Introduction Bus bar is subdivided into sections, each of which is separately protected. A fault in one section does not involve the tripping of the complete station. Important load can be supplied from the healthy sections, and will not suffer any interruption of supply if one section is tripped.
Regional Lab SR-1 2
Need for bus bar protection In its absence fault clearance takes place in zone-II of distance relay by remote end tripping. This means slow and unselective tripping and wide spread back out.
Regional Lab SR-1 3
Trip logic ( 3 output) Initiates main breaker trip coil-1 Initiates main breaker trip coil-2 Initiates BFR for main breaker Block A/R of main breaker Send direct trip signal to remote end in channel 1&2 Initiates disturbance recorder and event logger. Regional Lab SR-1 4 Effect of delayed clearance
Greater damage at fault point.
Indirect shock to connected equipments like shafts of generator and windings of transformer.
Regional Lab SR-1 5
Topics of Discussion
Basic criteria for bus bar
protection. High impedance versus low impedance protection. Effect of CT saturation on protection. Stability for external faults.
Regional Lab SR-1 6
Criteria for operation The saturation voltage of the involved CT’s must be at least twice the selected operate value of the relay and all CT’s must have identical turns ratios. Non-linear resistors are used at the CT summation point in each phase for limitation of high peak voltages during internal faults. The secondary saturation E.M.F of current transformers should be at least twice the operate voltage of the relay in order to ensure fast operation for internal faults. It is to be ensured that the CT’s and current circuits of the bus bar protection are correctly connected.
Regional Lab SR-1 7
High impedance Type In high impedance type, relatively high impedance is connected in series in the differential circuit and it has been designed with filter circuits, which will attenuate the DC component. This type setup is found to be inoperative even for the most extreme CT saturation. High impedance unbiased differential protection is used for the protection of bus bar. E.g. RADHA (ABB)
Regional Lab SR-1 8
Low impedance type
In conventional low impedance
differential protections, considerable spill currents can occur during thro’ faults, due to saturation of the current transformers. The saturation is primarily caused by the DC transients of the fault current.
Regional Lab SR-1 9
Percentage biased Differential type
Free of any need for matched Ct
characteristic or ratios, low leakage reactance or resistance. Insensitive to CT saturation. Stable for even infinite fault level.
Regional Lab SR-1 10
Effect of CT saturation
Regional Lab SR-1 11
Stability for external faults The maximum permitted primary current must be larger than the largest fault current, which can arise at external faults. The maximum fault current is determined from the short-circuiting power of the network in this point. During normal conditions, the E.M.F’s induced in current transformers are opposed and equal. Thus the voltage across the relay will be zero. In the event of saturation of current transformers during an external fault a voltage will form across the relay. This differential voltage will reach its maximum when one of the current transformer is completely saturated and the other current transformer is entirely unaffected by saturation.
Regional Lab SR-1 12
Stability …Contd. The magnetizing impedance of the saturated current transformer becomes zero. As the impedance of the relay circuit is much larger than the combined resistance of the secondary circuit, the current will be forced thro’ the secondary winding of the saturated current transformer. It follows that the maximum voltage which occur across the relay circuit during an external fault will be equal to product of current thro’ the saturated CT and the combined resistance of saturated CT. However it never happens that one current transformer is completely saturated while the other not. As the weaker current transformer begins to saturate the voltage developed across the relay circuit will transfer the burden from the weaker to the stronger CT.
Regional Lab SR-1 13
What This Means Add a strong statement that summarizes how you feel or think about this topic Summarize key points you want your audience to remember
Regional Lab SR-1 14
Next Steps Summarize any actions required of your audience Summarize any follow up action items required of you