SPECIFICATIONS FOR OXYGEN ANALYSER Type: In-Situ Oxygen Transmitter - Explo-Proof Sensing Probe Type- Snubber Diffusion Element

or vendor to specify Probe Length: 3' (0.91m) Probe Flange Size: ANSI 3" 150 lb bolt circle Mounting Adapter (stack side): Vendor to specify if required Mounting Hardware (Probe Side): Probe only (ANSI) Electronics: Mounted remotely, requires cable ATEX EExdIIB+H2T2 (Approx. distance 25 m) Hazardous Area Approval: ATEX EExd IIB + H2 (Class 1, Division 1, Group B,C,D) Electronics to Probe Cable: 25m Cable - Remote Electronics Output signal: 4 20 mA DC HART

OXYGEN TRANSMITTER STOICHIOMETER SPECIFICATION Net O2 Range: 0-10% Accuracy: Typically 0.75% of reading or 0.05% O2, whichever is greater Lowest detectable limit: .05% O2 System Response to Test Gas: Initial response in less than 3 seconds T90 in less than 8 seconds PROBE SPECIFICATION Temperature Limits: Sample Gas Temperature: 0-1200 C Electronics: -40 to 185F (-40 to 85C) actual temperature inside electronics Local operator interface: -40 to 185F (-40 to 85C) Probe Lengths, Nominal and Approximate Shipping 3 foot (0.91 m approx) Mounting and Mounting Position: Vertical or horizontal Spool pieces are required (vendor to specify), to offset transmitter housing from hot duct Work. Materials: Probe: Wetted or welded parts 316L stainless steel Non-wetted parts 304 stainless steel, low-copper aluminum Calibration: Semi-automatic or automatic Calibration Gas Mixtures Recommended: 0.4% O2, balance N2, 8% O2, balance N2 Calibration Gas Flow: Vendor to specify Reference Air 2 scfh (1 l/m)/ Vendor to specify, clean, dry, instrument-quality Electronics: NEMA 4X, IP 66 with fitting and pipe on reference exhaust port to clean dry Atmosphere.