FE050B, FE100B, FE150B Power Modules: dc-dc Converters; 38 Vdc to 60 Vdc Input, 12 Vdc Output; 50 W to 150 W
Features
s s s s s s s s
High efciency: 86% typical Parallel operation with load sharing Low prole: 12.7 mm (0.5 in.) Complete input and output ltering Within FCC requirements for Telecom Constant frequency Case ground pin Input-to-output isolation Remote sense Remote on/off Short-circuit protection Output overvoltage clamp
The FE050B, FE100B, and FE150B Power Modules use advanced, surface-mount technology and deliver high-quality, compact, dc-dc conversion at an economical price.
s s s
Applications
s s
s s
Options
s
* UL is a registered trademark of Underwriters Laboratories, Inc. CSA is a registered trademark of Canadian Standards Association. TV is a registered trademark of Technischer berwachungsVerein.
Description
The FE050B, FE100B, and FE150B Power Modules are dc-dc converters that operate over an input voltage range of 38 Vdc to 60 Vdc and provide a precisely regulated dc output. The outputs are fully isolated from the inputs, allowing versatile polarity congurations and grounding connections. The modules have maximum power ratings from 50 W to 150 W at a typical full-load efciency of 86%. Built-in ltering, for both the input and output of each device, eliminates the need for external lters. Two or more modules may be paralleled with forced load sharing for redundant or enhanced power applications. The package, which mounts on a printed-circuit board, accommodates a heat sink for high-temperature applications.
FE050B, FE100B, FE150B Power Modules: dc-dc Converters; 38 Vdc to 60 Vdc Input, 12 Vdc Output; 50 W to 150 W
Tstg
55
125
Electrical Specications
Unless otherwise indicated, specications apply over all operating input voltage, resistive load, and temperature conditions. Table 1. Input Specications Parameter Operating Input Voltage Maximum Input Current (VI = 0 V to 60 V): FE050B FE100B FE150B Inrush Transient Input Reected-ripple Current, Peak-to-peak (5 Hz to 20 MHz, 12 H source impedance) (See Figure 9.) Input Ripple Rejection (120 Hz) Fusing Considerations CAUTION: This power module is not internally fused. An input line fuse must always be used. This encapsulated power module can be used in a wide variety of applications, ranging from simple stand-alone operation to an integrated part of a sophisticated power architecture. To preserve maximum exibility, internal fusing is not included; however, to achieve maximum safety and system protection, always use an input line fuse. The safety agencies require a normal-blow, dc fuse with a maximum rating of 6 A (see Safety Considerations section). Based on the information provided in this data sheet on inrush energy and maximum dc input current, the same type of fuse with a lower rating can be used. Refer to the fuse manufacturers data for further information. Symbol VI II, max II, max II, max i2t Min 38 Typ 48 20 Max 60 2 4 6 1.0 Unit Vdc A A A A2s mAp-p
60
dB
FE050B, FE100B, FE150B Power Modules: dc-dc Converters; 38 Vdc to 60 Vdc Input, 12 Vdc Output; 50 W to 150 W
11.76 11.76
0.05 0.2
Vdc Vdc % % mV
70 200
mVrms mVp-p
IO IO IO
1 1 1 103
A A A % IO, max
135
170
% IO, max
0 0 0
F F F
84 85 85
85 86 86
% % %
mV s mV s
FE050B, FE100B, FE150B Power Modules: dc-dc Converters; 38 Vdc to 60 Vdc Input, 12 Vdc Output; 50 W to 150 W
General Specications
Parameter Calculated MTBF (IO = 80% of IO, max; TC = 40 C) Weight Min Typ 2,000,000 Max 200 (7) Unit hours g (oz.)
