You are on page 1of 12

OMICRON PTL Siemens 7SD8x V7.

80 Line PTT User Manual

OMICRON PTL

Siemens 7SD8x V7.80 Line PTT

User Manual

V2.000

© OMICRON electronics GmbH 1/12


OMICRON PTL Siemens 7SD8x V7.80 Line PTT User Manual

Content
1. General ...................................................................................................................................................3
1.1 Supported Relays .................................................................................................................................3
2. Test Universe-Based Testing ...............................................................................................................4
2.1 Software and Hardware Requirements ................................................................................................4
2.2 Hardware ..............................................................................................................................................4
2.3 Functional Range .................................................................................................................................5
2.4 XRIO Converter ....................................................................................................................................6
2.4.1 Diff Topology ..................................................................................................................................6
2.4.2 Additional Information .....................................................................................................................6
2.5 Specific Protection Test ........................................................................................................................7
2.5.1 Line Differential Protection .............................................................................................................7
3. RelaySimTest-Based Testing ...............................................................................................................8
3.1 Software and Hardware Requirements ................................................................................................8
3.2 Test Set Configurations ........................................................................................................................8
3.3 Functional Range .................................................................................................................................9
3.4 Power System Data ........................................................................................................................... 10
3.5 Automatic Reclosing Function ........................................................................................................... 11
3.5.1 General Test Case Settings ........................................................................................................ 11
3.5.2 AR with 1 Cycle ........................................................................................................................... 11
3.5.3 AR with 2 Cycles ......................................................................................................................... 11
3.5.4 AR with Distance Cross-Check ................................................................................................... 11
3.6 Teleprotection with Distance Protection ............................................................................................ 12

© OMICRON electronics GmbH 2/12


OMICRON PTL Siemens 7SD8x V7.80 Line PTT User Manual

1. General
This user manual describes details of testing Siemens 7SD8x relays with the OMICRON
Protection Test Template. General information on the usage of OMICRON Protection Testing Library
items can be found in the OMICRON PTL user manual.

General protection functions are tested with Test Universe (chapter 2). The RelaySimTest
templates provide tests for additional functions (chapter 3).

The template has been tested with the following relay:


Manufacturer: Siemens
Model: 7SL87
Firmware Version: 7.80

1.1 Supported Relays


The following relays can be tested with the Protection Test Template:
• 7SD82
• 7SD84
• 7SD86
• 7SD87

© OMICRON electronics GmbH 3/12


OMICRON PTL Siemens 7SD8x V7.80 Line PTT User Manual

2. Test Universe-Based Testing

2.1 Software and Hardware Requirements


To use this template, you must have a valid test license for the OMICRON Test Universe 4.00 software or
higher versions and the following test modules:
• Control Center
• Annunciation Checker
• Quick CMC
• Ramping
• Overcurrent
• State Sequencer
• Diff Operating Characteristic

Any CMC test set can be used with this Protection Test Template. In addition a CMGPS 588 is necessary.

2.2 Hardware
There are multiple possibilities of wiring a 7SD8x relay to a CMC test set. The advised connections are
shown in Figure 1. These connections are the default settings in the Hardware Configuration of the PTT.
Please note that in case of 3-pole-tripping application, the binary inputs Trip A, Trip B and Trip C should
be connected parallel.

Figure 1: Connection for 7SD8x

© OMICRON electronics GmbH 4/12


OMICRON PTL Siemens 7SD8x V7.80 Line PTT User Manual

2.3 Functional Range


Supported functions:
• Line Differential protection
• Overcurrent protection phase (1 inverse, 1-4 definite time stages) (50/51)
• Overcurrent protection ground (1 inverse, 1-4 definite time stages) (50N/51N)

Not supported functions:


• Line Differential protection option: Transformer in the protection range
• Synchrocheck, synchronizing function (25)
• Voltage protection (27), (59)
• Power protection active/reactive power
• Thermal overload (49)
• Instantaneous High-Current Tripping (50)
• Switch On To Fault SOTF protection
• Directional Time-Overcurrent Protection (67/67N)
• Circuit breaker failure protection (50BF)
• Automatic reclosing (79)
• Frequency protection (81 O/U)
• Differential protection (87L/87T/87STUB)
• Fault locator

Although the functions listed above are not supported by the Protection Test Template, the
Relay Parameter Section of the XRIO Converter includes most protection parameters of the relay.

