8-5.3 Schedule for Ordinary Hazard Occupancies. 8-5.3.

1 Branch lines shall not exceed eight sprinklers on either side of a cross main. Exception: Where more than eight sprinklers on a branch line are necessary, lines shall be permitted to be increased to nine sprinklers by making the two end lengths 1 in. (25.4 mm) and 11/4 in. (33 mm), respectively, and the sizes thereafter standard. Ten sprinklers shall be permitted to be placed on a branch line, making the two end lengths 1 in. (25.4 mm) and 11/4 in. (33 mm), respectively, and feeding the tenth sprinkler by a 21/2-in. (64-mm) pipe. 8-5.3.2 Pipe sizes shall be in accordance with Table 8-5.3.2(a). Exception: Where the distance between sprinklers on the branch line exceeds 12 ft (3.7 m) or the distance between the branch lines exceeds 12 ft (3.7 m), the number of sprinklers for a given pipe size shall be in accordance with Table 8-5.3.2(b). Table 8-5.3.2(a) Ordinary Hazard Pipe Schedule
1 in. 11/4 in. 11/2 in. 2 in. 21/2 in. 3 in. 31/2 in. Steel 2 sprinklers 3 sprinklers 5 sprinklers 10 sprinklers 20 sprinklers 40 sprinklers 65 sprinklers 1 in. 11/4 in. 11/2 in. 2 in. 21/2 in. 3 in. 31/2 in. 4 in. 5 in. 6 in. 8 in. Copper 2 sprinklers 3 sprinklers 5 sprinklers 12 sprinklers 25 sprinklers 45 sprinklers 75 sprinklers 115 sprinklers 180 sprinklers 300 sprinklers See Section 5-2

4 in. 100 sprinklers 5 in. 160 sprinklers 6 in. 275 sprinklers 8 in. See Section 5-2 For SI units, 1 in. = 25.4 mm.

Table 8-5.3.2(b) Number of Sprinklers Greater than 12-ft (3.7-m) Separations


21/ 2 in. 3 in. 31/2 in. Steel 15 sprinklers 30 sprinklers 60 sprinklers 21/ 2 in. 3 in. 31/2 in. Copper 20 sprinklers 35 sprinklers 65 sprinklers

For SI units, 1 in. = 25.4 mm. Note: For other pipe and tube sizes, see Table 8-5.3.2(a).

Copyright NFPA

You might also like