You are on page 1of 30

Differential Protection

Measuring Principle
Basis is the first Kirchhoffs law
I I1 I I = II1 + I2I In the case of load: I1 = IL I = 0 I2 = -IL

e.g. Transformer
1 I2 IL

I=0

The currents to a node are positive defined.

Internal fault (nfeed from two sides) I1 = I1,F I2 = I2,F I = II1,F + I2,FI trip

External fault I1 = IF I2 = -IF I = IIF - IF I = 0 no trip


Siemens. Innovation for generations.

/ Copyright Siemens Australia & NZ 2007. All rights reserved.

Peculiarity of the Transformer Differential Protection


1. Vector group (e. g. Yd5)
I1 I I 150 I2 trip region current transformer tap changer, CT adaptation (will be eliminated) magnetising current

2. Different CTs, tap changer, magnetising current

vector group adaptation


3. Dynamic currents
inrush current overflux (overexcitation) CT saturation during external faults
/ Copyright Siemens Australia & NZ 2007. All rights reserved.

restraint function (stabilising) is necessary


I = f (Irestr.) Irestr. = |I1| + |I2|
blocking via harmonics saturation detector

ITr, IRestr.

Siemens. Innovation for generations.

Differential Currents with Harmonics


i

energising
t=0

Y y

iDiff = i1

even, 2nd harm.


20 i 40 60 iDiff = i1 80 ms 100 t

i1

energising
t=0

D y

even 2nd harm.


20 40 60

i1

paralleling (energising transformer T1)


i2 T2

80 ms 100 iDiff = i2

even and odd 2nd harm.

T1

20

40

60

ms

80

/ Copyright Siemens Australia & NZ 2007. All rights reserved.

Siemens. Innovation for generations.

Differential Currents with Harmonics


Over-excitation UTr > UN
odd
i1 i2 i

iDiff = i1 - i2

3rd and 5th harm.


20 i 40 60 ms 80 t

External short circuit with saturation of the CTs at the low-voltage side
even and odd

iDiff = i1 - i2

i1

i2

20

40

60

ms

80

t iDiff = i1

internal short circuit with saturation of the CTs at the high-voltage side

even and odd

i1

i2 ~ 0 20 40 60 ms 80 t

/ Copyright Siemens Australia & NZ 2007. All rights reserved.

Siemens. Innovation for generations.

Differential Protection for Generators and Motors


Basic principle can be nearly direct used.
1. Stabilising characteristic
I
I

Trip area
Error currents via CT
IRestr.

identically current transformers sensitive setting is possible

2. Transients

sensitive settings Insensitive settings at matching transformers in the secondary circuit different primary CTs different burden
Siemens. Innovation for generations.

generators: external short circuit with large dc time constants motors: start-up currents transient transfer features of a CT are important (dc component)
/ Copyright Siemens Australia & NZ 2007. All rights reserved.

Devices with Differential Protection Functions 7UM62 and7UT6xx -Family

7UM621 and 7UM622 for protection objects with two ends (machines) 7UT612 for protection objects with two ends 7UT613 for protection objects with three ends 7UT633 for protection objects with three ends 7UT635 for protection objects up to five ends
Siemens. Innovation for generations.

/ Copyright Siemens Australia & NZ 2007. All rights reserved.

Applications

7UM 62 7UT612 7UT613

7UT613

Transformer

Two winding transformer 2 or 3phases

Three winding transformer 2 or 3phases

1 1/2 circuit breaker application with two winding transformer

GS 3~

7UT6 7UM 62 7UT612

7UT613

Generator/Motor longitudinal or transversal differential protection

Short lines 2 ends

Short lines 3 ends

/ Copyright Siemens Australia & NZ 2007. All rights reserved.

Siemens. Innovation for generations.

Connection Example
Side1 (Winding1) Side 3 (Winding 3) Side 2 (Winding 2)

direct connection to the main CTs no matching transformers / no matching connections numerical vector group adaptation without zero sequence current correction depending of the type of earthing of the winding.