Feature Specications
Unless otherwise indicated, specications apply over all operating input voltage, resistive load, and temperature conditions. See Feature Descriptions for further information. Parameter Remote On/Off Signal Interface (VI = 0 V to 60 V; open collector or equivalent compatible; signal referenced to VI () terminal; see Figure 12 and Feature Descriptions.): Logic LowModule On Logic HighModule Off Logic Low: At Ion/off = 1.0 mA At Von/off = 0.0 V Logic High: At Ion/off = 0.0 A Leakage Current Turn-on Time (IO = 80% of IO, max; VO within 1% of steady state) Output Voltage Adjustment (See Feature Descriptions.): Output Voltage Remote-sense Range Output Voltage Set-point Adjustment Range (trim) Parallel Operation Load Sharing (See Feature Descriptions.) Output Overvoltage Clamp Symbol Min Typ Max Unit
1.2 1.0 18 50 10
V mA V A ms
VO, clamp
90 13.2
14.7
FE050B, FE100B, FE150B Power Modules: dc-dc Converters; 38 Vdc to 60 Vdc Input, 12 Vdc Output; 50 W to 150 W
Characteristic Curves
The following gures provide typical characteristics for the FE150B Power Module. The FE050B and FE100B characteristics are similar to the FE150B characteristics provided here, scaled by power level where appropriate.
6 5
INPUT CURRENT, II (A)
90 85
EFFICIENCY, (%)
80 75 70 65 60 55 50 0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 VI = 38 V VI = 48 V VI = 60 V
88 86
EFFICIENCY, (%)
VI = 38 V VI = 49 V VI = 60 V
8-890 (C)
FE050B, FE100B, FE150B Power Modules: dc-dc Converters; 38 Vdc to 60 Vdc Input, 12 Vdc Output; 50 W to 150 W
20 mV
1 s
100 mV
50 s
TIME, t (1 s/div)
8-893 (C) 8-895 (C)
Figure 5. Typical FE150B Output Ripple Voltage at Room Temperature, 48 V Input, and 12.5 A Output
Figure 7. Typical FE150B Transient Response to Step Increase in Load from 50% to 75% of Full Load at Room Temperature and 48 V Input (Waveform Averaged to Eliminate Ripple Component.)
100 mV
50 s
1 ms
TIME, t (1 ms/div)
8-894 (C)
8-896 (C)
Figure 6. Typical FE150B Transient Response to Step Decrease in Load from 50% to 25% of Full Load at Room Temperature and 48 V Input (Waveform Averaged to Eliminate Ripple Component.)
Figure 8. Typical FE150B Start-Up Transient at Room Temperature, 48 V Input, and 12.5 A Output
FE050B, FE100B, FE150B Power Modules: dc-dc Converters; 38 Vdc to 60 Vdc Input, 12 Vdc Output; 50 W to 150 W
Test Congurations
TO OSCILLOSCOPE LTEST 12 H CS 220 F ESR < 0.1 33 F @ 20 C, 100 kHz ESR < 0.7 @ 100 kHz V I () CURRENT PROBE V I (+)
Design Considerations
Input Source Impedance
The power module should be connected to a low ac-impedance input source. Highly inductive source impedances can affect the stability of the power module. For the test conguration in Figure 9, a 33 F electrolytic capacitor (ESR < 0.7 at 100 kHz) mounted close to the power module helps ensure stability of the unit. For other highly inductive source impedances, consult the factory for further application guidelines.
BATTERY
8-203 (C).l
Note: Measure input reected-ripple current with a simulated source inductance (LTEST) of 12 H. Capacitor CS offsets possible battery impedance. Measure current as shown above.
Safety Considerations
For safety-agency approval of the system in which the power module is used, the power module must be installed in compliance with the spacing and separation requirements of the end-use safety agency standard, i.e., UL-1950, CSA 22.2-950, and EN60950. For the converter output to be considered meeting the requirements of safety extra-low voltage (SELV), the input must meet SELV requirements.
PARALLEL SENSE(+) SENSE() VO(+) IO VI() VO() CONTACT AND DISTRIBUTION LOSSES
8-683 (C)
VI(+) SUPPLY II
LOAD
If the input meets extra-low voltage (ELV) requirements, then the converters output is considered ELV. The input to these units is to be provided with a maximum 6 A normal-blow fuse in the ungrounded lead.
CONTACT RESISTANCE
Note: All measurements are taken at the module terminals. When socketing, place Kelvin connections at module terminals to avoid measurement errors due to socket contact resistance.
[ V O ( + ) V O ( ) ] I O x 100 = ------------------------------------------------ [ V I ( + ) V I ( ) ] I I - Figure 10. Output Voltage and Efciency Measurement Test Setup
8-513 (C)
Note: Use a 0.1 F ceramic capacitor. Scope measurement should be made using a BNC socket. Position the load between 50 mm (2 in.) and 76 mm (3 in.) from the module.
