PROJECT: PROJECT: 2 X 660 MW IB THERMAL POWER STATION

TEST REPORT CUM COMISSIONING PROTOCOL


DRY TYPE TRANSFORMER 5
IDCT-PMCC

CLIENT ODHISHA POWER GENERATION CORPORATION LTD Page 1 of 7


EPC-BOP BGR ENERGY SYSTEMS LTD - POWER PROJECT DIVISION Date: 16.6.17

1. DRY TYPE TRANSFORMER DETAILS

1 Area /Location IDCT-PMCC


2 Application Indoor
3 Drawing No -
4 Make VOLTAMP,VADODARA
6 KVA 1000
7 Sl. No 62545/2
8 Voltage(Pri/Sec) & 11KV/433V & 50Hz
Frequency
9 Primary Current 52.49A
10 Secondary Current 1333.37A
11 Vector Group Dyn11
12 Degree of Protection IP-33
13 % Impedance 5.10%
14 CT (Ratings) if applicable 500/1A,CL-5P20,15VA

2. Clearances:

Check the electrical clearance for live parts or as per requirement / drawing
1. HV Phase to Phase OK
2. HV Phase to Earth OK
3. LV Phase to Phase OK
4. LV Phase to Earth OK

NAME DESIGNATION SIGNATURE DATE


TEST ENGR. Suresh M Testing Engr.
BGRESL Rathina Kumar D Dy.Manager
OPGCL
PROJECT: PROJECT: 2 X 660 MW IB THERMAL POWER STATION

TEST REPORT CUM COMISSIONING PROTOCOL


DRY TYPE TRANSFORMER 5
IDCT-PMCC

CLIENT ODHISHA POWER GENERATION CORPORATION LTD Page 2 of 7


EPC-BOP BGR ENERGY SYSTEMS LTD - POWER PROJECT DIVISION Date: 16.6.17

3. Verification of Voltage Ratio

PRIMARY(IN VOLT) SECONDARY(IN VOLT) Tolerance Results


TAP
NO

R-Y Y-B B-R R-Y Y-B B-R R-N Y-N B-N OK

1 423 425 419 15.88 15.79 15.77 9.16 9.10 9.10 OK

2 422 420 418.5 16.22 16.16 16.18 9.36 9.38 9.34 OK


+/-5
3 421.3 420.3 419.3 16.61 16.53 16.59 9.59 9.58 9.54 OK

4 421.5 420.3 418.6 17.08 17.00 16.95 9.84 9.82 9.78 OK

5 420 420 419 17.4 17.4 17.41 10.12 10.09 10.04 OK

4. Verification of Vector Group (Dyn11)

NAME DESIGNATION SIGNATURE DATE


TEST ENGR. Suresh M Testing Engr.
BGRESL Rathina Kumar D Dy.Manager
OPGCL
PROJECT: PROJECT: 2 X 660 MW IB THERMAL POWER STATION

TEST REPORT CUM COMISSIONING PROTOCOL


DRY TYPE TRANSFORMER 5
IDCT-PMCC

CLIENT ODHISHA POWER GENERATION CORPORATION LTD Page 3 of 7


EPC-BOP BGR ENERGY SYSTEMS LTD - POWER PROJECT DIVISION Date: 16.6.17

APPLIED VOLTAGE
1U 1V 419.8
1V 1W 419.3
1W 1U 418.5
MEASURED VOLTAGE
1V2v 405.3
1W2w 404.6
1U1V 419.8
1V2n 411.5
1V2w 406.8
1W2v 412.1
1U2n 9.55
Acceptance Criteria
Check the Measured Values for satisfaction of the following Conditions

I. 1V2v = 1V2w
405.3=406.8

II. 1W2w < 1W2v


404.6 < 412.1

III. 1U1V = 1U2n+ 1V2n.


419.8=9.55+411.5
419.8=421.05

NAME DESIGNATION SIGNATURE DATE


TEST ENGR. Suresh M Testing Engr.
BGRESL Rathina Kumar D Dy.Manager
OPGCL
PROJECT: PROJECT: 2 X 660 MW IB THERMAL POWER STATION

TEST REPORT CUM COMISSIONING PROTOCOL


DRY TYPE TRANSFORMER 5
IDCT-PMCC

CLIENT ODHISHA POWER GENERATION CORPORATION LTD Page 4 of 7


EPC-BOP BGR ENERGY SYSTEMS LTD - POWER PROJECT DIVISION Date: 16.6.17

5. Magnetizing Current test: At nominal tap, Tap No.:

Applied Volts Measure Current


1U1V 1V1W 1W1U 1U 1V 1W
421.3 420.3 419.3 15.1mA 10.8mA 11.3mA

Acceptance Criteria:
General Pattern is two similar readings on Outer phases and one lower
reading on Center Phase
Note:
Possible Abnormalities shall be found using this test is
Winding inter-turn Failure, Shift of Winding & Core Defects

