Society of Heating, Refrigerating and Air-
Conditioning Engineers, Inc. It is presented for educational purposes only. This article may not be copied and/or distributed electronically or in paper
form without permission of ASHRAE.
A
utomatic dampers control airflow in HVAC systems. of the control system must make the pressure in the mixing box
Applications include controlling mixed air tempera- (Point A) less than atmospheric.
ture in economizer cycles and airflow to the space Similarly, the total system pressure drop for selecting the
in variable air volume systems. Selecting and sizing exhaust/relief damper is the pressure drop between Point B
dampers to provide linear control action aids proper and outdoors. For determining the damper authority, the total
system operation. With linear control, a given change in damper system pressure drop includes the pressure drop across the
position produces a proportional change in air quantity. If con- relief duct and louver. It does not include the pressure drop
trol is not linear, a given change in control signal might produce across the exhaust/relief damper.
a consistent change in damper position but a different change The total system pressure drop for selecting the return damper
in air quantity. The result is unstable or inaccurate control. may be less obvious. It is the pressure drop from Point B (the
The resistance of the wide open damper can be expressed as discharge of the return fan) to Point A (the mixing box plenum).
a fraction of the total system resistance. That fraction is called The return air damper does not control the flow through the
“Damper Authority” or “Characteristic Ratio.” return fan. It simply proportions the flow between the relief duct
Open Damper Resistance and the return air duct. The pressure at Point B must always be
Damper Authority (%) = × 100% greater than atmospheric or air will not leave the system.
Total System Resistance For a VAV box, the total system pressure drop is the pressure
The resistance is a pressure drop, so from the primary duct to the space. A separate control loop
Open Damper Pressure Drop (typically variable speed drive, variable inlet vanes, or fan dis-
Damper Authority (%) = × 100% charge damper) controls fan capacity to maintain relatively con-
Total System Pressure Drop stant pressure in the primary air duct. The VAV box damper
Note: Total system resistance and total system pressure drop does not appreciably affect the flow through the main duct. It
are for the system without the wide open damper. only affects the portion of the main duct flow that passes
It is important to realize that “Total System Resistance” or through the VAV box. Therefore, the total system pressure drop
“Total System Pressure Drop” relates only to the part of the for a VAV box damper is from the primary air duct to the space.
system where the damper controls the flow. It is not the entire
system pressure drop or the fan total static pressure. The total Damper Types
system pressure drop for selecting dampers is usually the pres- Figure 2 shows the two damper arrangements used in our
sure drop from a constant pressure point in the system to the industry.
destination for the air.
Figure 1 shows a traditional airside economizer cycle with a About the Authors
return fan. Evans J. Lizardos is founder and president of Lizardos Engineering Associates,
The total system pressure drop for the outside air damper is Mineola, Long Island, N.Y. He is a past Handbook chairman, and serves on
the pressure difference between outside air and Point A, the TC.10.9, Refrigeration Applications for Foods and Beverages. Ken Elovitz is an
mixing box plenum. The outside air damper only controls the engineer and in house counsel for Energy Economics, Foxboro, Mass. He is
flow through the weather louver, the damper, and the outside ASHRAE Journal’s Practical Guide editor.
V VP
VP FT- 1C FT- 1 FT- 2C FT- 2
Example 2: Return Air Damper Design 2 ,1 0 0 0.14 0.22 0.06 0.18 0.46 30% Parallel
In most cases, the return air damper and associated ductwork
pressure drop from the return fan discharge to the air-handling 2 ,5 0 0 0.20 0.10 0.06 0.10 0.40 50% Parallel
unit mixing box must dissipate a differential pressure of more
April 2000 ASHRAE Journal 39
Figure 3: Damper authority curves of installed parallel blade
dampers.
Advertisement in the print edition formerly in this space.