Figure 11. Peak-to-Peak Output Noise Measurement Test Setup Lucent Technologies Inc. 7
FE050B, FE100B, FE150B Power Modules: dc-dc Converters; 38 Vdc to 60 Vdc Input, 12 Vdc Output; 50 W to 150 W
Electrical Descriptions
Current Limit
To provide protection in a fault (output overload) condition, the unit is equipped with internal current-limiting circuitry and can endure current limiting for an unlimited duration. At the point of current-limit inception, the unit shifts from voltage control to current control. If the output voltage is pulled very low during a severe fault, the current-limit circuit can exhibit either foldback or tailout characteristics (output-current decrease or increase). The unit operates normally once the output current is brought back into its specied range.
given in the Feature Specications table, i.e.: [VO(+) VO()] [SENSE(+) SENSE()] 1.2 V The voltage between the VO(+) and VO() terminals must not exceed the minimum output overvoltage clamp voltage as indicated in the Feature Specications table. This limit includes any increase in voltage due to remote-sense compensation and output voltage set-point adjustment (trim), see Figure 13. If not using the remote-sense feature to regulate the output at the point of load, connect SENSE(+) to VO(+) and SENSE() to VO() at the module.
PARALLEL SENSE(+)
Feature Descriptions
Remote On/Off
To turn the power module on and off, the user must supply a switch to control the voltage between the on/off terminal and the VI() terminal (Von/off). The switch can be an open collector or equivalent (see Figure 12). A logic low is Von/off = 0 V to 1.2 V, during which the module is on. The maximum Ion/off during a logic low is 1 mA. The switch should maintain a logic-low voltage while sinking 1 mA. During a logic high, the maximum Von/off generated by the power module is 15 V. The maximum allowable leakage current of the switch at Von/off = 15 V is 50 A. If not using the remote on/off feature, short the ON/OFF pin to VI().
VI(+) SUPPLY II VI() CONTACT RESISTANCE
IO
LOAD
+
Von/off
Remote Sense
Remote sense minimizes the effects of distribution losses by regulating the voltage at the remote-sense connections. For single-unit operation, the PARALLEL pin should be connected to SENSE(). The voltage between the remote-sense pins and the output terminals must not exceed the output voltage sense range 8
Connecting the external resistor (Rtrim-down) between the TRIM and SENSE(+) pins (VO, adj) decreases the output voltage set point as dened in the following equation: ( V O, adj 1.25 ) 17.8 R trim-down = ------------------------------------------------------12 V O, adj k
FE050B, FE100B, FE150B Power Modules: dc-dc Converters; 38 Vdc to 60 Vdc Input, 12 Vdc Output; 50 W to 150 W
Adjustment Without TRIM Pin The output voltage can be adjusted by placing an external resistor (Radj) between the SENSE(+) and VO(+) terminals (see Figure 16). By adjusting Radj, the output voltage can be increased by 10% of the nominal output voltage. The equation below shows the resistance required to obtain the desired output voltage. Radj = (VO, adj VO, nom) 899
PARALLEL SENSE(+) SENSE() VI(+) VO(+) IO VI() CONTACT RESISTANCE VO() CONTACT AND DISTRIBUTION LOSSES
8-710 (C).c
Radj
Rtrim-up TRIM PARALLEL SENSE(+) SENSE() VI(+) SUPPLY II VI() CONTACT RESISTANCE VO(+) IO VO() CONTACT AND DISTRIBUTION LOSSES
8-717 (C).c
SUPPLY
II
LOAD
VI(+) SUPPLY II
LOAD
The parallel pins of all units must be connected together. The paths of these connections should be as direct as possible. All remote-sense pins should be connected to the power bus at the same point, i.e., connect all SENSE(+) pins to the (+) side of the power bus at the same point and all SENSE() pins to the () side of the power bus at the same point. Close proximity and directness are necessary for good noise immunity.
FE050B, FE100B, FE150B Power Modules: dc-dc Converters; 38 Vdc to 60 Vdc Input, 12 Vdc Output; 50 W to 150 W
Lucent
FE150B9 DC-DC Power Module
IN:DC 48V, 3.7A
CASE ON/OFF + IN
OUT:DC 12V, 12.5A OUT 150W + MADE IN USA Protected by U.S. Patents: 5,036,452 5,179,365
TUV Rheinland
8-582 (C).p
Figure 18. Case Temperature Measurement Location The temperature at this location should not exceed 95 C. The maximum case temperature can be limited to a lower value for extremely high reliability. The output power of the module should not exceed the rated power for the module as listed in the Ordering Information table. For additional information about these modules, refer to the Lucent Technologies Thermal Management for High-Power Board-Mounted Power Modules Technical Note (TN97-009EPS).
