You are on page 1of 7

Traducido por mccloud_1 revisin 1 fecha 30/07/2010

1
6.3 Slab Punching Shear Check

The distribution of stresses close to concentrated loads or
reaction points in reinforced and prestressed concrete
slabs is quite complex. Punching shear is one particular
failure mode recognized by design codes for which an
elastic plate bending analysis may not provide adequate
stress distribution. Most codes use empirical methods
based on experimental verification to check against
punching shear failures. SAFE automates this check for
common geometries. If the check results in a punching
shear ratio greater than unity (i.e., punching failure), SAFE
will design punching shear reinforcement. The SAFE
procedure for the punching shear check carried out for
each column, for each design combination is as follows:





Locate the critical section around the column or
point load. SAFE reports whether it assumed the
column to be an interior, edge, or corner column.
This determination is based on whether the slab
is present within 10 times the slab thickness
along the column edges. A column is classified
as a corner column when two slab edges are
found within 10 times the slab thickness. A
column with only one slab edge within 10 times
the slab thickness is classified as an edge
column, and a column is classified as interior
when no slab edges are found within 10 times
the slab thickness. For single footings, this
determination is based on the minimum area of
the critical section.



Check that each slab element in the area
enclosed between the face of the column and the
critical section for punching shear has the same
slab property label. If this is not the case, the
minimum slab thickness within the punching
shear perimeter is used.

Use the net shear to check punching shear if a
point load or column (call it load/column A) is
within the critical section for punching shear for
another point load or column (call it load/column
B).


Calculate punching shear based on net
forces in the slab when line objects (beams,
walls, or releases) frame into a column.


Calculate the reactive force and moments at the
column for the combination. The shear and
moment values used in the punching shear
check are reduced by the load (or reaction) that
is included within the boundaries of the punching
shear critical section.

Calculate the distribution of shear stress around
the critical section.

Obtain the shear capacity of the critical section.

6.3 Comprobacin de Punzonado en Losas.

La distribucin de tensiones cerca de cargas concentradas
o puntos de reaccin en losas de hormign armado y
pretensado es bastante complejo. El Punzonamiento es un
modo de fallo particularmente sealado por los cdigos de
diseo para el cual un anlisis de una placa de flexin
elstica puede no proporcionar la distribucin de tensin
adecuada. La mayora de los cdigos usan mtodos
empricos basados en la comprobacin experimental para
comprobar los fallos contra la perforacin de cizalla o
punzonado. SAFE automatiza este chequeo para
geometras comunes. Si la verificacin de los resultados
tienen un ratio de punzonamiento mayor que la unidad (es
decir, falla por perforacin), SAFE diseara la armadura
transversal por punzonado. El procedimiento que sigue
SAFE para el chequeo del punzonamiento que se efecta
para cada columna, para cada combinacin de diseo es
el siguiente:

Localiza la seccin crtica alrededor de la
columna o de puntos de carga. SAFE informa de
si se asume la columna como interior, de borde,
o una columna de esquina. Esta determinacin
se basa en si la losa est presente en 10 veces
el espesor de la losa a lo largo de los bordes de
la columna. Una columna se clasifica como una
columna de esquina cuando dos bordes de la
losa se encuentran en 10 veces el espesor de la
losa. Una columna con un solo borde de losa si
se encuentra en 10 veces el espesor de la losa
se clasifica como una columna de borde, y una
columna se clasifica como interior cuando no
hay cantos de los forjados se encuentran dentro
de 10 veces el espesor de la losa. Para zapatas
individuales, esta determinacin se basa en la
superficie mnima de la seccin crtica.

Chequea que cada elemento de una placa en la
zona delimitada entre la cara de la columna y la
seccin crtica de punzonamiento tiene la misma
etiqueta de propiedad de la losa. Si este no es el
caso, se utiliza la losa de mnimo espesor en el
permetro de punzonamiento.

Utiliza la red de fuerza cortante para comprobar
si el punzonamiento en un punto de carga o de
la columna (denominado carga / columna A) se
encuentra dentro de la seccin crtica de
punzonamiento para otro punto de carga o de la
columna (llamada cargua / columna B).

