Maxsys

i n t e g r at e d s Y S T E M S T E C H N O L O G Y

PC4108A/4116
HARDWIRED ZONE EXPANSION MODULES
PC4108A

MAXSYS systems can be expanded in increments of 8 and 16 hardwired zones up to the rated capacity of each system using multiple PC4108A and PC4116 hardwired zone expansion modules. Each module can be added as required anywhere on the system Combus providing the utmost in flexibility for hardwired zone expansion to meet customer requirements now and in the future!

PC4116

PC4108A 8 Zone Expansion Module


provides 8 programmable hardwired zones zone supervision : zones can be NC with no EOLR, NO/NC with single EOLR or NC with double EOLR (5600ohm resistors) 30 programmable zone types & 8 zone options VAUX output : 12VDC, 250mA max. from Combus optional built-in tamper switch supervised by system connection for external tamper supervised by system connect up to 1,000' (305m) from control panel via COMBUS operating environment - 32 to 122F (0 to 50C) - 90% RH non-condensing current draw 30 mA (from Combus) plus power required for VAUX output if used

PC4116 16 Zone Expansion Module


provides 16 programmable hardwired zones zone supervision : zones can be NC with no EOLR, NO/NC with single EOLR or NC with double EOLR (5600ohm resistors) 30 programmable zone types & 8 zone options VAUX output : 12 VDC, 250 mA max. from Combus connection for external tamper supervised by system connect up to 1,000' (305m) from control panel via COMBUS operating environment - 32 to 122F (0 to 50C) - 90% RH non-condensing current draw 30 mA (from Combus) plus power required for VAUX output if used

Typical System Arrangement


PC4204/CF repowers the Combus as required to compensate for voltage drop

Ordering Information
PC4108A . . . . . . . . 8 hardwired zone expansion module PC4108AT . . . . . . . . 8 hardwired zone expansion module with built-in tamper switch (for use with PC5001CP enclosure only) PC4116 . . . . . . . . . . 16 hardwired zone expansion module
Connect modules to COMBUS up to 1,000' (305m) from main control panel

MAXSYS
MAIN CONTROL PANEL

ALARM SYSTEM MODULES

PC4204/CF
POWER SUPPLY RELAY OUTPUT MODULE

COMBUS - 4 conductor unshielded station wire

Listings
PC4108A
EXPANSION MODULE

PC4116
EXPANSION MODULE

USA UL864 ...... Control Units System (L, CS, -A, M, SS, WF) UL1610 .... Central Station Burglar Alarm UL609 ...... Local Burglar Alarm UL365 ...... Police Station Burglar Alarm UL985 ...... Household Fire Warning UL1023 .... Household Burglar Alarm

CANADA ULC-S527 .... Central Station Fire Alarm ULC-S302 .... Central & Monitoring Station Burglar Alarm ULC-S303 .... Local Alarm (Commercial Burglary) ULC-S310 .... Household Burglar Alarm ULC-S545 .... Household Fire Warning UL294 .......... Access Control

Digital Security Controls 1645 Flint Road, Downsview, ON Canada M3J 2J6
North American # 29002922

Distributed by :

1998 Printed in Canada 04/98