ARTICLE 310: Conductors for General Wiring

NEC Figure 310.60

Figure 310.60. Cable installation dimensions for use with Tables 310.77 through 310.86.
190 mm (7.5 in.)

Detail 1 290 mm x 290 mm (11.5 in. x 11.5 in.) Electrical duct bank One electrical duct

190 mm

190 mm (7.5 in.) Detail 2 475 mm x 475 mm (19 in. x 19 in.) Electrical duct bank Three electrical ducts or

190 mm

190 mm (7.5 in.) Detail 3 475 mm x 675 mm (19 in. x 27 in.) Electrical duct bank Six electrical ducts or

190 mm

190 mm

190 mm (7.5 in.)

190 mm (7.5 in.)

Detail 4 675 mm x 675 mm (27 in. x 27 in.) Electrical duct bank Nine electrical ducts

190 mm (7.5 in.)

190 mm (7.5 in.)

675 mm x 290 mm (27 in. x 11.5 in.) Electrical duct bank Three electrical ducts 190 mm (7.5 in.) 190 mm (7.5 in.)

675 mm x 475 mm (27 in. x 19 in.) Electrical duct bank Six electrical ducts 600 mm (24 in.) 600 mm (24 in.)

Detail 5 Buried 3 conductor cable 190 mm (7.5 in.) 190 mm (7.5 in.)

Detail 6 Buried 3 conductor cable 190 mm (7.5 in.)

Detail 7 Buried triplex cables (1 circuit) 190 mm (7.5 in.)

Detail 8 Buried triplex cables (2 circuits) 190 mm (7.5 in.) 190 mm (7.5 in.)

600 mm (24 in.)

Detail 9 Buried single-conductor cables (1 circuit)

Detail 10 Buried single-conductor cables (2 circuits)

Legend Backfill (earth or concrete) Electrical duct

Cable or cables