Hazardous area
Safe area
Ch 2 P I P I Ch 1
+ 6 5 4/20mA 4
4/20mA
I I I I
12 4/20mA 11 10 Ch 1 9 8 7
Ch 2
+ 3
4/20mA
2 1
13
14
20 to 35V dc Vs+ Vs
MTL5549 / MTL5549Y
SPECIFICATION
See also common specification Number of channels Two Location of I/P converter Zone 0, IIC, T46 hazardous area if suitably certified Div. 1, Group A, hazardous location Working range 4 to 20mA Digital signal bandwidth 500Hz to 10kHz Maximum load resistance 800 (16V at 20mA) Minimum load resistance 90 (short-circuit detection at < 50) Output resistance > 1M Under/over range capability Under range = 1mA Over range = 24mA (load 520) Input and output circuit ripple <40A peak-to-peak Communications supported HART Transfer accuracy at 20C Better than 20A Temperature drift < 1.0A/C Input characteristics
Field wiring state Normal Open-circuit Short-circuit MTL4549 < 6.0V < 0.9mA < 0.9mA MTL4549C < 6.0V < 0.9mA N.A. MTL4549Y < 6.0V < 0.5mA N.A.
Hazardous area
Safe area
Ch 2 P I P I Ch 1
4/20mA
+ 6
5 4 2 1
I I I I
7 8 9
Ch 2
4/20mA
+ 3
Ch 1 10 11 12 4/20mA
4/20mA
13 14
Vs Vs+ 20 to 35V dc
LED indicator Green: power indication Maximum current consumption (with 20mA signals into 250 load) 70mA at 24V dc Power dissipation within unit (with 20mA signals into 250 load) 1.6W at 24V Safety description (each channel) Uo =28V Io =93mA Po =0.65W Um = 253V rms or dc SIL capable These models have been assessed for use in IEC 61508 functional safety applications. See data on MTL web site.
The given data is only intended as a product description and should not be regarded as a legal warranty of properties or guarantee. In the interest of further technical developments, we reserve the right to make design changes.