30
Thermal Considerations
Introduction
The power modules operate in a variety of thermal environments; however, sufcient cooling should be provided to help ensure reliable operation of the unit. Heat-dissipating components inside the unit are thermally coupled to the case. Heat is removed by conduction, convection, and radiation to the surrounding environment. Proper cooling can be veried by measuring the case temperature. Peak temperature occurs at the position indicated in Figure 18.
20
10
0.1 m/s (20 ft./min.) NATURAL CONVECTION
0 0 20 40 60 80 100
8-587 (C)
Figure 19. Power Derating vs. Local Ambient Temperature and Air Velocity
10
FE050B, FE100B, FE150B Power Modules: dc-dc Converters; 38 Vdc to 60 Vdc Input, 12 Vdc Output; 50 W to 150 W
5.0 NO HEAT SINK 4.0 3.0 2.0 1.0 0.0 NAT CONV 0.25 in. HEAT SINK 0.5 in. HEAT SINK 1 in. HEAT SINK
THERMAL RESISTANCE,
0.5 (100)
1.0 (200)
1.5 (300)
2.0 (400)
2.5 (500)
Figure 21. Heat Sink Resistance Curves; Fins Oriented Along Length These measured resistances are from heat transfer from the sides and bottom of the module as well as the top side with the attached heat sink; therefore, the case-to-ambient thermal resistances shown are generally lower than the resistance of the heat sink by itself. The module used to collect the data in Figure 20 and Figure 21 had a thermal-conductive dry pad between the case and the heat sink to minimize contact resistance. To choose a heat sink, determine the power dissipated as heat by the unit for the particular application. Figure 22 shows typical heat dissipation for a range of output currents and three voltages for the FE050B, FE100B, and FE150B.
5.0 NO HEAT SINK 4.0 3.0 2.0 1.0 0.0 NAT CONV 0.25 in. HEAT SINK 0.5 in. HEAT SINK 1 in. HEAT SINK
THERMAL RESISTANCE,
0.5 (100)
1.0 (200)
1.5 (300)
2.0 (400)
2.5 (500)
Figure 20. Heat Sink Resistance Curves; Fins Oriented Along Width
11
FE050B, FE100B, FE150B Power Modules: dc-dc Converters; 38 Vdc to 60 Vdc Input, 12 Vdc Output; 50 W to 150 W
Use Figure 20 and Figure 21 to determine air velocity for the 0.5 inch heat sink. The minimum airow necessary for the FE150B module depends on heat sink n orientation and is shown below:
s s
0.4 m/s (80 ft./min.) (oriented along width) 0.45 m/s (90 ft./min.) (oriented along length)
VI = 49 V VI = 38 V VI = 60 V
PD Figure 22. FE150B Power Dissipation as Heat vs. Output Current Example If an 85 C case temperature is desired, what is the minimum airow necessary? Assume the FE150B module is operating at low line and an output current of 12.5 A, maximum ambient air temperature of 40 C, and the heat sink is 0.5 inch. Solution Given: VI = 38 V IO = 12.5 A TA = 40 C TC = 85 C Heat sink = 0.5 inch. Determine PD by using Figure 22: PD = 24 W Then solve the following equation: (TC TA) ca = ----------------------PD 85 40 ) ca = ( ----------------------24
TA
Figure 23. Resistance from Case-to-Sink and Sinkto-Ambient For a managed interface using thermal grease or foils, a value of cs = 0.1 C/W to 0.3 C/W is typical. The solution for heat sink resistance is: sa = ------------------------ cs
PD (TC TA)
This equation assumes that all dissipated power must be shed by the heat sink. Depending on the userdened application environment, a more accurate model, including heat transfer from the sides and bottom of the module, can be used. This equation provides a conservative estimate for such instances.