Calcula el punzonamiento basado en las
fuerzas netas de la losa cuando los objetos
de lnea (vigas, paredes, o enlanzamientos)
caen en una columna.

Calcula la fuerza de reaccin y momentos en la
columna para la combinacin. El corte y los
valores utilizados en el momento de verificacin
para punzonamiento se reducen por la carga (o
reaccin) que se incluye dentro de los lmites de
la seccin crtica de punzonamiento.

Calcula la distribucin de esfuerzo cortante
alrededor de la seccin crtica.

Obtiene la capacidad a cortante de la seccin
crtica.

Traducido por mccloud_1 revisin 1 fecha 30/07/2010
2
Compare the shear stress distribution with the
shear capacity. The comparison is reported as a
ratio for the worst combination. A value above
1.0 indicates failure.

SAFE designs rebar ties or stud rails when such
options are activated in the punching shear
design overwrites. The details of rebar ties or
stud rails are documented in the Reinforced
Concrete Design Manual and the Post-
Tensioned Concrete Design Manual.


Design overwrites are available to modify the
location type, punching shear perimeter,
openings in the slab, and reinforcement pattern,
when the punching shear parameters computed
need to be changed.


For computing the punching parameters, the
following assumptions are used:

Punching shear is calculated for columns
punching through a slab or a drop panel. SAFE
also checks the drop panel punching through a
slab. The effect of column capitals is included in
the punching shear calculation.


SAFE uses the effective depth for computing the
punching shear. The concrete cover to rebar is
taken from the design preferences unless a
design strip is present. In that case, the rebar
cover is taken from the design strip.



Openings within 10 times the slab thickness are
automatically included in the punching shear
calculations. The slab edge within the punching
zone radius is subtracted from the punching
shear perimeter.



The vertical component of prestressing force is currently
ignored in computing the punching shear capacity.


Compara la distribucin del esfuerzo cortante
con la capacidad de corte. La comparacin se
reporta como una relacin de la peor
combinacin. Un valor superior a 1,0 indica falla.

SAFE disea solapes de barras o rieles
montantes cuando dichas opciones se
encuentran activas en el punching shear design
overwrites. Los detalles de los solapes de barras
o rieles montantes estn documentados en el
Manual de Diseo de Hormign Armado y el
Manual de Diseo de Hormign Post-Tensados.

Design overwrites se encuentran disponibles
para modificar el tipo de ubicacin, la abertura
del permetro de corte, las aberturas en la losa, y
el patrn de refuerzo, cuando los parmetros de
punzonamiento calculados necesitan ser
cambiados.

Para calcular los parmetros de punzonado, las
hiptesis que se utilizan son las siguientes:

El Punzonamiento se calcula para las columnas
que punzonan a travs (por encima) de una losa
o un panel de losa. SAFE tambin comprueba el
punzonado del panel debajo de una losa. El
efecto de los capiteles de columnas est incluido
en el clculo de punzonamiento.

SAFE utiliza la altura til para el clculo del
punzonamiento. El recubrimiento de barras de
refuerzo se ha tomado de las preferencias de
diseo a menos que una franja de diseo
(design strip) este presente. En ese caso, el
recubrimiento de la armadura se ha tomado de
la franja de diseo.

Las aberturas con 10 veces el espesor de la losa
se incluyen automticamente en los clculos de
punzonamiento. El borde de la losa dentro del
radio de la zona de perforacin se resta del
permetro de punzonamiento.















La componente vertical de la fuerza de pretensado es ignorada
para el momento del clculo de la capacidad de
punzonamiento


Fuente: Section 6.3 Key Features and Terminology. SAFE- v12.1.0 Enero 2009




Traducido por mccloud_1 revisin 1 fecha 30/07/2010
3

Design for ACI 318-08

2.6 Slab Design

2.6.2 Check for Punching Shear

The algorithm for checking punching shear is detailed in
the section entitled Slab Punching Shear Check in the
Key Features and Terminology manual. Only the code-
specific items are described in the following sections.