6. MAGNETIC BALANCE TEST

Voltage Voltage Measured Between (v)


Applied
Between R-Y Y-B B-R r-y y-b b-r r-n y-n b-n
(v)
B 420 311.5 109.7 16.69 4.59 12.09 9.59 7.09 2.48
Y 114.8 305.4 420.1 4.36 16.49 12.14 2.58 6.94 9.54
R 215 420 205 14.49 14.28 0.229 4.90 9.58 4.68

Acceptance Criteria:

The Voltage Induced in the Center Phase may be 50 to 90% of the applied Voltage
when the Voltage applied in the Outer phase
When the Voltage is applied in Center Phase, then the voltage induced in the outer
phases may be 30% to 70% of applied Voltage
Note:
Zero or Negligible voltage induced in other two phase is not acceptable and should be
investigated
NAME DESIGNATION SIGNATURE DATE
TEST ENGR. Suresh M Testing Engr.
BGRESL Rathina Kumar D Dy.Manager
OPGCL
PROJECT: PROJECT: 2 X 660 MW IB THERMAL POWER STATION

TEST REPORT CUM COMISSIONING PROTOCOL


DRY TYPE TRANSFORMER 5
IDCT-PMCC

CLIENT ODHISHA POWER GENERATION CORPORATION LTD Page 5 of 7


EPC-BOP BGR ENERGY SYSTEMS LTD - POWER PROJECT DIVISION Date: 16.6.17

7. WINDING RESISTANCE MEASUREMENT


7.1 HV WINDING
Configuration Delta Amb Temp

TAP No
Phase Resistance ,Rt (Ohms) Resistance ,R75(Ohms) Remarks

R-Y 649.76
566 m
Y-B 648.62
1 565 m
B-R 648.62
565 m
R-Y 635.99
554 m
Y-B 634.84
2 553 m
B-R 637.14
555 m
R-Y 615.32
536 m
Y-B 616.47
3 537 m
B-R 616.47
537 m
R-Y 602.7
525 m
Y-B 601.55
4 524 m
B-R 601.55
524 m
R-Y 582.03
507 m
Y-B 580.88
5 506 m
B-R 582.03
507m

NAME DESIGNATION SIGNATURE DATE


TEST ENGR. Suresh M Testing Engr.
BGRESL Rathina Kumar D Dy.Manager
OPGCL
PROJECT: PROJECT: 2 X 660 MW IB THERMAL POWER STATION

TEST REPORT CUM COMISSIONING PROTOCOL


DRY TYPE TRANSFORMER 5
IDCT-PMCC

CLIENT ODHISHA POWER GENERATION CORPORATION LTD Page 6 of 7


EPC-BOP BGR ENERGY SYSTEMS LTD - POWER PROJECT DIVISION Date: 16.6.17

7.2 LV WINDING
Configuration Star Amb Temp
Resistance
Phase Resistance ,Rt (Ohms) Remarks
,R75(Ohms)
R-Y 833 956.28
Y-B 832 955.13
B-R 833 956.28
Acceptance Criteria: Values shall be approximately equal to factory results

8. INSULATION RESISTANCE

Insulation Resistance PI
Winding Combination values
15S 60S 600S
HV+E 6.04G 7.06G 8.03G 1.13
8.04G 12.3G 17.8G 1.14
LV HV

LV E >1G -

Acceptance Criteria: Minimum accepted value


> 100 M ohms for HV to LV + EARTH
> 20 M Ohms for LV to HV + EARTH
> 100 M Ohms for HV to LV

NAME DESIGNATION SIGNATURE DATE


TEST ENGR. Suresh M Testing Engr.
BGRESL Rathina Kumar D Dy.Manager
OPGCL
PROJECT: PROJECT: 2 X 660 MW IB THERMAL POWER STATION

TEST REPORT CUM COMISSIONING PROTOCOL


DRY TYPE TRANSFORMER 5
IDCT-PMCC

CLIENT ODHISHA POWER GENERATION CORPORATION LTD Page 7 of 7


EPC-BOP BGR ENERGY SYSTEMS LTD - POWER PROJECT DIVISION Date: 16.6.17

9. WTI Settings:

Sl No Description of Settings Values


1. Setting of WTI alarm 80 Degree
2. Setting of WTI trip 85 Degree

10. Remarks:
Transformer test results & other protection checks interlocking are found
satisfactory.s

NAME DESIGNATION SIGNATURE DATE


TEST ENGR. Suresh M Testing Engr.
BGRESL Rathina Kumar D Dy.Manager
OPGCL