You are on page 1of 1

PUMP HEAD CALCULATION - ETP - TG BUILDING (Tag no.

PPCle91- 023 & 024) PRESSURE DROP IN PIPES (AS PER HAZEN WILLIAMS)
Sl. No. Pipe ID(mm "C" )"d" Q (Cu.M/hr) Area "A" in m2 V M/s Pipe Length (m)"L" Hydraulic Head loss in radius pipe (D/4) in m (m)

(AS PER DARCY'S)


Head loss in pipe (m)

Description

MSRL pipe - Suction side MSRL pipe Discharge side

65

140

0.00332

0.42

0.016

0.018

0.011676

100

140

0.00785

0.18

400

0.025

0.173

0.108384

PRESSURE DROP IN FITTINGS (AS PER DARCY'S)


Sl. No. m (cp) Reducer( Expander Strainer(n 90 deg Friction no.) (no.) o.) elbows (no.) factor(f) (K=0.5) (K=0.5) (K=420) (K= 30) 45 deg elbows (no.) (K=16) Tee(nos.) Flow thru run (K=20) Tee(no s.) Flow thru branch (K=60) 1 Gate valve (nos.) (K=8) NRV (nos.) (K=50) Butterfly valve (nos.) (K=25) Equivalent length of valves & fitings Total Friction Strainer Friction loss in loss loss in fittings (m) fittings MLC"Hf" MLC

Description

Re

MSRL pipe - Suction side MSRL pipe Discharge side

1000 2.72E+04

0.017

131

0.020

0.5

0.520

1000 1.77E+04

0.017

350.5

0.009

0.009

OTHER LOSSES
ENTRANCE LOSS(K=0.5) EXIT LOSS(K=1) = = 0.00446 0.00159 m m

TOTAL PRESSURE DROP IN PIPES & FITTINGS


1 Suction side Total Pressure drop in pipes & fittings Considering 10% margin Total Pressure drop in pipes & fittings = = = = 0.542 0.596 0.184 0.202 MLC MLC MLC MLC

2 Discharge side

PUMP HEAD CALCULATION SUCTION SIDE


Static Suction lift Velocity Head Total friction head Total Dynamic Suction head mlc mlc mlc mlc 3.400 0.009 0.596 3.987

DISCHARGE SIDE
Static Discharge head Velocity Head Total friction head Total Dynamic Discharge head mlc mlc mlc mlc 1.000 0.002 0.202 1.204

Suction pipe size (mm) 65 80 100

TDH (MWC)

5.2 5.2 5.2

TOTAL DYNAMIC HEAD Selected head as per Tender.

5.19 10

MWC MWC

Selected head is greater than the calculated head, hence OK