ELECTRICAL THUMB RULES Current rating of Transformer / Generator (I) Impedence of Transformer (Z) :5 % Short circuit rating of Transformer

Current Rating / % Impedence = I / Z

: KVA X 1.4

No Load Current of Transformer :< 2 % of rated current of Transformer Impedence of Generator : 15 % Short circuit rating of Generator : Current Rating / % Impedence = I / Z Full load current ( FLC ) of 3 Phase Motor : HP X 1.5

No load current of 3 Phase Motor : 30% of FLC Full load current of Single Phase Motor : HP X 6 KW rating of Motor : HP X 0.75

OLR selection DOL STARTER :- FLC X 1 STAR & DELTA STARTER :- FLC X 0.6 Fuse Rating for Motor protection DOL :- FLC X 2 STAR & DELTA :- FLC X 1.5 SLIP RING MOTOR :FLC X 1.25