TEST REPORT FOR DRY TYPE TRANSFORMER

Client : JSPL Project:

SHEET : 1

OF: 27

1. 2.

Location

: Process Boiler

Name plate details : Make Capacity Voltage Rating Current Rating KIRLOSKOR 1.25MVA 6600V 433A

TEST REPORT FOR DRY TYPE TRANSFORMER

Client : JSPL Project:

SHEET : 2

OF: 27

Sr.No. Vector Group Phases Frequency % Imp. Volt Type of cooling 3. General Inspection

10CMC015/4 Dyn11 03 50Hz 5.19 AN :

4. Insulation Resistance and Polarization Index Test :

TEST REPORT FOR DRY TYPE TRANSFORMER

Client : JSPL Project:

SHEET : 3

OF: 27

Ref. Pri Earth Pri Sec Sec Earth

Applied Voltage(V)

PI Value

5000V 5000V 500V

2.10 1.97 1.95

5. Magnetizing Current Test: RY Applied Voltage(V) YB BR Measured Magnetizing current (mA) R Y B

TEST REPORT FOR DRY TYPE TRANSFORMER

Client : JSPL Project:

SHEET : 4

OF: 27

422

423

420

39.5

28.9

27.5

6.Magnetic Balance Test: Ref Measured Values(V)

TEST REPORT FOR DRY TYPE TRANSFORMER

Client : JSPL Project:

SHEET : 5

OF: 27

RY 423 -

YB 423 -

BR 422

RY 209 111.4

YB 306 310

BR 117.3 212.2 -

7. Vector Group Verification: Conditions: (i) 1U1V=2U2N+2N1V, 424=15.9+406

TEST REPORT FOR DRY TYPE TRANSFORMER

Client : JSPL Project:

SHEET : 6

OF: 27

(ii)

1W2W>1W2V, 423>396

(iii)

1U2W=1U2V, 399.8=400

TEST REPORT FOR DRY TYPE TRANSFORMER

Client : JSPL Project:

SHEET : 7

OF: 27

The above conditions are satisfied.

TEST REPORT FOR DRY TYPE TRANSFORMER

Client : JSPL Project:

SHEET : 8

OF: 27

8. Ratio Test: Tap 1 2 Applied Primary voltage (V) RY YB BR 424 426 423 426 421 425 Measured secondary Voltage (V) Rn yn Bn 26.6 27.2 26.4 27.3 26.4 27.2

TEST REPORT FOR DRY TYPE TRANSFORMER

Client : JSPL Project:

SHEET : 9

OF: 27

3 (At Nominal Tap) 4 5

422 424 426

423 425 425

420 424 423

27.9 28.6 29.5

27.8 28.4 29.2

27.9 28.4 29.2

9. Winding Resistance Test:

TEST REPORT FOR DRY TYPE TRANSFORMER

Client : JSPL Project:

SHEET : 10

OF: 27

Tap 1 2 3 4 5

Primary Measured resistance value m RY 284 277 271 264 257 YB 284 277 270 264 257 Secondary BR 285 278 271 264 258

TEST REPORT FOR DRY TYPE TRANSFORMER

Client : JSPL Project:

SHEET : 11

OF: 27

Measured resistance value (m) At nominal tap 3 rn 0.30 yn 0.32 Bn 0.32

10.

Functional checks: (Whether Operational Checks OK / Not OK / Not Applicable)

TEST REPORT FOR DRY TYPE TRANSFORMER

Client : JSPL Project:

SHEET : 12

OF: 27

1 2

Inspection of any physical damages Tightness of power cable checks

OK OK

11.

Remarks

TEST REPORT FOR DRY TYPE TRANSFORMER

Client : JSPL Project:

SHEET : 13

OF: 27

TEST REPORT FOR DRY TYPE TRANSFORMER

Client : JSPL Project:

SHEET : 14

OF: 27

TEST REPORT FOR DRY TYPE TRANSFORMER

Client : JSPL Project:

SHEET : 15

OF: 27

1. 2.

Location

: Process Boiler

Name plate details : Make Capacity Voltage Rating Current Rating KIRLOSKOR 1.25MVA 6600V 433A

TEST REPORT FOR DRY TYPE TRANSFORMER

Client : JSPL Project:

SHEET : 16

OF: 27

Sr.No. Vector Group Phases Frequency % Imp. Volt Type of cooling 3. General Inspection

10 CMC015/3 Dyn11 03 50Hz 5.19 AN :

4. Insulation Resistance and Polarization Index Test :

TEST REPORT FOR DRY TYPE TRANSFORMER

Client : JSPL Project:

SHEET : 17

OF: 27

Ref. Pri Earth Pri Sec Sec Earth

Applied Voltage(V)

PI Value

5000V 5000V 500V

1.92 1.63 2.10

5. Magnetizing Current Test: Applied Voltage(V) Measured Magnetizing current (mA)

TEST REPORT FOR DRY TYPE TRANSFORMER

Client : JSPL Project:

SHEET : 18

OF: 27

RY 424

YB 424

BR 420

R 27.5

Y 21.7

B 21.8

6.Magnetic Balance Test: RY 424 Ref YB BR RY Measured Values(V) YB 282 BR 141.4

TEST REPORT FOR DRY TYPE TRANSFORMER

Client : JSPL Project:

SHEET : 19

OF: 27

426 -

420

214 149

272

211 -

7. Vector Group Verification: Conditions: (i) 1U1V=2U2N+2N1V, 423.3=15.9+407

TEST REPORT FOR DRY TYPE TRANSFORMER

Client : JSPL Project:

SHEET : 20

OF: 27

(ii)

1W2W>1W2V, 422>395

(iii)

1U2W=1U2V, 397=397.3

TEST REPORT FOR DRY TYPE TRANSFORMER

Client : JSPL Project:

SHEET : 21

OF: 27

The above conditions are satisfied.

8. Ratio Test:

TEST REPORT FOR DRY TYPE TRANSFORMER

Client : JSPL Project:

SHEET : 22

OF: 27

Tap 1 2 3 (At Nominal Tap)

Applied Primary voltage (V) RY YB BR 423 426 422 424 426 423 421 425 420

Measured secondary Voltage (V) rn yn Bn 26.1 26.9 27.7 26.3 26.9 27.5 26.2 26.8 27.5

TEST REPORT FOR DRY TYPE TRANSFORMER

Client : JSPL Project:

SHEET : 23

OF: 27

4 5

424 426

425 425

424 423

28.7 29.3

28.6 29.4

28.5 29.4

9. Winding Resistance Test: Tap Primary Measured resistance value m

TEST REPORT FOR DRY TYPE TRANSFORMER

Client : JSPL Project:

SHEET : 24

OF: 27

RY 1 2 3 4 5 At nominal tap 3 286 278 270 264 256

YB

BR 285 278 270 263 257 m Bn 0.32

285 277 269 263 257 Secondary Measured resistance value yn 0.32

rn 0.30

TEST REPORT FOR DRY TYPE TRANSFORMER

Client : JSPL Project:

SHEET : 25

OF: 27

10.

Functional checks: (Whether Operational Checks OK / Not OK / Not Applicable) 1 2 Inspection of any physical damages Tightness of power cable checks OK OK

TEST REPORT FOR DRY TYPE TRANSFORMER

Client : JSPL Project:

SHEET : 26

OF: 27

11.

Remarks

TEST REPORT FOR DRY TYPE TRANSFORMER

Client : JSPL Project:

SHEET : 27

OF: 27