ASHRAE Standard 62-2001

Ventilation For Acceptable Indoor Air Quality

ASHRAE Standard 62-2001


Multiple Space Equation 6.1

Vot Y= Vst
Von X= Vst

Corrected Fraction of OA in SA Need to Know X and Z First

X Y= [1 + X Z ]
Vot
Corrected Total OA CFM Total SA CFM

Uncorrected Fraction of OA in Supply Air

Vst

Voc Z= Vsc

Von Sum of Spaces OA CFM


Critical Space OA Fraction

Voc Critical Space OA CFM

Vsc Critical Space SA CFM

ASHRAE Standard 62
HAP Space Input Considerations
Each Space Has Its Own Input For Ventilation Rate Choice of User Defined or Standard 62 ASHRAE Defined Ventilation Rates

ASHRAE Standard 62
HAP Systems Input Considerations
Use Constant Airflow Control Maintain Code Ventilation at ALL Load Points Select ASHRAE Std 62-2001 or ASHRAE Std 622001 Max Only Check Ventilation Report Details (Next Slide)

Total System Airflow

Total OA Uncorrected

X =

1665 Von = = .253 6585 Vst

Z =

375 Voc = = .321 1167 Vsc

X=.253 Z=.321

X .253 Y = = = .271 [1 + X Z ] 1 + .253 .321

ASHRAE Standard 62-2001


Benefits of Computer Calculations Some Systems Might Require You to Check Multiple Spaces to Determine Critical Space (Z Factor) Most Designers Ignore Minimum Position Point (It Could Be Critical Point) HAP Does the Math Faster and More Accurately If Over Ventilating Is Extreme, Considering Alternatives is Easy