OMICRON PTL
User Manual
V1.000
Content
1. General .............................................................................................................................................3
1.1 Supported Relays ............................................................................................................................3
2. Software and Hardware Requirements............................................................................................3
3. Hardware ..........................................................................................................................................4
4. Functional Range .............................................................................................................................4
5. XRIO Converter ................................................................................................................................5
5.1 Specialties of the Additional Information Block .................................................................................5
6. Specific Protection Tests .................................................................................................................6
6.1 Thermal Overload ...........................................................................................................................6
6.2 Under/Over Voltage.........................................................................................................................6
6.2.1 Pickup Tests ..............................................................................................................................6
6.2.2 Trip Time Tests..........................................................................................................................6
1. General
This user manual describes details of testing 7SJ6x relays with the OMICRON Protection Test Template.
General information on the usage of OMICRON Protection Testing Library items can be found in the
OMICRON PTL user manual.
Any CMC test set can be used with this Protection Test Template.
3. Hardware
There are multiple possibilities of wiring a 7SJ6x relay to a CMC test set. The advised connections are
shown in Figure 1. These connections are the default settings in the Hardware Configuration of the PTT.
Connection for
Siemens 7SJ6x
CB 52a*
VN
VC
VB
VA
IA-IB-IC
IA
IB
IC
Alarm*
Start*
Trip
CB aux.(52a)
IN
IN
4. Functional Range
Supported functions:
• Overcurrent (50,51,50N,51N)
• Phase Directional Overcurrent (67,67N)
• Negative Sequence Overcurrent (46)
• Thermal Overload (49)
• Under/Over Voltage (27,59)
Although the functions listed above are not supported by the Protection Test Template, the
Relay Parameter Section of the XRIO Converter includes all protection parameters of the relay.
5. XRIO Converter
The Test Object already contains the Siemens 7SJ6x XRIO Converter, which includes setting
parameters of the modelled protection relay. The setting parameters are built as an image of the DIGSI
4.83 software.
The Standard Filter for XRIO files can be used for importing settings into the Relay Parameter Section.