DESIGN EXAMPLE 1 CHS COLUMN The circular hollow section column to be designed is an interior column of a multi-storey building. The column is simply supported at its ends. The inter-storey height is 3,50 m.
NEd N
sd
Structure Simply supported column, length between supports: l = 3,50 m Actions Permanent and variable actions result into a vertical design compression force equal to: NEd = 250 kN Cross-section properties Try a 159 4 CHS, grade 1.4401 Geometric properties d = 159 mm t A = 19,5 cm I 3 Wpl Wel = 73,6 cm
Material properties 0,2% proof stress = 220 N/mm2. Take fy = 220 N/mm2. E = 200 000 N/mm2 and G = 76 900 N/mm2 Classification of the cross-section
= 1,01
d 159 = = 39,8 t 4
Table 4.2
Section in compression :
117
Job No. Job Title Institute of Steel Construction Mies-van-der-Rohe-Str. 1 52074 Aachen, Germany Fax: +49-(0)241/ 88-20140 Subject
OSM 466
Sheet
of
Rev
Client
HS AB/IR JBL
CALCULATION SHEET
ECSC
For Class 1,
Section 4.7.3
Eq. 4.25
= 390 kN Section 5.3.3 Eq. 5.2a
Nc,Rd =
Nb,Rd = A f y M1
= 0,5 1 + ( 0 ) + 2
+ 2 2
A fy N cr
0, 5
Eq. 5.5a
N cr =
2 EI
L cr
2
2 200000 585,3 10 4
(3,50 10 )
= 0,67
3 2
10 3 = 943,1 kN
Table 5.1
= 0,79
0,5
= 0,83
Nb,Rd = 0,83 19,5 220 10-1 / 1,1 = 323,7 kN The applied axial load is NEd = 250 kN. Thus the member has adequate resistance to flexural buckling.