Layout Considerations
Copper paths must not be routed beneath the power module standoffs.
ca = 1.88 C/W
12
FE050B, FE100B, FE150B Power Modules: dc-dc Converters; 38 Vdc to 60 Vdc Input, 12 Vdc Output; 50 W to 150 W
Outline Diagram
Dimensions are in millimeters and (inches). Tolerances: x.x mm 0.5 mm (x.xx in. 0.02 in.), x.xx mm 0.25 mm (x.xxx in. 0.010 in.) Top View
121.9 (4.80)
5.3 (0.21)
Lucent
52.83 (2.080) 63.5 (2.50)
CASE ON/OFF + IN
TRIM PARALLEL
+ SENSE OUT
TUV Rheinland
5.3 (0.21)
55.63 (2.190)
55.63 (2.190)
FOR OPTIONAL HEAT SINK MOUNTING #4-40 THD 4.6 (0.18) DEEP 6 PLCS
Side View
SIDE MARKING 12.7 (0.50) 1.57 (0.062) 0.05 (0.002) DIA TIN-PLATED BRASS TYP 12 PLCS 1.0 (0.04)
Bottom View
113.54 (4.470) 12.2 (0.48) 20.32 (0.800) 25.40 30.48 (1.000) (1.200) 35.56 (1.400)
15.24 (0.600)
13
FE050B, FE100B, FE150B Power Modules: dc-dc Converters; 38 Vdc to 60 Vdc Input, 12 Vdc Output; 50 W to 150 W
15.24 (0.600)
OUT +
35.56 30.48 (1.400) 25.40 (1.200) 20.32 (1.000) (0.800) 12.2 (0.48)
8-719 (C).m
Ordering Information
This family of modules is not recommended for new designs. For new designs, we recommend the JFW family of power modules. Please refer to the Lucent Technologies Power Systems Selection Guide or to individual data sheets. For further assistance, you may call the Lucent Technologies Power Systems Technical Hotline (1-800-526-7819 or 972-284-2626). Optional TRIM pin is designated by the ending 9 in device code name. Input Voltage 48 V 48 V 48 V 48 V 48 V 48 V Output Voltage 12 V 12 V 12 V 12 V 12 V 12 V Output Power 50 W 100 W 150 W 50 W 100 W 150 W Trim Yes Yes Yes No No No Device Code FE050B9 FE100B9 FE150B9 FE050B FE100B FE150B Comcode Not Available Not Available Not Available 106258304 106258353 105775530
14
FE050B, FE100B, FE150B Power Modules: dc-dc Converters; 38 Vdc to 60 Vdc Input, 12 Vdc Output; 50 W to 150 W
Notes
15
FE050B, FE100B, FE150B Power Modules: dc-dc 38 Vdc to 60 Vdc Input, 12 Vdc Output; 50 W to 150 W
For additional information, contact your Lucent Technologies Account Manager or the following: POWER SYSTEMS UNIT: Network Products Group, Lucent Technologies Inc., 3000 Skyline Drive, Mesquite, TX 75149, USA +1-800-526-7819 (Outside U.S.A.: +1-972-284-2626, FAX +1-972-329-8202) (product-related questions or technical assistance) INTERNET: http://www.lucent.com E-MAIL: techsupport@lucent.com ASIA PACIFIC: Lucent Technologies Singapore Pte. Ltd., 750A Chai Chee Road #05-01, Chai Chee Industrial Park, Singapore 469001 Tel. (65) 240 8041, FAX (65) 240 8053 JAPAN: Lucent Technologies Japan Ltd., 7-18, Higashi-Gotanda 2-chome, Shinagawa-ku, Tokyo 141-0022, Japan Tel. (81) 3 5421 1600, FAX (81) 3 5421 1700 LATIN AMERICA: Lucent Technologies Inc., Room 9N128, One Alhambra Plaza, Coral Gables, FL 33134, USA Tel. +1-305-569-4722, FAX +1-305-569-3820 EUROPE: Data Requests: DATALINE: Tel. (44) 1189 324 299, FAX (44) 1189 328 148 Technical Inquiries:GERMANY: (49) 89 95086 0 (Munich), UNITED KINGDOM: (44) 1344 865 900 (Bracknell), FRANCE: (33) 1 48 83 68 00 (Paris), SWEDEN: (46) 8 600 7070 (Stockholm), FINLAND: (358) 9 4354 2800 (Helsinki), ITALY: (39) 2 6608131 (Milan), SPAIN: (34) 1 807 1441 (Madrid)