Tyco Electronics MV Surge Arresters for cable sheath protection system CPA

High-voltage cable sheath protection system CPA Designed to the specific requirements in cable sheath protection. A robust, non tracking housing plus the high energy handling capabilities of the Raychem arrester family make it the ideal choice for the designer.
L

CPA arresters installed in a cubicle to protect HV cable sheath cross bonds

Generic technical data: CPA-xx series Rated discharge current (8/20s): Line discharge class according to IEC 60099-4 Operating duty impulse withstand current (4/10s): Long duration current impulse (2000s): 10 second temporary overvoltage (UTOV/UC) High current short circuit: (pre-failing method) (Safe non-shattering failure mode) Energy line discharge impulse high current impulse 1-7 kV Uc 10 kA Class 1 100 kA 400 A 1,25 16 kA 2,6 kJ/kV Uc 5,3 kJ/kV Uc

CPA CPA-01 CPA-02 CPA-03 CPA-04 CPA-05 CPA-06 CPA-07

Height L (mm) 94 101 107 114 123 138 148

Mechanical strength data Cantilever Tensile Torque 200 Nm 1000 N 58 Nm

Protective Characteristics CPA Uc kV

Ur kV

CPA-01 CPA-02 CPA-03 CPA-04 CPA-05 CPA-06 CPA-07

1 2 3 4 5 6 7

1,2 2,5 3,7 5,0 6,2 7,5 8,7

Ures in kV when tested to impulse waveforms Lightning Steep lightning (8/20s) (1/20s) 5kA 10kA 20kA 40kA 10kA 3,1 3,3 3,7 4,4 3,6 6,2 9,3 12,4 15,5 18,6 21,7 6,7 10,0 13,3 16,7 20,0 23,3 7,7 11,2 15,0 18,7 22,4 26,2 8,7 13,1 17,5 21,8 26,2 30,6 7,3 10,9 14,5 18,2 21,8 25,4

Switching (30/60s) 125A 500A 2,3 2,5 4,6 6,9 9,2 11,5 13,8 16,0 4,9 7,4 9,9 12,3 14,8 17,3

Uc: Continous Voltage; Ur: Rated Voltage; Ures: Residual Voltage 26