2.6.2.1 Critical Section for Punching Shear

The punching shear is checked on a critical section at a
distance of d/2 from the face of the support (ACI
11.11.1.2). For rectangular columns and concentrated
loads, the critical area is taken as a rectangular area with
the sides parallel to the sides of the columns or the point
loads (ACI 11.11.1.3). Figure 2-4 shows the auto punching
perimeters considered by SAFE for the various column
shapes. The column location (i.e., interior, edge, corner)
and the punching perimeter may be overwritten using the
Punching Check Overwrites.



2.6.2.2 Transfer of Unbalanced Moment

The fraction of unbalanced moment transferred by flexure
is taken to be
f
M
u
and the fraction of unbalanced
moment transferred by eccentricity of shear is taken to be

v
M
u
.


For flat plates, v is determined from the following
equations taken from ACI 421.2R-07 [ACI 2007] Seismic
Design of Punching-Shear Reinforcement in Flat Plates.


For interior columns,

Diseo por ACI 318-08 (COVENIN 1753-06)

2.6 Diseo de Losas

2.6.2 Chequeo por punzonado.

El algoritmo de control de punzonamiento se detalla en la
seccin titulada " Slab Punching Shear Check " en el
manual Key Features and Terminology. Slo los puntos
especficos de cdigo se describen en las secciones
siguientes.

2.6.2.1 Seccin Critica para Punzonado

El punzonamiento se verifica en una seccin crtica a una
distancia de d/2 desde la cara del soporte (ACI 11.11.1.2).
Para las columnas rectangulares y las cargas
concentradas, la zona crtica se toma como un rea
rectangular con los lados paralelos a los lados de las
columnas o las cargas de punto (ACI 11.11.1.3). La Figura
2-4 muestra los permetros de perforacin automtica
considerada por SAFE para las formas diversas de
columna. La ubicacin de columna (es decir, el interior,
borde, esquina) y el permetro de perforacin se puede
sobrescribir con Punching Check Overwrites.


















2.6.2.2 Transferencia de Momentos no Balanceados.

La fraccin del momento transferido por flexin no
balanceada se toma como fMu y la fraccin del momento
desequilibrado transferido por excentricidad de cortante se
toma como vMu.


1 2
1
1 0,67
f
b b
=
+
(Covenin 1753 seccin 11.9.6 ecuacin 11-37b)
1
v f
=
(Covenin 1753 seccin 11.9.6 ecuacin 11-37a)

Para las placas planas, v se determina a partir de las
siguientes ecuaciones tomadas de ACI ACI 421.2R-07
[2007] Diseo Ssmico de punzonamiento-Refuerzo en
Placas Planas.

Para columnas Interiores,






Traducido por mccloud_1 revisin 1 fecha 30/07/2010
4

For edge columns,


For corner columns,


where b1 is the width of the critical section measured in the
direction of the span and b2 is the width of the critical
section measured in the direction perpendicular to the
span. The values lx and ly are the projections of the shear
critical section onto its principal axes, x and y, respectively.

2.6.2.3 Determine Concrete Capacity

The concrete punching shear stress capacity is taken as
the minimum of the following three limits:


where, c is the ratio of the maximum to the minimum
dimensions of the critical section, bo is the perimeter of the
critical section, and s is a scale factor based on the
location of the critical section.


A limit is imposed on the value of '
c
f as:


2.6.2.4 Determine Capacity Ratio

Given the punching shear force and the fractions of
moments transferred by eccentricity of shear about the two
axes, the shear stress is computed assuming linear
variation along the perimeter of the critical section. The
ratio of the maximum shear stress and the concrete
punching shear stress capacity is reported as the punching
shear capacity ratio by SAFE. If this ratio exceeds 1.0,
punching shear reinforcement is designed as described in
the following section.







Para columnas laterales,








Para columnas de esquina,






donde b1 es el ancho de la seccin crtica medida en el
sentido del claro y b2 es la anchura de la seccin crtica se
mide en la direccin perpendicular al rango de medicin.
Los valores lx y ly son las proyecciones de la seccin crtica
de corte en sus ejes principales, x e y, respectivamente.