7UT613; 633

increased sensitivity by 33% by measuring of the zero sequence current (7UT6) for single-pole faults. 1A/5A main CTs adaptation in the relay permissible ratio CT nominal current to transformer nominal current up to 1:8

7UM 62 7UT 612 )*


)* direct zero sequence current also possible

/ Copyright Siemens Australia & NZ 2007. All rights reserved.

Siemens. Innovation for generations.

Functional Diagram of the Differential Protection


tripping characteristic and saturat. detection
IDiff IDiff>

tripping by IDIFF>
IStab

i1P

measured value preprocessing winding 1 measured value preprocessing winding 2 measured value preprocessing winding 3

i1A* iDIFF = i1A* + i2A* + i3A* basic wave filtering IDiff iStab = | i*1A | + | i*2A | + | i*3A | rectified mean value IStab

harmonics analysis crossblock blocking by 2nd harmonics and 3rd or 4th. or 5th harmonics fast tripping with evaluation of
IDiff and iDiff

tripping logic
Blocking by harmonics

TRIPcommand TRIP L1 TRIP L2

i2P

i2A*

&

>1

TRIP L3

i3P

i3A*

tripping by IDIFF>> iDIFF>> Stage

i1P, i2P, i3P i *1A, i *2A, i *3A IDiff iDiff IStab iStab

sampling values from winding 1, 2, 3 values after vector group and CT matching basic wave contents in the differential current differential current rectified mean value of the stabilising current stabilising current
Siemens. Innovation for generations.

/ Copyright Siemens Australia & NZ 2007. All rights reserved.

Measuring Pre-processing, Example for CT Matching (Part 1)


SN = 100MVA UN1 = 110kV UN2 = 30kV 1000/1A IP1 = 500A (load current) Side 1 Side 2 2000/1A IP2 = 1833A (load current)

IN, Trafo = 525A

IN, Trafo = 1924A

IS1 = 0,5A

7UM 62 7UT6

IS2 = - 0,92A
measured secondary currents

IDiff = ? IRestr. = ?

/ Copyright Siemens Australia & NZ 2007. All rights reserved.

Siemens. Innovation for generations.

Measuring Pre-processing, Example for CT Matching (Part 2)


1. Calculation of the transformer nominal current 2. Correction factor 3. Correction nominal current 4. Calculation of the differential and stabilising current INTrafo = kW =
SN 3 UN I NCT I NTrafo

I = kW IS Idiff = |I1' + I2' | Istab = |I1' | + |I2' |

Calculation example:
SN = 100MVA; UN1 = 110kV; UN2 = 30kV; Correction factors: Load conditions: Secondary currents: Matched currents: IN1CT = 1000A; IN2CT = 2000A kW2 = 1,04 Ip2 = 1833A Is2 = 0,92A I2' = 0,95A Idiff = 0A IStab = 1,9A Idiff = 0 IN Trafo Istab = 1,9IN Trafo

kW1 = 1,9; Ip1 = 500A; Is1 = 0,5A; I1' = 0,95A;

/ Copyright Siemens Australia & NZ 2007. All rights reserved.

Siemens. Innovation for generations.

Measuring Preprocessing: Vector Group Adaptation)


Ip
L1 L2 L3

YN

d5

Is IpL1 IsL3

IE IpL3 IpL2

IsL2

IsL1

Protection

zero sequence elimination


I *pL1 I pL1 2 - 1 - 1 1 I *pL2 = 3 -1 2 - 1 I pL2 I * I pL3 -1 - 1 2 pL3
I * sL1 - 1 0 1 I sL1 I * = 1 1 - 1 0 I sL2 sL2 3 0 1 - 1 I sL3 I * sL3

standard setting

additional earth current measurement (I0-correction)


I *pL1 I pL1 1 0 0 I E 1 I *pL2 = 0 1 0 I pL2 + 3 IE I * I pL3 0 0 1 I E pL3

I * sL1 - 1 0 1 I sL1 1 I * sL2 = 3 1 - 1 0 I sL2 0 1 - 1 I sL3 I * sL3

increasing of the sensitivity via the connection of IE-CT (only at 7UT6 possible)

/ Copyright Siemens Australia & NZ 2007. All rights reserved.