© OMICRON electronics GmbH 5/12


OMICRON PTL Siemens 7SD8x V7.80 Line PTT User Manual

2.4 XRIO Converter


The Test Object contains the 7SD8x XRIO Converter, which includes setting parameters of the modelled
protection relay. The setting parameters are built as an image of the Digsi5 V07.80 software. In this
chapter, the specifics of the sections Diff Topology and Additional Information are described. General
information about the converter structure can be found in the OMICRON PTL user manual.

2.4.1 Diff Topology


The Diff Topology block contains the parameter Local device is device (DIGSI Addr. 31.5131.101). If
your local relay under test is “1”, choose “1”. If your local relay under test is not “1”, choose “2” (Figure 2).

Figure 2: Diff Topology

2.4.2 Additional Information


Settings Remote Relay
Certain parameters of the remote relay have to be entered in the Additional Information\Settings
Remote Relay (Figure 3). The parameters Threshold Idiff> and Threshold Idiff fast are automatically
calculated according to the settings of the local relay and the current transformer of the remote relay. The
correct parameters are important for end to end tests of the differential protection function.

Figure 3: Settings Remote Relay

Relay Information – General


The Additional Information\Relay Information\General block contains the parameter Standard unit
system, which defines the used unit system. The values “SI units (km and °C)” and “US units (mi and °F)”
can be selected.

© OMICRON electronics GmbH 6/12


OMICRON PTL Siemens 7SD8x V7.80 Line PTT User Manual

2.5 Specific Protection Test


In this chapter the specific protection tests, which are not covered by the OMICRON PTT user manual,
are described.

2.5.1 Line Differential Protection


Communication Check
An Annunciation Checker test module is used to guide the tester through the process of checking the Line
Differential protection communications. Please follow the instructions given by the Test Navigator. The
Annunciation Checker test has to be assessed manually.

Line Differential Pickup Test


The Line Differential pickup test has to be performed with active communication. Each relay (local and
remote) has to be tested independently. During the test of one relay it has to be ensured that the remote
end does not measure any current. The pulsed currents are ramped until the differential protection picks
up. The pickup value is assessed.

Line Differential Trip Time Test


The Line Differential Trip Time Test simulates a fault on the line protected with the Line Differential
protection. A relay trip is expected. The trip time is assessed.

Line Differential External Fault


The State Sequencer test module is used to test the stability of the Line Differential function for through
fault conditions. The local and the remote relay are involved in these end to end type tests. To
synchronize the test signals of both ends, CMGPS 588 is required. The corresponding test modules for
relay 1 and relay 2 need to be opened and then run simultaneously on both sides.

A fault outside the protection area located at side 2 followed by a fault outside the protection area located
at side 1 is simulated. Both relays must not send a trip signal during the tests.

Line Differential Operating Characteristic


The Diff Operating Characteristic test module is used to test the operating characteristic of the Line
Differential function. The local and the remote relay are involved in these end to end type tests. To
synchronize the test signals of both ends, CMGPS 588 is required. The corresponding test modules for
relay 1 and relay 2 need to be opened and then run simultaneously on both sides.

Please check and adjust the test points to fit your application. Please make sure, that the same test points
are used in the corresponding test modules for both relays.

© OMICRON electronics GmbH 7/12


OMICRON PTL Siemens 7SD8x V7.80 Line PTT User Manual

3. RelaySimTest-Based Testing

3.1 Software and Hardware Requirements


To use the PTL RelaySimTest (RST) templates, you must have a valid test license for the OMICRON
RelaySimTest 3.21 software or higher versions. Any CMC test set can be used with this
Protection Test Template.

3.2 Test Set Configurations


The following figures show the default connections for relay 1 (relay 2 equivalent). The connections of the
CMC and relay terminals have to be checked and adapted if required.