2.6.2.3 Determinacin de la capacidad del Concreto

La capacidad de esfuerzo por punzonado del concreto se
toma como el mnimo de las tres siguientes lmites:

0
0
0
0
1,06
0,53 '
min 0,53 '
1,06 '
c
c
s
c c
c
f b d
d
f b d
b
f b d


| |
+
|
\

| |
= +
|
\

(Covenin 1753 seccin 11.9.2)



donde, c es la relacin entre el mximo a las dimensiones
mnimas de la seccin crtica, bo es el permetro de la
seccin crtica, y s es un factor de escala basada en la
ubicacin de la seccin crtica.

10,6 para columnas interiores
8,0 para columnas laterales
5,3 para columnas de esquinas
s

(Covenin 1753 seccin 11.9.2)



Un lmite se impone sobre el valor de
'
c
f
como:

2
' 26 /
c
f Kgf cm
(Covenin 1753 seccin 11.2)

2.6.2.4 Determinacin de la Relacin de Capacidad

Dada la fuerza de corte y punzonado de las fracciones de
los momentos transferidos por excentricidad de corte sobre
los dos ejes, el esfuerzo cortante se calcula suponiendo
como una variacin lineal a lo largo del permetro de la
seccin crtica. La relacin entre el esfuerzo cortante
mximo y la capacidad del concreto al esfuerzo de
punzonamiento es mostrada por SAFE como la relacin
entre la capacidad de punzonado. Si esta relacin supera
el 1,0, la armadura transversal por punzonado es diseado
como se describe en la seccin siguiente.
Traducido por mccloud_1 revisin 1 fecha 30/07/2010
5

2.6.3 Design Punching Shear Reinforcement

The use of shear studs as shear reinforcement in slabs is
permitted, provided that the effective depth of the slab is
greater than or equal to 6 inches, and not less than 16
times the shear reinforcement bar diameter (ACI 11.11.3).
If the slab thickness does not meet these requirements, the
punching shear reinforcement is not designed and the slab
thickness should be increased by the user. The algorithm
for designing the required punching shear reinforcement is
used when the punching shear capacity ratio exceeds
unity. The Critical Section for Punching Shear and Transfer
of Unbalanced Moment as described in the earlier sections
remain unchanged. The design of punching shear
reinforcement is described in the subsections that follow.



2.6.3.1 Determine Concrete Shear Capacity

The concrete punching shear stress capacity of a section
with punching shear reinforcement is limited to:


2.6.3.2 Determine Required Shear Reinforcement

The shear force is limited to a maximum of:


Given Vu, Vc, and Vmax, the required shear reinforcement
is calculated as follows, where, , the strength reduction
factor, is 0.75 (ACI 9.3.2.3).


If Vu > Vmax, a failure condition is declared.
(ACI 11.11.3.2)
If Vu exceeds the maximum permitted value of
Vmax, the concrete section should be
increased in size.



2.6.3 Diseo del Refuerzo por Punzonado

El uso de pernos o conectores de corte como refuerzo de
cortante en losas se permite, siempre que la profundidad
efectiva de la losa sea mayor o igual a 6 pulgadas, y no
menos de 16 veces el dimetro de barra de refuerzo a
cortante (ACI 11.11.3). Si el espesor de la losa no cumple
estos requisitos, el refuerzo por punzonamiento no es
diseado y el espesor de la losa debe ser aumentado por
el usuario. El algoritmo para el diseo de la armadura
necesaria por punzonamiento se utiliza cuando la relacin
de punzonamiento es superior a la unidad. La seccin
crtica de punzonamiento y transferencia de momentos no
balanceados como se describe en las secciones anteriores
permanecen sin cambios. El diseo de la armadura
transversal por punzonado se describe en las
subsecciones que siguen.

2.6.3.1 Calculo de la Capacidad a Corte del Concreto

La capacidad del concreto al corte de una seccin con
armadura transversal por punzonado se limita a:









2.6.3.2 Calculo del Refuerzo Requerido por Corte

La fuerza de corte se limita a un mximo de:











Dado Vu, Vc, y Vmax, el refuerzo por cortante requerido se
calcula de la siguiente manera, donde , el factor de
reduccin de resistencia, es 0,75 (Covenin 1753 seccin
9.4).

( )
u c
y
V V s
A
f d

=
(Covenin 1753 seccin 11.4.3 ecuacin 11-10)








Si Vu> Vmax, una condicin de falla se declara.
(ACI 11.11.3.2)
Si Vu excede el valor mximo permitido de Vmax,
la seccin de hormign se debe aumentar de
tamao.