Siemens. Innovation for generations.

Example Calculation: Vector Group Correction Situation: Single Phase Fault, No Load
ISC L1 L2 L3 ISC F1 IL1 IL2 IL3 IE = -ISC = 0 = 0 = ISC F2 IL1 IL2 IL3 IE = = = = 0 0 0 ISC Il 1 = Il 3 = ISC / 3 0 Il 2 = - ISC / 3 ISC/ 3 F1 F2

Ynd1

ISC/ 3 Source

/ Copyright Siemens Australia & NZ 2007. All rights reserved.

Siemens. Innovation for generations.

Example Calculation: Vector Group Correction I Zero Elimination


F1 I*L1 2 -1 -1 I*L2 = 1/3 -1 2 -1 I*L3 -1 -1 2 I*L1 = I*L2 = I*L3 = IDIFF1 = I*L1 + I*l 1 = IDIFF2 = I*L2 + I*l 2 = IDIFF3 = I*L3 + I*l 3 = - ISC 0 0 -2/3 ISC 1/3 ISC 1/3 ISC 0 0 0 F2 0 0 0 0 0 0 2/3 ISC 1/3 ISC 1/3 ISC I*l 1 = 1/3 ISC + 1/3 ISC = 2/3 ISC I*l 2 = 0 - 1/3 ISC = -1/3 ISC I*l 3 = -1/3 ISC + 0 = -1/3 ISC I*l 1 I*l 2 I*l 3 1 -1 0 = 1/3 0 1 -1 -1 0 1 ISC / 3 - ISC / 3 0

We see in all three phases a differential current; this must be considered during a single phase test Use only the trip signal from the tested phase!
Siemens. Innovation for generations.

/ Copyright Siemens Australia & NZ 2007. All rights reserved.

Example Calculation: Vector Group Correction I Zero Correction


F1 I*L1 I*L2 I*L3 1 0 0 = 0 1 0 0 0 1 I*L1 = I*L2 = I*L3 = IDIFF1 =I*L1 + I*l 1 = IDIFF2 =I*L2 + I*l 2 = IDIFF3 =I*L3 + I*l 3 = - ISC 0 0 -2/3ISC 1/3 ISC 1/3 ISC 0 0 0 F2 0 0 0 1/3 ISC 1/3 ISC 1/3 ISC ISC 0 0 1/3 ISC + 1/3 ISC 1/3 ISC I*l 1 1 -1 0 ISC / 3 1 I*l 2 = 0 1 -1 - ISC / 3 I*l 3 3 -1 0 1 0

I*l = 1/3 ISC + 1/3 ISC = 2/3 ISC I*l 2 = 0 - 1/3 ISC = -1/3 ISC I*l 3 = -1/3 ISC + 0 = -1/3 ISC

We see only in the faulty phase the currents

/ Copyright Siemens Australia & NZ 2007. All rights reserved.

Siemens. Innovation for generations.

Tripping Characteristic

flexible adaptation to various transformers, e.g. with tap changer or different main CTs high stability against external faults with CT saturation fast tripping for solid short-circuits within one period
/ Copyright Siemens Australia & NZ 2007. All rights reserved.

Siemens. Innovation for generations.

Relay Settings Influence of the Tap Changer Problem: The tap changer modifies the transformer ratio additional error in the differential current Example:
tap changer c = 16%

I diff = I res c = 0,16

c 2m c I diff

0 ,087 I res

If IN.Tr. is flowing the additional Idiff is approx. 17,5% of the transformer current. With slope 1 = 0,25 there is the pick-up threshold at 50%. The security margin is for steady state conditions high enough. Considering transient conditions (CT-influence) a small increasing of slope 1 (to 0,3) is recommended. Recommendation for voltage setting:

U N, New

U max U min = 2 = U N (1 - c2 ) U max + U min


Siemens. Innovation for generations.

c: steps of tap changer (p.u.)