Figure 4: Test set configuration – analog outputs

Figure 5: Test set configuration - binary inputs

Figure 6: Test set configuration – binary outputs (only single-end template)

© OMICRON electronics GmbH 8/12


OMICRON PTL Siemens 7SD8x V7.80 Line PTT User Manual

3.3 Functional Range


This PTT package includes two RST-templates with different testing approaches:
• Single-End
• End-to-End

Supported functions:
• Automatic reclosing, 1-/3-pole, with distance zone Z1B or differential protection
o 1 cycle
o 2 cycles
• Teleprotection with distance protection (PUTT, POTT, Blocking)

Not supported functionalities:


• Automatic reclosing:
o Dead time after evolving fault

© OMICRON electronics GmbH 9/12


OMICRON PTL Siemens 7SD8x V7.80 Line PTT User Manual

3.4 Power System Data


The parameters of the following table have to be entered in the power system. Ideally, the data of the
power system components is taken from a network calculation software instead the relay settings.

RST Element RST Test Case Setting Relay Parameter


System under Nominal frequency Device settings/General/Rated frequency
test
Infeed 1 Nominal Voltage L-L Line/General/Rated Values/Rated voltage
Grounding Line/General/Line Data/Neutral point
SIR1 <no relay parameter>
Infeed 2 2 Nominal Voltage L-L Line/General/Rated Values/Rated voltage
Grounding Line/General/Line Data/Neutral point
SIR1 <no relay parameter>
Line Nominal current Line/General/Rated Values/Rated current
Length Line/General/Line data/Line length
Line Impedances = Device settings/General/Set. format residu. comp =
R', X', RN/R, XN/X resp. Kr, Kx resp. K0
Z', k- Factor
R', X', X' Line/General/Line data/X per length unit (primary)
RN/R, R' <see calculation 1>
XN/X
RN/R Line/General/Line data/Kr
XN/X Line/General/Line data/Kx
Z', k- Z' <see calculation 2>
Factor k-Factor Line/General/Line data/K0 and Line/General/
Angle (K0)
CT Rated prim. current Power System/Meas.point I-3ph/CT 3-phase/
Rated primary current
Rated sec current Power System/Meas.point I-3ph/CT 3-phase/
Rated secondary current
Polarity Power System/Meas.point I-3ph/CT 3-phase/
Neutr. point in dir.of ref.obj
VT Rated prim. voltage L-L Power System/Meas.point I-3ph/VT 3-phase/
Rated primary voltage
Rated sec. voltage L-L Power System/Meas.point I-3ph/VT 3-phase/
Rated secondary voltage
CB Aux. contact simulation <if configured>
1 Source (to line) impedance ratio
2 Adjust phase angle for a higher load current (e.g. for lines > 100km)

Calculations for RST line-element impedances (X in primary):

1. R’ for mode Kr, Kx:


𝑋 𝑝𝑒𝑟 𝑙𝑒𝑛𝑔𝑡ℎ 𝑢𝑛𝑖𝑡 𝑝𝑟𝑖𝑚𝑎𝑟𝑦
𝑅′ =
tan(𝐿𝑖𝑛𝑒 𝑎𝑛𝑔𝑙𝑒)

2. Z‘ for mode K0:


𝑋 𝑝𝑒𝑟 𝑙𝑒𝑛𝑔𝑡ℎ 𝑢𝑛𝑖𝑡 𝑝𝑟𝑖𝑚𝑎𝑟𝑦
𝑍′ =
sin(𝐿𝑖𝑛𝑒 𝑎𝑛𝑔𝑙𝑒)

© OMICRON electronics GmbH 10/12


OMICRON PTL Siemens 7SD8x V7.80 Line PTT User Manual

3.5 Automatic Reclosing Function


The RST-templates provide tests for a 1-/3-pole automatic reclosing (AR) mode using a protection area of
100% line length. This may be a differential protection function or an overreaching zone of a distance
protection function. The templates have to be adapted, if you are using a different application concerning
mode or additional signals, e.g. a CB ready signal or CB aux. contacts.

Important: The Iterative Closed-Loop simulation method of RelaySimTest is used for testing the AR
function. Further information can be found in the RelaySimTest help.