Traducido por mccloud_1 revisin 1 fecha 30/07/2010
6
2.6.3.3 Determine Reinforcement Arrangement

Punching shear reinforcement in the vicinity of rectangular
columns should be arranged on peripheral lines, i.e., lines
running parallel to and at constant distances from the sides
of the column. Figure 2-5 shows a typical arrangement of
shear reinforcement in the vicinity of a rectangular interior,
edge, and corner column.


The distance between the column face and the first line of
shear reinforcement shall not exceed d/2. The spacing
between adjacent shear reinforcement in the first line
(perimeter) of shear reinforcement shall not exceed 2d
measured in a direction parallel to the column face (ACI
11.11.3.3).

Punching shear reinforcement is most effective near
column corners where there are concentrations of shear
stress. Therefore, the minimum number of lines of shear
reinforcement is 4, 6, and 8, for corner, edge, and interior
columns respectively.



2.6.3.4 Determine Reinforcement Diameter, Height, and
Spacing

The punching shear reinforcement is most effective when
the anchorage is close to the top and bottom surfaces of
the slab. The cover of anchors should not be less than the
minimum cover specified in ACI 7.7 plus half of the
diameter of the flexural reinforcement.

Punching shear reinforcement in the form of shear studs is
generally available in 3/8-, 1/2-, 5/8-, and 3/4-inch
diameters.

When specifying shear studs, the distance, so, between
the column face and the first peripheral line of shear studs
should not be smaller than 0.5d. The spacing between
adjacent shear studs, g, at the first peripheral line of studs
shall not exceed 2d, and in the case of studs in a radial
pattern, the angle between adjacent stud rails shall not
exceed 60 degrees. The limits of so and the spacing, s,
between the peripheral lines are specified as:

2.6.3.3 Diseo del Arreglo del Refuerzo

El refuerzo por punzonado en las proximidades de
columnas rectangulares deben disponerse en las lneas
perifricas, es decir, lneas paralelas y a distancias
constantes de los lados de la columna. La Figura 2-5
muestra una disposicin tpica de armadura a cortante en
las proximidades de una columna rectangular interior, de
borde y de esquina.













La distancia entre la cara de columna y la primera lnea del
refuerzo por cortante no exceder de d/2. El espacio entre
las armaduras transversales adyacentes en la primera
lnea (permetro) de la armadura transversal no ser
superior a 2d medido en una direccin paralela a la cara
de la columna (ACI 11.11.3.3).

La armadura transversal por punzonado es ms eficaz
cerca de las esquinas de la columna donde hay
concentraciones de esfuerzos por cortante. Por lo tanto, el
nmero mnimo de lneas de la armadura a cortante es de
4, 6 y 8, pora las columnas de esquina, borde e interior
respectivamente.


2.6.3.4 Calculo del Dimetro del Refuerzo, Altura y
Separacin

El refuerzo por punzonamiento es ms eficaz cuando el
anclaje est cerca de las superficies superior e inferior de
la losa. El recubrimiento de los anclajes no debe ser menor
que el mnimo recubrimiento especificado en ACI 7.7 ms
la mitad del dimetro del refuerzo a flexin.

La armadura transversal por punzonado en forma de
pernos o conectores de corte generalmente se dispone en
dimetros de 3/8, 1/2, 5/8, y 3/4 de pulgada.

Al especificar los conectores de corte, la distancia s0, entre
la cara de columna y la primera lnea perifrica de los
conectores de corte no debe ser menor que 0.5d. La
separacin entre conectores de corte adyacentes, g, en la
primera lnea perifrica de conectores no ser superior a
2d, y en el caso de los conectores en un patrn radial, el
ngulo entre los conectores adyacentes montados no
exceder de 60 grados. Los lmites de s0 y el
espaciamiento, s, entre las lneas perifricas estn
especifican como:



Traducido por mccloud_1 revisin 1 fecha 30/07/2010
7



Fuente: Section 2.6 Reinforced Concrete Design Manual. SAFE- v12.0.0 Diciembre 2008

You might also like