/ Copyright Siemens Australia & NZ 2007. All rights reserved.

Pick up of Differential Protection

For triggering of internal tasks, events and fault records the differential protection function needs a pickup information. This pickup becomes active, if the differential current or the restraint current is over an internal threshold (dotted line). Each external large current leads to a pickup.

Pickup doesnt always means internal failure!


/ Copyright Siemens Australia & NZ 2007. All rights reserved.

Siemens. Innovation for generations.

IDiff / IRestr.- Areas for Short Circuit / Normal Operation


I diff I NTr
internal short circuit/ Inrush
limiting curve

external short circuit with CT saturation

external short circuit normal operation 2 (nominal current)

(low current) 4

external short circuit with a high current

I Restr. I NTr

/ Copyright Siemens Australia & NZ 2007. All rights reserved.

Siemens. Innovation for generations.

Rush Stabilisation
Cross-block = No (phase separate blocking)
iRUSH = iDiff filter window 1 cycle L1-block Idiff, L1 > trip blocking Idiff, L2 > trip blocking Idiff, L3 > trip blocking

Inrush current in one phase

& & &

L2-block L3-block

t
1P I2HAR Idiff 2P 3P

Cross-block = Yes (blocking of all phases)


L1-block

block
setting value
no block t

15 %

L2-block L3-block

OR 1

IDiff > trip blocking for a limited time

Recognise inrush condition by evaluating the ratio 2nd harmonic I2HAR to basic wave IDiff. Time limit for cross-block. Reliable reaction to the inrush condition with cross-block. Trip of a short circuit after the set time delay. Recognise over-excitation by evaluating the ratio 3rd or 5th harmonic to basic wave
/ Copyright Siemens Australia & NZ 2007. All rights reserved.

Siemens. Innovation for generations.

Example of an Inrush Current


A unit transformer (IN = 396 A) was switched on from the high voltage side

/ Copyright Siemens Australia & NZ 2007. All rights reserved.

Siemens. Innovation for generations.

Stabilising at Motor Starting


Typical for motor starting is the starting current and the superimposed dc component with a large time constant. The current transformers (ct) transfer different this dc component. The result is a differential current and the risk of an over-function is given.

Detection of motor starting: Increases the pick-up values for a restricted time

Criterion: Supervision of restraint current Istab > I-Restr. Startup (until 2 I/InO) than the Start-Factor (max. 2) is active for a restricted time T Start Max (Duration of dynamical increasing of pickup)
/ Copyright Siemens Australia & NZ 2007. All rights reserved.

Siemens. Innovation for generations.

Setting Recommendations
Power System Data 1
The setting of this parameters are important, because they are necessary for the scaling and direction definition of the measurands. At the protection object transformer the setting for star point Solid Earthed leads to a zero sequence elimination. Isolated leads to a direct current comparison (without zero sequence consideration). This setting is only allowed at a really free star point (no over voltage arrester, no Peterson coil). At the protection object generator always the direct current comparison method is active (no zero sequence elimination).

Setting values:
Under normal conditions the factory settings correspond with the practical experiences. Its not necessary to change these parameters. At transformers with tap changer the inclination of SLOPE 1 should be increased. The setting for the inrush detection can be final select during the primary test. If we are on the limits (low setting value) an activation of CROSSBL. 2. Harm. is recommended. If are current transformer operates on their limit the pickup value Idiff > and die slope 1 should be increased. The Idiff >> - stage must be set over the maximum inrush current. At generators and motors SLOPE 1 can be reduced (to 0,15), if the current transformers are identical. At generators the Idiff>>-stage must be set over the transient fault current (3 to 7 IN,G). Additional at generators its also recommended an activation of increasing the pickup threshold during starting or at external faults (Start-Factor > 1). Siemens. Innovation for generations.

/ Copyright Siemens Australia & NZ 2007. All rights reserved.

