Current ratings for UL-CSA cables

Current ratings
PVC-insulated single and multicore wiring cables according to UL-AWM and CSA-TEW standards are used in switchboard and distribution cabinets of electrical equipments and as well as for the installation of machines and transformers in protecting tubes. PVC-insulation is allowed at maximum temperature range of 1058 C. The indicated values stated in the following tables are considered as guiding values. In critical situation the rules and recommendations for the current ratings should be followed.
*

for single core cables at ambient temperature up to 308C


Cross-section mm2 0,21 0,33 0,52 0,82 1,31 2,08 3,32 5,26 8,35 13,29 21,14 Load rating A 3,5 5,0 6,0 9,5 20 24 34 52 75 95 120 AWG No. 3 2 1 1/0 2/0 3/0 4/0 250 300 400 Cross-section mm2 26,65 33,61 42,38 53,43 67,40 84,97 107,17 127 152 178 Load rating A 154 170 180 200 225 275 325 345 390 415

AWG No. 24 22 20 18 16 14 12 10 8 6 4

for multicore cables at ambient temperature up to 308C


Cross-section mm2 0,21 0,33 0,52 0,82 1,31 2,08 3,32 5,26 8,35 13,29 21,14 26,65 33,61 42,38 Load rating up to 3 cores A 2 3 5 7 10 15 20 30 40 55 70 80 95 110 Load rating 4 6 cores A 1,6 2,4 4 5,6 8 12 16 24 32 44 56 64 76 88 Load rating 7 24 cores A 1,4 2,1 3,5 4,9 7 10,5 14 21 28 38 49 56 66 77 Load rating 25 42 cores A 1,2 1,8 3 4,2 6 9 12 18 24 33 42 48 57 66 Load rating 43 and above A 1 1,5 2,5 3,5 5 7,5 10 15 20 27 35 40 57 55

AWG Nr. 24 22 20 18 16 14 12 10 8 6 4 3 2 1

Correction-factors at ambient temperature over 308C


Ambient temperature 8C 31 40 41 45 46 50 Load rating values of above tables correction-factors f 0,82 0,71 0,58