Example: Damper Pressure Drop (DPR) + TSD must equal
0.60 in. w.g. (150 Pa)
for 30% authority, DPR = 0.30 × TSD
DPR + TSD = 0.3 × TSD = TSD =0.60
1.3 TSD = 0.60; TSD = 0.46
From the table, the return air damper should be sized at face
velocity of 1,400 to 1,600 fpm (7 to 8 m/s) if it is an opposed blade
damper or 2,200 to 2,400 fpm (11 to 12 m/s) if it is a parallel blade
damper. Whichever damper is selected, duct and fitting pressure
drop of 0.40 to 0.55 in. w.g. (100 to 135 Pa) must be included to
achieve damper authorities of 10% to 15% for opposed blade
dampers and 30% to 50% for parallel blade dampers.
DP R -V DP R FT- 1 FT- 2 MP D T SD DA
DA DP R Ty p e
0.5-
1 ,4 0 0 0.06 0 0.24 0.34 10% Opposed
4
0.5-
1 ,6 0 0 0.08 0 0.22 0.22 15% Opposed
2
0.4-
2 ,1 0 0 0.14 0 0.16 0.16 30% Parallel
6
0.4- Figure 5: Economizer cycle damper arrangement.
2 ,5 0 0 0.20 0 0.10 0.10 50% Parallel
0
From the previous table, the return air damper should be
From the table above, the outdoor air damper should be sized at sized at a face velocity of 1,400 to 1,600 fpm (7 to 8 m/s) when
face velocity of 1,400 to 1,600 fpm (7 to 8 m/s) when using using opposed blade dampers and 2,100 to 2,500 fpm (11 to 12
opposed blade dampers. It should be sized for 2,200 to 2,400 m/s) when using parallel blade dampers.
fpm (11 to 12 m/s) when using parallel blade dampers. Which-
ever damper is selected, a duct and fitting pressure drop of 0.40 Example 5: Exhaust/Relief Air Damper Design
to 0.55 in. w.g. (100 to 135 Pa) must be added to achieve damper in an Exhaust/Relief Fan Economizer Cycle
authorities of 10% to 15% for opposed blade dampers and 30% The exhaust air damper controls a total system pressure drop
to 50% for parallel blade dampers. of about 0.80 in. w.g. (200 Pa). This pressure drop is the differ-
ence between the pressure required to push air out the exhaust
Example 4: Return Air Damper Design in an duct and louver (0.30 in. w.g./75 Pa) and the pressure in the
Exhaust/Relief Fan Economizer Cycle return duct at the inlet to the exhaust/relief fan (–0.50 in. w.g./
The total system pressure drop for the return air damper is 125 Pa).
the pressure drop from the space to the mixing box. It is in the
order of 0.6 in. w.g. (150 Pa). DP R -V DP R T SD DA
DA DP R Ty p e
I n l e t Di a m e t e r
CFM FP M VP
VP DP R T SD DA
DA
S i z e ( i n i n ch e s )
Figure 6: The return air fan economizer cycle (Examples 1
4 225 2,600 0.42 0.21 0.70 30% & 2).
6 500 2,600 0.42 0.21 0.70 30%
10
10 1,400 2,600 0.42 0.21 0.70 30%
12
12 2,000 2,600 0.42 0.21 0.70 30%
14
14 3,000 2,600 0.42 0.21 0.70 30%
16
16 4,000 2,600 0.42 0.21 0.70 30%
Conclusion
This article introduces the concept of damper authority
and provides examples of how the concept can be used to
design for linear damper control. The typical pressure drops
used in the examples are just that—typical. The techniques
presented here can be applied to actual jobs by calculating
actual pressure drop for the actual system and selecting ve-
locities accordingly. Since damper authority is defined as the
ratio of the damper pressure drop to the system pressure drop
without the damper, the pressure drop through the wide open
damper must be added to the “system pressure drop” when
sizing the fan.
Please circle the appropriate number on the Reader Service Card at the back of
the publication.
Extremely Helpful ........................................................................................................ 458
Helpful ........................................................................................................................ 459
Somewhat Helpful ...................................................................................................... 460
Not Helpful ................................................................................................................. 461