Earth Current Differential Protection in the 7UM62


The earth current differential protection (restricted earth fault protection - REF) offers a higher sensitivity at single phase faults (approx. 5 %) against the conventional protection. Its used at generators with low ohmic star point or at earthed Wye connected transformer windings . Connection 1

Connection 2

At connection 1 the zero sequence current is calculated from the phase currents and direct measured on the star point (transformer application) At connection 2 the zero sequence current is calculated only from the phase currents. (generator application, where more than one generator feeds into the busbar)

protection object

protection object

/ Copyright Siemens Australia & NZ 2007. All rights reserved.

Siemens. Innovation for generations.

Measuring Principle of Earth Current Differential Protection in the 7UM62


protection object: generator

iL1S1 iL2S1 iL3S1

iL1S2 iL2S2 iL3S2 iee2

3I 01 = I L1S1 + I L2S1 + I L3S1 3I 02 = I L1S2 + I L2S2 + I L3S2


or

3I01

3I02 1
1

3I 02 = I EE2

I/InO

I0Diff

Tripping range Stabilizing range Range not possible

I 0 Diff = 3I 01 + 3I 02 I 0 Stab = 3I 01 + 3I 02

I-EDS>
1

I/InO

I0Stab
/ Copyright Siemens Australia & NZ 2007. All rights reserved.

Siemens. Innovation for generations.

Earth Current Differential Protection in the 7UM62 Stabilizing against Overfunction


Main problem are external faults: Transient conditions with large time constants; Short current circuits with current transformer saturation
Direction of zero sequence current:
90 115 65

II. III.
1 8 0

I. IV.
| | = 0

I. internal fault III. external fault IV. direction not considered II. measuring repetition (<90internal fault)

2104 EDS || I MIN>

Limitation of phase current: I > Imax (max. 2.5 IN), than blocking Release at zero sequence voltage: A release of zero sequence current measurement is be caused by a measured zero sequence voltage (can be switched off).
/ Copyright Siemens Australia & NZ 2007. All rights reserved.

Siemens. Innovation for generations.

Restricted Earth Fault Protection (REF) in the 7UT6


Trip = I0' - k S Stab < 0 Trip Trip = I0' Trip - tripping quantity

i1 i2 i3

Stab 0 Stab - I0 angle-dependent stabilization


iF

restricted earth fault protection 7UT6


i "0 = i1 + i2 + i3

i '0

fault current against earth stabilization area

tripping area IEDF- pick-up valve

i 0" + i0' = iF

Stab = I I '0 - I " 0| - | I ' 0 + I " 0|

calculation of the basic wave and the complex vectors of I0' and I0" insensitive against DC components and CT saturation evaluation of the modulus and angle between I0' and I0" sensitive fault detection starting with 5% transformer nominal current
/ Copyright Siemens Australia & NZ 2007. All rights reserved.

Siemens. Innovation for generations.

Commissioning with Browser- Support

Currents on the high and low voltage side

Tripping characteristic with actual operating points

/ Copyright Siemens Australia & NZ 2007. All rights reserved.

Siemens. Innovation for generations.

Benefits for the Customer


Protection relay with flexible adaptation to the transformer/generator/motor or short line. Programming of the device data in the relay. Reduced amount of wiring by direct connection to the main CTs. No matching transformers and therefore no wiring errors. Zero sequence current can be measured (in the 7UT6). Sensitivity for single-pole faults in the transformer increased by 33% . Flexible adaptation of the tripping characteristic to various main CTs, tapped transformers. Exact discrimination between the short circuit condition and the inrush condition by on-line analysis of the harmonics. Fast tripping for high-current faults. Saturation detector for external faults. Thermal monitoring of two transformer windings. Back-up DMTL/IDMTL with reverse blocking for one winding. Sensitive short circuit protection for faults winding against earth. Manifold commissioning aids.
/ Copyright Siemens Australia & NZ 2007. All rights reserved.

Siemens. Innovation for generations.

You might also like