3.5.1 General Test Case Settings


The following parameters have to be entered in the test case view for the automatic reclosing test cases:

Measurement RST Test Case Setting Relay Parameter


Trip times Set assessment conditions/ Line/21 Distance prot./AR zone 1/Operate
Trip time A, B, C delay 1-phase/multi-ph. (dependent on the
fault type)
Reclaim time Simulation test settings/ Circuit breaker/79 Auto. reclosing/
Pause/Defined pause before General/Reclai. time aft.succ.cyc.
each test step
Dead time(s) Set assessment conditions/ Circuit breaker/79 Auto. reclosing/
Dead time cycle # Cycle #/Dead time aft. 1-/3-pole trip
(dependent on the fault type)

3.5.2 AR with 1 Cycle


The AR function with 1 cycle is tested with faults at 100% line length (resp. on both line ends for end-to-
end tests). The phase-selective trip signals and the close command signal of the relay are measured and
assessed.
In the AR successful test, the line fault extinguishes after a time delay of 100 ms. In the AR unsuccessful
test, the fault remains until the end of the test.

3.5.3 AR with 2 Cycles


The AR function with 2 cycles is tested with faults at 100% line length (resp. on both line ends for end-to-
end tests).. The phase-selective trip signals and the close command signal of the relay are measured and
assessed.
In the AR successful after cycle 1 test, the line fault extinguishes after a time delay of 100 ms. In the AR
successful after cycle 2 test, the line fault has to extinguish during the second interruption. Therefore, the
"Delay since previous event" (see Figure 7) for the line fault 1 inactive event is dependent on the dead
time of the first AR cycle and has to be set manually. In the AR unsuccessful test, the fault remains until
the end of the test.

Example for AR successful after cycle 2 test for 1-pole-fault:


Delay since previous event =
Cycle 1/Dead time aft. 1-pole trip time + 200 ms = 500 ms + 200 ms = 700 ms

Figure 7: Fault settings

3.5.4 AR with Distance Cross-Check


For cross-checking an AR distance zone, the power system has to be extended by a following line. The
tests have to be created manually.

© OMICRON electronics GmbH 11/12


OMICRON PTL Siemens 7SD8x V7.80 Line PTT User Manual

3.6 Teleprotection with Distance Protection


The RST-templates include tests for the teleprotection with distance protection function and the following
modes:
• Permissive Underreach Transfer Trip (PUTT)
• Permissive Overreach Transfer Trip (POTT)
• Blocking Method

The following parameters have to be entered in the test case view for the teleprotection test cases:

Test Case Measurement RST Test Case Setting Relay Parameter


Fault on Trip time relay 1 Set assessment conditions/ <Operate delay of reverse zone>
Busbar 1 Trip time - Relay 1
Trip time relay 2 Set assessment conditions/ Line/21 Distance prot./Z2/
Trip time - Relay 2 Operate delay
Fault on Trip time relay 1 Set assessment conditions/ Line/21 Distance prot./Z2/
Busbar 2 Trip time - Relay 1 Operate delay
Trip time relay 2 Set assessment conditions/ < Operate delay of reverse zone >
Trip time - Relay 2
Fault on Trip time relay 1 Set assessment conditions/ Line/21 Distance prot./Z1(Z1B)/
Line, 0%, Trip time - Relay 1 Operate delay
50%, 100% Trip time relay 2 Set assessment conditions/ Line/85-21 <teleprotection
Trip time - Relay 2 mode>/Operate delay (multi-ph.)

The teleprotection with distance protection function is tested with significant faults at the following
locations:
• Busbar 1
• Busbar 2
• Line, 0%
• Line, 50%
• Line, 100%

The trip signals and the send signal of the relay are measured and assessed according to the expected
relay behavior of the teleprotection mode.

Important: The Iterative Closed-Loop simulation method of RelaySimTest is disabled for testing the
teleprotection function. With Iterative Closed-Loop enabled, please adjust the trip time assessments for
the “Fault on Busbar” test cases according to your application (iterative tripping of relay 1 and relay 2
possible). Further information about Iterative Closed-Loop can be found in the RelaySimTest help.

© OMICRON electronics GmbH 12/12