Professional Documents
Culture Documents
LOW SMOKE & HALOGEN FREE FLAME RETARDANT CABLES WITH ARMOUR
34
Standards Achieved :
Construction
Flame propagation
Acid gas emission
Smoke emission
Construction :
: BS 6724
: BS EN 60332-3
: BS EN 60754-2
: BS EN 61034
1. Conductor
2. Insulation
Classification :
3. Filler
4. Binding tape
5. Bedding
6. Armour
7. Binding tape
8. Outer sheath
Application :
: 90C
: 1,000 V
: 3,500 V
Preferably used for installation into conduit and open tray wiring which provide
flame retardant, low smoke & corrosive gases properties in case of fire.
No.
Conductor
Thickness Thickness
of
Cross- No. of Diameter
of
of
core sectional wires
insulation bedding
area
Diameter
of
wire
armour
Thickness
of
outer
sheath
Overall
diameter
Conductor
resistance
at 20C
mm
mm
mm
mm
/km
Current
rating
in free air
at 40C
ambient
A
(Max.)
12.1
7.41
4.61
3.08
1.83
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
0.0470
26
35
46
59
80
105
140
170
210
260
320
370
420
480
560
635
725
mm2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
mm
mm
Cable
weight
Standard
length
kg/km
(Approx.)
290
360
430
510
630
930
1,280
1,760
2,240
2,850
3,910
4,670
5,540
7,190
8,890
10,700
13,080
500
500
500
500
500
500
500
500
500
500
500
400
400
300
250
200
100
16
Revision : 01, May 2010
16