You are on page 1of 1

CONVERSION

1 m = 3.28 ft
1 ft = 0.3048 m
1 mm = 0.03937 in
1 in = 25.4 mm
1 sq m = 10.764 sq ft
1 sq ft = 0.929 sq m
1 cu m = 35.34 cu ft
1 cu ft = 0.0283 cu m
1 m/sec = 196.9 fpm
1 fpm = 0.0051 m/sec
1 cu m/sec = 2119 cfm
1 cfm = 0.000472 cu m/sec
1 cu m/hr = 0.588 cfm
1 cfm = 1.70 cu m/hr
1 l/sec = 2.119 cfm
1 cfm = 0.472 l/sec
1 l/sec = 0.472 l/sec
1 l/sec = 15.81 gpm
1 gpm = 0.063 l/sec
1 kg = 2.2 lb
1 lb = 0.4536 kg
Deg C = 5/9(deg F-32)
Deg F = 9/5 C+32
1 kj = 0.9479 BTU
1 BTU = 1.055 kj
1 MJ = .278 kw.hr
1 kw.hr = 3.60 mj
1 kw = 1.34 Hp
1 Hp = 0.746 kw
1 w = 3.41 BTU/Hr
1 BTU/Hr = 0.2931 w
1 kw = 0.2843 Ton
1 Ton = 3.517 kw
1 kpa = 4.016 in H2O
1 in H2O = 0.2491 kPa
1 kPa = 0.2953 in Hg
1 in Hg = 3.386 kPa
1 kPa = 0.145 psi
1 psi = 6.895 kPa
1 inch = 25.4 mm
1 inch = 2.54 cm
DIGITAL DUCTULATOR (29Sept09)
V = FPM, RATES = CFM/SQ INCH
1500 FPM = 10 CFM/SQ INCH
1200 FPM = 7.56 CFM/SQ INCH
1000 FPM = 6.4 CFM/SQ INCH
900 FPM = 5.92 CFM/SQ INCH
800 FPM = 5.1 CFM/SQ INCH
F = 200 CFM/.003 WG/100FT
FLEXIBLE DUCT
UP TO 80 CFM = 6

81 TO 165 CFM = 8
166 TO 300 CFM = 10
301 TO 490 CFM =12
491 TO 725 CFM = 14
726 TO 1025 CFM = 16
SCD/RCD
UP TO 150 CFM = 6X6
151 TO 300 CFM = 9X9
301 TO 550 CFM = 12X12
551 TO 780 CFM = 15X15
781 TO 1100 CFM = 18X18
1101 TO 1375 CFM = 2121
1376 TO 1800 CFM = 24X24
SLSD/RLSD(3/4 Slot Width)
#Slot/CFM/FACE-mm
1/160/79
2/295/117
3/410/151
4/574/185
5/650/218
6/820/253
7/900/289
8/984/321
CHILLER PIPINGS
GPM = 24XTONS/10 OR DELTA T
Sch 40 Steel Pipes
Recommended H2O Velocity or
Pump Discharge = 8 to 12 fps
How to get size of the Pipes (V=8fps)
= 58.6 gpm/inches of dia of pipes
Recommend Water Velocity
Pump Discharge = 8-12 fps
Pump Suction = 4-7 fps
Drain Line = 4-7 fps
Header = 4-15 fps
Riser = 3-10 fps
General Service = 5-10 fps
City Water = 3-7 fps
PLENUM BOX LSD (Width x
Height)
1 Slot = 10 cm x 20 cm
2 Slot = 14 cm x 29 cm
3 Slot = 28 cm x 32 cm