Appendix B: Controller Test Sequences

MODE LOCK 4
Parameter Checksum

This procedure displays the checksum values of the controllers various parameter sets. You can determine which (if any) of the alternate parameter sets is currently in use by comparing the checksum of the Present and Long-Term sets to those for the alternate sets. You can also tell if any of these parameter sets agree with those recorded on a parameter worksheet by comparing these checksums to those recorded on that worksheet. To view the parameter checksums, press the following keys:
4 MODE LOCK

CS= F882 P = A76F

or

If the confirming display beings with CS, the present parameter set is the same as that stored in long-term memory. If that display begins with P, the two sets differ and the checksum shown is for the present set. In that case, you can display the long-term parameter checksum by pressing the decimal key:

L = A3C2

If the two parameter sets are different, you should use the Disable Reconfiguration [MODE LOCK 5 0] procedure to disable reconfiguration. The controller will then correct any errors that occur in the present parameter set. To display the Alternate Parameter Set checksums, continue to press the decimal () key:

CS1=B94A CS2=632E CS3=44FC

You can cycle through the displays of all four (or five) checksums by continuing to press the decimal () key as many times as you want.

August 2010

UM3301 (1.3.1)